Si20-701_B
Troubleshooting by Remote Controller
252
3.52
J7
Liquid Pipe Thermistor
Abnormality
Remote Controller Display
J7
Applicable Models
CMSQ
Method of Error Detection
The error is detected according to the temperature
detected by liquid pipe thermistor.
Error Decision Conditions
When the liquid pipe thermistor is short circuited or open
circuited
Supposed Causes
Defective liquid pipe thermistor (R6T)
Defective outdoor unit PCB
Defective thermistor connection