background image

R REMQ10~16P8 + REMHQ12P8Y1B

VRVIII System air conditioner

4PW48463-1A

Installation manual

26

12.4. Test operation

In case the unit is operated with the leak detection function
available:

the outdoor temperature must be 0°C DB~43°C DB

the indoor temperature must be 20°C DB~32°C DB

In case the unit is operated out of the temperature range as
instructed above, the display of the remote controller shows 

U3

and the unit operates without the availability of the leak detection
function.

In the test operation, the following checks and judgement will be
performed:

Check of the stop valve opening

Check for wrong wiring

Check of refrigerant overcharge

Initial refrigerant detection

In case the leak detection function is available, the check
operation will last 2 hours, otherwise it takes between 40 and
60 minutes to complete the check operation.

Make sure to carry out the test operation after the first
installation. Otherwise, the malfunction code 

U3

 will be displayed

on the remote controller and normal operation can not be
carried out.

In case of a multi system, check the settings and results on the
master unit.

Abnormalities on indoor units can not be checked for each unit
individual. After the test operation is finished, check the indoor
units one by one by performing a normal operation using the
remote controller.

Test operation procedure

1

Close all front panels except the front panel of the electric box.

2

Turn ON the power to all outdoor units and the connected indoor
units.

Be sure to turn on the power 6 hours before operation in order to
have power running to the crank case heater and to protect the
compressor.

3

Make the field setting as described in the paragraph 

"12.3. Field

setting" on page 24

.

4

Press the 

 button once, and set to the SETTING

MODE (H1P LED = OFF).

5

In case the leak detection function is required,
press and hold the 

 button down for 5 seconds or

more. The unit will start the test operation.

In case the leak detection function is not required,
go into setting mode 2 by pressing the 

 button for 5

seconds. The H1P LED is on 

w

. Perform following steps.

1.

Press the 

 button 3 times.

2.

Press the 

 button once to confirm.

3.

Press the 

 button in order to change the LED

display to the following display.

4.

Press the 

 button once to confirm.

5.

Press the 

 button a second time to start the

test operation. The unit will start the test operation.

The test operation is automatically carried out in cooling
mode, the H2P LED will light up and the messages "Test
operation" and "Under centralized control" will display on the
remote controller.

It may take 10 minutes to bring the state of the refrigerant
uniform before the compressor starts.

During the test operation, the refrigerant running sound or
the magnetic sound of a solenoid valve may become loud
and the LED display may change, but these are not mal-
functions.

During the test operation, it is not possible to stop the unit
operation from a remote controller. To abort the operation,
press the 

 button. The unit will stop after

±30 seconds.

6

Close the front panel in order to let it not be the cause of
misjudgement.

7

Check the test operation results by the LED display on the
outdoor unit.

8

When the test operation is fully completed, normal operation will
be possible after 5 minutes. 

Otherwise, refer to 

"Correcting after abnormal completion of the

test operation" on page 26

  to take actions for correcting the

abnormality.

Correcting after abnormal completion of the test operation

The test operation is only completed if there is no malfunction code
displayed on the remote controller. In case of a displayed malfunction
code, perform the following actions to correct the abnormality:

Confirm the malfunction code on the remote controller

Do not insert fingers, rods or other objects into the air
inlet or outlet. When the fan is rotating at high speed, it
will cause injury.

Do not perform the test operation while working on the
indoor units.

When performing the test operation, not only the outdoor
unit, but the connected indoor unit will operate as well.
Working on a indoor unit while performing a test operation
is dangerous.

NOTE

A test operation can not be carried out when the
outdoor temperature is less than –5°C.

H1P

H2P

H3P

H4P

H5P

H6P

H7P

w x

x

x

x w w

BS1  MODE

BS4  TEST

BS1  MODE

BS2  SET

H1P

H2P

H3P

H4P

H5P

H6P

H7P

w x

x

x

x

x c

H1P

H2P

H3P

H4P

H5P

H6P

H7P

w x

x

x

x c x

H1P

H2P

H3P

H4P

H5P

H6P

H7P

Normal completion

x

x w x

x

x

x

Abnormal completion

x w w x

x

x

x

Installation error

Error code

Remedial action

The stop valve of an 
outdoor unit is left 
closed.

E3

E4

F3

F6

UF

Open the stop valve.

The phases of the 
power to the outdoor 
units are reversed.

U1

Exchange two of the three phases 
(L1, L2, L3) to make a positive 
phase connection.

No power is supplied 
to an outdoor or 
indoor unit (including 
phase interruption).

LC

U1

U4

Check if the power wiring for the 
outdoor units are connected 
correctly.

Incorrect 
interconnections 
between units

UF

Check if the refrigerant line piping 
and the unit wiring are consistent 
with each other.

Refrigerant 
overcharge

E3

F6

UF

Recalculate the required amount of 
refrigerant from the piping length 
and correct the refrigerant charge 
level by recovering any excessive 
refrigerant with a refrigerant 
recovery machine.

Insufficient refrigerant

E4

F3

Check if the additional refrigerant 
charge has been finished correctly.
Recalculate the required amount of 
refrigerant from the piping length 
and add an adequate amount of 
refrigerant.

BS3  RETURN

BS2  SET

BS3  RETURN

BS3  RETURN

BS3  RETURN

Summary of Contents for REMQ8P9Y1B

Page 1: ...INSTALLATION MANUAL REMQ8P9Y1B REMQ10P8Y1B REM H Q12P8Y1B REMQ14P8Y1B REMQ16P8Y1B System air conditioner...

Page 2: ...mm d 500 mm a 50 mm b 100 mm c 50 mm d 500 mm a 200 mm b 300 mm a 10 mm b 300 mm c 10 mm d 500 mm e 20 mm a 50 mm b 100 mm c 50 mm d 500 mm e 100 mm a 200 mm b 300 mm e 400 mm a 10 mm b 300 mm c 10 mm...

Page 3: ...500 mm 1 1 1 A B 2 2 2 4 5 3 8 F1 F2 F1 F2 Q1 Q2 F1 F1 F2 F2 Q1Q2 7 TOIN DUNIT TOOUT DUNIT TOMULTIUNIT A1P Q1 Q2 A1P Q1 Q2 A1P 1 2 2 3 4 5 6 8 10 10 9 9 REMQ8 12 REMQ14 16 REMHQ12 1 2 3 4 1 5 6 7 8 F...

Page 4: ...uz uvjet da se oni koriste u skladu s na im uputama 16 megfelelnek az al bbi szabv ny ok nak vagy egy b ir nyad dokumentum ok nak ha azokat el r s szerint haszn lj k 17 spe niaj wymogi nast puj cych...

Page 5: ...ll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi 14 Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS TSmin...

Page 6: ...75 kW For changing the refrigerant flow to indoor units the REYQ P system can be combined with BS units of the types BSVQ100P BSVQ160P and BSVQ250P only Other BS unit types will cause malfunctions whe...

Page 7: ...REYQ48 REMQ16 REMQ16 REMQ16 600 1560 Standard combinations of outdoor units Total capacity of indoor units REYHQ16 REMQ8 REMQ8 200 520 REYHQ20 REMQ8 REMHQ12 250 650 REYHQ22 REMQ10 REMHQ12 275 715 REY...

Page 8: ...owable safety limits in the event of a refrigerant leak 11 To prevent dripping water to form a puddle underneath the unit install a drain pan available as option kit 12 The equipment is not intended f...

Page 9: ...The height of the foundation must at least be 150 mm from the floor The unit must be installed on a solid longitudinal foundation steelbeam frame or concrete and make sure the base under the unit is...

Page 10: ...piping must be installed by a licensed refrigeration technician and must comply with relevant local and national regulations Caution to be taken when brazing refrigerant piping Do not use flux when b...

Page 11: ...lves are fully closed 2 Connect a charge hose to service ports of all stop valves 3 Recover gas and oil from the pinched piping by using a recovery unit 4 When all gas and oil is recovered from the pi...

Page 12: ...ns The piping between the outdoor units must be routed level or slightly upward to avoid the risk of oil retention into the piping side Pattern 1 Pattern 2 Prohibited patterns change to pattern 1 or 2...

Page 13: ...ation may lead to malfunction of the outdoor unit 5 Piping length restrictions Make sure to perform the piping installation within the range of the maximum allowable pipe length allowable level differ...

Page 14: ...40 m Outdoor unit multi connection piping kit and refrigerant branch kit selection How to select the refnet joint When using refnet joints at the first branch counted from the outdoor unit side choose...

Page 15: ...of the connected outdoor unit Suction gas pipe Liquid pipe 20 25 32 40 50 12 7 6 4 Outdoor unit capacity type Hp Piping outer diameter size mm 63 80 100 125 15 9 9 5 Suction gas pipe HP LP gas pipe Li...

Page 16: ...ncreased to 90 m Size up of the main suction gas pipe may affect a good oil return to the outdoor unit due to influence of the HP LP gas pipe indoor unit 8 b c d e f g p 90 m increase the pipe size of...

Page 17: ...fan PS Switching power supply A1P A3P Q1DI Earth leakage breaker field supply Q1RP Phase reversal detection circuit R1T Thermistor air A1P fin A3P R3T R9T Thermistor H E gas H E de icer sub cool H E g...

Page 18: ...for connection wiring to indoor outdoor transmission F1 F2 outdoor outdoor transmission F1 F2 outdoor multi transmission Q1 Q2 and on how to use BS1 BS5 and DS1 DS2 switch Do not operate the unit by s...

Page 19: ...eans that an earth leakage breaker capable of handling high frequency electrical noise must be used in order to prevent malfunctioning of the earth leakage breaker itself Earth leakage breakers that a...

Page 20: ...he back of the electric box lid 2 Power wiring and ground wiring between outdoor units inside conduit When the wiring is routed out through the lateral panel 3 Transmission wiring 4 Pipe opening 5 Con...

Page 21: ...nsmission wiring between outdoor units 1 Liquid pipe 2 HP LP gas pipe 3 Finishing tape 4 Suction gas pipe 5 Transmission wiring 6 Insulation material 1 Power supply 380 415 V 3N 50 Hz 2 Earth leakage...

Page 22: ...igerant follow the procedure as described in this chapter 11 1 Important information regarding the refrigerant used This product contains fluorinated greenhouse gases covered by the Kyoto Protocol Do...

Page 23: ...its that are active can be read from the LED display in the Monitor Mode procedure below NOTE National implementation of EU regulation on certain fluorinated greenhouse gases may require to provide th...

Page 24: ...button to return to step 1 setting mode 1 H1P x OFF Adding refrigerant using the automatic refrigerant charging function is recommended When charging a system charging over the permissible quantity ca...

Page 25: ...BS unit indoor unit 13 Stop valve 14 Service port 15 Field piping 16 Refrigerant flow when pre charging through the liquid stop valve service port refer to step 3 on page 19 17 Refrigerant flow when...

Page 26: ...to confirm that charging is completed Record the amount that was added on the additional refrigerant charge label provided with the unit and attach it on the back side of the front panel Perform the p...

Page 27: ...c x x w x x x x w Slave unit 1 a c x x x x x x x c Slave unit 2 a c x x x x x x x x Error code P8 recharge operation Close valve A immediately and press the TEST OPERATION button once The operation w...

Page 28: ...rocedure from step 2 onwards Make sure to open the stop valves after charging the refrigerant Operating with the stop valves closed will damage the compressor BS1 MODE BS1 MODE WARNING ELECTRIC SHOCK...

Page 29: ...tch which is located on the outdoor unit PCB A1P The figure shows state of the LED indications when the unit is shipped from the factory Check operation procedure 1 Turn the power on for the outdoor u...

Page 30: ...state x normal w abnormal c under preparation or under test operation 2 Indication of low noise operation state x standard operation factory setting w operation 3 Indication of power consumption limi...

Page 31: ...arts During the test operation the refrigerant running sound or the magnetic sound of a solenoid valve may become loud and the LED display may change but these are not mal functions During the test op...

Page 32: ...gerant charge hose to the refrigerant charging port for additionaly charging 4 When the unit is not operating push the button until the additional refrigerant charging operation function A in setting...

Page 33: ...heavier than air Procedure for checking maximum concentration Check the maximum concentration level in accordance with steps 1 to 4 below and take whatever action is necessary to comply 1 Calculate th...

Page 34: ...P8 REMHQ12P8Y1B VRVIII System air conditioner 4PW48463 1A 16 DISPOSAL REQUIREMENTS Dismantling of the unit treatment of the refrigerant of oil and of other parts must be done in accordance with releva...

Page 35: ...3 2 6 6 6 6 23 18 9 8 1 2 4 3 5 13 14 15 10 7 12 19 2 1 24 6 11 16 17 15 6 5 10 11 12 7 4 9 16 17 18 3 8 13 14 2 2 1 1 9 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6...

Page 36: ...4PW48463 1A Copyright Daikin...

Reviews: