Installation manual

9

R REMQ10~16P8 + REMHQ12P8Y1B

VRVIII System air conditioner

4PW48463-1A

6.6.

Example of connection

Example of connection

(Connection of 8 indoor units)

Branc

h with refnet joint

Branc

h with refnet joint and refnet header

Branc

h with refnet header

Outdoor units installed 

in a m

ultiple outdoor 

unit system 

(REYQ18~48 +

R

REYHQ20~24)

Install the joint par

t (

 par

t in the figure) of the outdoor unit m

ulti connection piping kit 

hor

iz

ontally with attention to the installation restr

ictions descr

ibed in "connecting the 

refr

iger

ant piping".

(*) In case of m

ulti combination, inter

prete the w

ord "outdoor" as "first outdoor 

br

anch".

Maxim

um allo

wab

le 

length

Betw

een outdoor and indoor units

Actual pipe length

Pipe length betw

een outdoor(*) and indoor units 

165 m

[Example] unit 8:

 a+b+c+d+e+s

165 

m

[Example] unit 6:

 a+b+l

165 m, 

unit 8:

 a+m+n+p

165 m

[Example] unit 8:

 a+o

165 m

Equiv

alent length

Equiv

alent pipe length betw

een outdoor(*) and indoor units 

190 m (Assume equiv

alent pipe length of the refnet joint to be 0.5 m, of the refnet header to be 1.0 m, 

of the BSVQ100 and BSVQ160 to be 4 m and of the BSVQ250 to be 6 m (f

or calculation pur

poses)) (See note 1)

T

otal e

xtension length

T

otal piping length from outdoor(*) to all indoor units 

1000 m

Betw

een the first outdoor unit m

ulti connection piping kit 

and outdoor unit (in case of a m

ultiple outdoor unit system)

Actual and equiv

alent 

pipe length

The actual pipe length from the first outdoor unit m

ulti connection piping kit to the outdoor unit 

10 m.

 (x

10 m, y

10 m, z

10 m)

The equiv

alent pipe length from the first outdoor unit m

ulti connection piping kit to the outdoor unit 

13 m.

 (x

13 m, y

13 m, z

13 m)

Allo

wab

le height 

diff

erence

Betw

een outdoor and indoor units

Diff

erence in height betw

een outdoor and indoor units (H1)

50 m (

40 m if outdoor unit is located in a lo

w

er position).

Betw

een indoor and indoor units

Diff

erence in height betw

een adjacent indoor units (H2)

15 m

Betw

een outdoor and outdoor units

Diff

erence in height betw

een adjacent outdoor units (H3)

5 m

Allo

wab

le length after the branc

h

Actual pipe length

Pipe length from first refr

iger

ant br

anch kit (either refnet joint or refnet header) to indoor unit 

40 m (See note 2)

[Example] unit 8:

 b+c+d+e+s

40 m

[Example] unit 6:

 b+l

40 m, unit 8:

 m+n+p

40 m

[Example] unit 8:

 o

40 m

Outdoor unit m

ulti connection piping kit and refrigerant branc

h kit selection 

Ho

w to select the refnet joint

When using refnet joints at the first br

anch counted from the outdoor unit side

, choose from 

the f

ollo

wing tab

le in accordance with the capacity of the outdoor unit (e

xample:

 refnet joint 

A).

Ho

w to select the refnet header

Choose from the f

ollo

wing tab

le in accordance with the total capacity of all the indoor units connected 

belo

w the refnet header.

Note

250 type indoor unit can not be connected low

er than the refnet header.

Outdoor unit 

capacity type (Hp)

Refrig

erant branc

h kit name

Indoor 

capacity type

Refrig

erant branc

h kit name

3 pipes

2 pipes

8+10

KHRQ23M29T

<200

KHRQ23M29H KHRQ22M29H

12~22

KHRQ23M64T

200

x<290

KHRQ23M29H KHRQ22M29H

24

KHRQ23M75T

290

x<640

KHRQ23M64H

KHRQ22M64H

F

or refnet joints other than the first br

anch, select the proper br

anch kit model based on the 

total capacity inde

x of all indoor units connected after the refr

iger

ant br

anch.

640

KHRQ23M75H KHRQ22M75H

Ho

w to c

hoose an outdoor m

ulti connection piping kit (this is required when the 

system is a m

ultiple outdoor unit system)

Indoor 

capacity type

Refrig

erant branc

h kit name

3 pipes

2 pipes

Choose from the f

ollo

wing tab

le in accordance with the number of outdoor units

<200

KHRQ23M20T

KHRQ22M20T

Number of 

outdoor units

Branc

h kit name

200

x<290

KHRQ23M29T9

KHRQ22M29T

290

x<640

KHRQ23M64T

KHRQ22M64T

2

BHFQ23P907

640

KHRQ23M75T

KHRQ22M75T

3

BHFQ23P1357

Example of do

wnstream indoor units

[Example]

in case of refnet joint C:

 indoor units 5+6+7+8

[Example]

in case of refnet joint B:

 indoor units 7+8,

in case of refnet header:

 indoor units 1+2+3+4+5+6

[Example]

in case of refnet header:

 indoor units 

1+2+3+4+5+6+7+8

Use the outdoor unit m

ulti connection piping kit that is sold separ

ately 

as an option (BHF1357) f

or the m

ulti installation of outdoor 

units

. Selection method is as sho

wn in the r

ight tab

le

.

AB

C

D

E

ab

c

d

e

8

H2

H1

H3

f

ln

p

B1

B2

B3

B4

xy

z

F

h

1

g

G

j

2

k

mo

q

r

s

3

i

4

5

6

7

A

B

am

H2

H1

H3

b

B1

B2

B3

B4

n

p

xy

z

d

1

fh

g

j

i

kl

o

2

3

4

5

6

7

8

ce

B5

a

H2

H1

H3

B1

B2

B3

B4

xy

z

c

1

eg

f

i

hj

l

no

2

3

4

5

6

7

8

k

bd

B2

B3

m

Outdoor unit side (3 pipes)

Indoor unit side (2 pipes)

Suction gas pipe

Gas pipe

HP/LP gas pipe

BS unit

Liquid pipe

Liquid pipe

indoor unit

refnet header

Outdoor unit side (3 pipes)

refnet joint

outdoor m

ulti connection piping kit

Indoor unit side (2 pipes)

Refr

iger

ant br

anch kits can only be used with R410A.

Summary of Contents for REMQ8P9Y1B

Page 1: ...INSTALLATION MANUAL REMQ8P9Y1B REMQ10P8Y1B REM H Q12P8Y1B REMQ14P8Y1B REMQ16P8Y1B System air conditioner...

Page 2: ...mm d 500 mm a 50 mm b 100 mm c 50 mm d 500 mm a 200 mm b 300 mm a 10 mm b 300 mm c 10 mm d 500 mm e 20 mm a 50 mm b 100 mm c 50 mm d 500 mm e 100 mm a 200 mm b 300 mm e 400 mm a 10 mm b 300 mm c 10 mm...

Page 3: ...500 mm 1 1 1 A B 2 2 2 4 5 3 8 F1 F2 F1 F2 Q1 Q2 F1 F1 F2 F2 Q1Q2 7 TOIN DUNIT TOOUT DUNIT TOMULTIUNIT A1P Q1 Q2 A1P Q1 Q2 A1P 1 2 2 3 4 5 6 8 10 10 9 9 REMQ8 12 REMQ14 16 REMHQ12 1 2 3 4 1 5 6 7 8 F...

Page 4: ...uz uvjet da se oni koriste u skladu s na im uputama 16 megfelelnek az al bbi szabv ny ok nak vagy egy b ir nyad dokumentum ok nak ha azokat el r s szerint haszn lj k 17 spe niaj wymogi nast puj cych...

Page 5: ...ll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi 14 Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS TSmin...

Page 6: ...75 kW For changing the refrigerant flow to indoor units the REYQ P system can be combined with BS units of the types BSVQ100P BSVQ160P and BSVQ250P only Other BS unit types will cause malfunctions whe...

Page 7: ...REYQ48 REMQ16 REMQ16 REMQ16 600 1560 Standard combinations of outdoor units Total capacity of indoor units REYHQ16 REMQ8 REMQ8 200 520 REYHQ20 REMQ8 REMHQ12 250 650 REYHQ22 REMQ10 REMHQ12 275 715 REY...

Page 8: ...owable safety limits in the event of a refrigerant leak 11 To prevent dripping water to form a puddle underneath the unit install a drain pan available as option kit 12 The equipment is not intended f...

Page 9: ...The height of the foundation must at least be 150 mm from the floor The unit must be installed on a solid longitudinal foundation steelbeam frame or concrete and make sure the base under the unit is...

Page 10: ...piping must be installed by a licensed refrigeration technician and must comply with relevant local and national regulations Caution to be taken when brazing refrigerant piping Do not use flux when b...

Page 11: ...lves are fully closed 2 Connect a charge hose to service ports of all stop valves 3 Recover gas and oil from the pinched piping by using a recovery unit 4 When all gas and oil is recovered from the pi...

Page 12: ...ns The piping between the outdoor units must be routed level or slightly upward to avoid the risk of oil retention into the piping side Pattern 1 Pattern 2 Prohibited patterns change to pattern 1 or 2...

Page 13: ...ation may lead to malfunction of the outdoor unit 5 Piping length restrictions Make sure to perform the piping installation within the range of the maximum allowable pipe length allowable level differ...

Page 14: ...40 m Outdoor unit multi connection piping kit and refrigerant branch kit selection How to select the refnet joint When using refnet joints at the first branch counted from the outdoor unit side choose...

Page 15: ...of the connected outdoor unit Suction gas pipe Liquid pipe 20 25 32 40 50 12 7 6 4 Outdoor unit capacity type Hp Piping outer diameter size mm 63 80 100 125 15 9 9 5 Suction gas pipe HP LP gas pipe Li...

Page 16: ...ncreased to 90 m Size up of the main suction gas pipe may affect a good oil return to the outdoor unit due to influence of the HP LP gas pipe indoor unit 8 b c d e f g p 90 m increase the pipe size of...

Page 17: ...fan PS Switching power supply A1P A3P Q1DI Earth leakage breaker field supply Q1RP Phase reversal detection circuit R1T Thermistor air A1P fin A3P R3T R9T Thermistor H E gas H E de icer sub cool H E g...

Page 18: ...for connection wiring to indoor outdoor transmission F1 F2 outdoor outdoor transmission F1 F2 outdoor multi transmission Q1 Q2 and on how to use BS1 BS5 and DS1 DS2 switch Do not operate the unit by s...

Page 19: ...eans that an earth leakage breaker capable of handling high frequency electrical noise must be used in order to prevent malfunctioning of the earth leakage breaker itself Earth leakage breakers that a...

Page 20: ...he back of the electric box lid 2 Power wiring and ground wiring between outdoor units inside conduit When the wiring is routed out through the lateral panel 3 Transmission wiring 4 Pipe opening 5 Con...

Page 21: ...nsmission wiring between outdoor units 1 Liquid pipe 2 HP LP gas pipe 3 Finishing tape 4 Suction gas pipe 5 Transmission wiring 6 Insulation material 1 Power supply 380 415 V 3N 50 Hz 2 Earth leakage...

Page 22: ...igerant follow the procedure as described in this chapter 11 1 Important information regarding the refrigerant used This product contains fluorinated greenhouse gases covered by the Kyoto Protocol Do...

Page 23: ...its that are active can be read from the LED display in the Monitor Mode procedure below NOTE National implementation of EU regulation on certain fluorinated greenhouse gases may require to provide th...

Page 24: ...button to return to step 1 setting mode 1 H1P x OFF Adding refrigerant using the automatic refrigerant charging function is recommended When charging a system charging over the permissible quantity ca...

Page 25: ...BS unit indoor unit 13 Stop valve 14 Service port 15 Field piping 16 Refrigerant flow when pre charging through the liquid stop valve service port refer to step 3 on page 19 17 Refrigerant flow when...

Page 26: ...to confirm that charging is completed Record the amount that was added on the additional refrigerant charge label provided with the unit and attach it on the back side of the front panel Perform the p...

Page 27: ...c x x w x x x x w Slave unit 1 a c x x x x x x x c Slave unit 2 a c x x x x x x x x Error code P8 recharge operation Close valve A immediately and press the TEST OPERATION button once The operation w...

Page 28: ...rocedure from step 2 onwards Make sure to open the stop valves after charging the refrigerant Operating with the stop valves closed will damage the compressor BS1 MODE BS1 MODE WARNING ELECTRIC SHOCK...

Page 29: ...tch which is located on the outdoor unit PCB A1P The figure shows state of the LED indications when the unit is shipped from the factory Check operation procedure 1 Turn the power on for the outdoor u...

Page 30: ...state x normal w abnormal c under preparation or under test operation 2 Indication of low noise operation state x standard operation factory setting w operation 3 Indication of power consumption limi...

Page 31: ...arts During the test operation the refrigerant running sound or the magnetic sound of a solenoid valve may become loud and the LED display may change but these are not mal functions During the test op...

Page 32: ...gerant charge hose to the refrigerant charging port for additionaly charging 4 When the unit is not operating push the button until the additional refrigerant charging operation function A in setting...