background image

9

Ex: passing piping out through the front

1.

Plug the areas marked with “ 

 ”. 

(When the piping is routed from the front panel.)

2.

Suction gas side piping

3.

Liquid side piping

4.

Discharge gas side piping

Use a nut with a resin clip plate to protect the nut tightening part from 

rusting.

6. REFRIGERANT PIPING

NOTE

After completing installation, be sure to open the valves. 
(See 

6-6 Additional refrigerant charge

 for details) (Operating the 

unit with the valves shut will break the compressor.)
Use R410A to add refrigerant. (The R410A refrigerant cylinder has a
pink stripe painted around it.)
All field piping must be installed by a licensed refrigeration technician
and must comply with relevant local and national regulations.

• CAUTION TO BE TAKEN WHEN BRAZING REFRIGERANT PIPING

Do not use flux when brazing copper-to copper refrigerant piping. (Par-
ticularly for the HFC refrigerant piping) Therefore, use the phosphor
copper brazing filler metal (B-Cu93P-710/795: ISO 3677) which does
not require flux.
(Flux has extremely harmful influence on refrigerant piping sys-
tems. For instance, if the chlorine based flux is used, it will cause
pipe corrosion or, in particular, if the flux contains fluorine, it will
damage the refrigerant oil.)

Installation tools:
Make sure to use installation tools (gauge manifold charge hose,
etc.) that are exclusively used for R410A installations to withstand
the pressure and to prevent foreign materials (e.g. mineral oils such
as SUNISO and moisture) from mixing into the system.
(The screw specifications differ for R410A.)
Vacuum pump (use a 2-stage vacuum pump with a non-return valve):

1.

Make sure the pump oil does not flow oppositely into the system
while the pump is not working.

2.

Use a vacuum pump which can evacuate to –14.6 psi.

6-1 Selection of piping material

1.

Foreign materials inside pipes (including oils for fabrication) must be
9mg/10ft. or less.

2.

Use the following material specification for refrigerant pipping:

construction material: Phosphoric acid deoxidized seamless cop-
per for refrigerant.

size: Determine the proper size referring to chapter “Example of
connection”.

The wall thickness of the refrigerant piping should comply with
relevant local and national regulations.

3.

Make sure to use the particular branches of piping that have been
selected referring to chapter “Example of connection”.

6-2 Connecting the refrigerant piping

1.

The local branch piping can be connected either forward or to the
sides (taken out of the bottom) as shown in the figure.

1.

Left-side connection

2.

Front connection

3.

Right-side connection

[One outdoor unit installed]

Front connection:
Remove the stop valve cover to connect.

(Refer to figure 6)

Side (bottom) connection:
Remove the knockout holes on the bottom frame and route the pip-
ing under the bottom frame.

[Multiple outdoor units installed]
To connect the piping between outdoor units, an optional piping
kit (multi connection piping kit) is always required. When installing
the piping, follow the instructions in the installation manual that
comes with the kit.

Front connection:
Remove the stop valve cover to connect.

(Refer to figure 6)

Side (bottom) connection:
Remove the knockout holes on the bottom frame and route the pip-
ing under the bottom frame.

(Refer to figure 6)

1.

Front connection

2.

Remove the stop valve cover to connect.

3.

Suction gas side accessory pipe (1) (2) (3)

4.

Discharge gas side accessory pipe (1)(2)(3)

5.

Suction gas line

6.

Liquid line

7.

Oil-equalizing piping stop valve

8.

No piping work is needed.

9.

Flare nut

10.

Discharge gas line

11.

Liquid side piping (field supply)

12.

Side (bottom) connection

13.

Remove the knockout holes on the bottom frame and route
the piping under the bottom frame.

14.

Knockout hole

15.

Punch the knockout holes.

16.

Discharge gas piping (field supply)

17.

Liquid piping (field supply)

18.

Suction gas piping (field supply)

19.

Oil-equalizing piping (field supply)

20.

Same as above

NOTE

Be sure to use the attached pipe when carrying out piping work in
the field.

Be sure that the local piping does not touch other pipes,  the
bottom panel or side panel. Especially for the bottom  and
side connection, be sure to protect the local piping with the
provided insulation, to prevent it from coming into contact
with the casing.

1

2

3

4

Resin clip plate

1

2

3

01_EN_3P114261-10Y.fm  Page 9  Thursday, June 16, 2005  3:14 PM

Summary of Contents for REYQ192MTJU

Page 1: ...EL REYQ96MTJU REYQ192MTJU Read these instructions carefully before installation Keep this manual in a handy place for future reference This manual should be left with the equipment owner 00_CV_3P11426...

Page 2: ...al 1 1 2 2 1 3 1 1 1 1 in H1 59 H1 59 X H2 19 5 8 H2 19 5 8 Y A 19 5 8 A 19 5 8 X 2 B1 11 3 4 B2 3 7 8 B1 11 3 4 Y 2 B2 3 7 8 Y 2 60 5 3 1 4 2 2 in 40 4 0 40 6 0 60 60 6 3 5 7 3 4 1 2 8 28 7 16 29 3 1...

Page 3: ...stalled 2 1 3 5 6 8 4 7 One outdoor unit installed One outdoor unit installed 1 2 4 5 6 3 7 1 2 4 5 6 3 1 2 3 4 5 6 7 8 9 16 10 11 15 14 12 17 13 1 2 3 4 5 6 13 18 12 20 16 16 9 10 11 17 8 19 7 1 2 3...

Page 4: ...1 2 3 5 7 10 8 1 4 6 9 2 3 1 2 1 2 3 4 5 A B C F1 F2 F1 F2 Q1 Q2 A B C F1 F1 F2 F2 Q1 Q2 2 1 C H SELECTOR TO IN D UNIT TO OUT D UNIT TO MULTI UNIT A1P IN D OUT D BS F1 F1 F2 F2 F1 F2 F1 F2 F1 F2 F1 F2...

Page 5: ...e unit on a foundation strong enough to withstand the weight of the unit A foundation of insufficient strength may result in the equipment falling and causing injuries Carry out the specified installa...

Page 6: ...t that the outdoor unit be used as a shelter by small ani mals Small animals making contact with electrical parts can cause mal functions smoke or fire Please instruct the customer to keep the area ar...

Page 7: ...lamp 1 Clamp 2 Clamp 3 Suction gas line piping attached to unit 1 Quantity 9 pcs 2 pcs 1 pc 1 pc Shape Name Suction gas line piping attached to unit 2 Suction gas line piping attached to unit 3 Discha...

Page 8: ...AND HANDLING THE UNIT At delivery the package should be checked and any damage should be reported immediately to the carrier claims agent When handling the unit take into account the following 1 Fragi...

Page 9: ...size referring to chapter Example of connection The wall thickness of the refrigerant piping should comply with relevant local and national regulations 3 Make sure to use the particular branches of pi...

Page 10: ...ate adversely affecting the refrigerant piping system NOTE The pressure regulator for the nitrogen released when doing the brazing should be set to 2 9 psi or less Refer to figure 9 1 Refrigerant pipi...

Page 11: ...topping outdoor unit Change to pattern 1 or pattern 2 UnitA Unit B Unit B UnitA to indoor unit Change as shown in the figure below to indoor unit to indoor unit to indoor unit Oilcollectstotheoutdooru...

Page 12: ...er of outdoor units Branch kit name Outdoor unit capacity type Refrigerant branch kit name indoor capacity index Refrigerant branch kit name In case of 3 pipes In case of 2 pipes 1 15 _ If the outdoor...

Page 13: ...ly excessive force to the stop valve Doing so may break the valve body as the valve is not a backseat type Always use the special tool 3 Make sure to tighten the cap securely Closing stop valve 1 Remo...

Page 14: ...n unsuitable substance may cause explosions and accidents so always ensure that the appropriate refrigerant R410A is charged Refrigerant containers shall be opened slowly Always use protective gloves...

Page 15: ...or the power cord 7 2 Power circuit and cable requirements A power circuit see table below must be provided for connection of the unit This circuit must be protected with the required safety devices i...

Page 16: ...wire 10 When wiring exercise sufficient caution not to detach the acoustic insulators from the compressor CAUTION Precautions when laying power wiring Use round pressure terminals for connections to t...

Page 17: ...necting wiring between the outdoor units in the same pipe line must be connected to the Q1 Q2 Out Multi terminals Con necting the wires to the Out Out terminals results in system mal function The wiri...

Page 18: ...the configuration on the parent unit Any settings made on a child unit will be ignored Always perform configuration after turning ON the power To learn the setting method refer to the Service Precauti...

Page 19: ...f refrigerant Ib charged to each system separately NOTE Where a single refrigerant facility is divided into 2 entirely indepen dent refrigerant systems then use the amount of refrigerant with which ea...

Page 20: ...1645 Wallace Drive Suite 110 Carrollton TX 75006 info daikinac com www daikinac com 3P114261 10Y EM04A002A 0506 HT 00_CV_3P114261 10Y fm Page 5 Thursday June 16 2005 4 31 PM...

Reviews: