Troubleshooting by Remote Controller
Si20-701_B
393
Is HAP
on the outdoor
unit PCB blinking?
(Outdoor unit
PCB)
Is
the power
for the optional
accessory supplied
from between 1 and 2
on terminal
block
X2M?
NO
NO
YES
Wire correctly.
YES
Replace the
outdoor unit fan
motor.
NO
Replace the
outdoor unit fan
motor.
YES
Is any
optional
accessory (
∗
1)
connected?
NO
NO
YES
YES
Turn OFF the power
supply and disconnect the
connector of the outdoor
unit fan motor. Then
power ON again.
Check the resistance
value of the outdoor unit
fan motor.
Is HAP
blinking? (Outdoor
unit PCB)
Is the
resistance
value of the outdoor
unit fan motor
normal?
A
B
C