Troubleshooting by Remote Controller
Si20-701_B
87
Troubleshooting
Are
fan motor
connectors properly
connected?
NO
YES
Connect
correctly.
With
connectors
unplugged and
the power supply
turned ON, is there
about 12 VDC between
pins 1 and 3 of fan
motor
connectors.
NO
YES
Replace the
indoor unit PCB.
Check the indoor
unit fan motor
and motor wiring.
Caution
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
may be damaged.