Troubleshooting by Remote Controller
Si20-701_B
193
NO
NO
With the
connector
disconnected from
the fan motor, the fan
cannot be
rotated by
hand.
Connectors of
harness between
the compressor
inverter PCB and the
fan inverter PCB are
disconnected.
The
fuse
(white tubular
fuse) on the fan
inverter PCB has a
broken wire (has
no continuity).
YES
Insert the
connectors in the
harness.
YES
Replace the fan
inverter PCB.
YES
Replace the
outdoor unit fan
motor.
NO
NO
Resistance
between the fan
motor power supply
cable terminal and the
motor frame (metal
part) is not
more than
1M
Ω
.
YES
Replace the
outdoor unit fan
motor.
A