![background image](http://html1.mh-extra.com/html/daikin/r71fuv1/r71fuv1_service-manual_4188538118.webp)
Troubleshooting by Remote Controller
Si20-701_B
111
Troubleshooting
NO
The error
is displayed again.
Is the
capacity setting
adaptor connected to
the indoor unit
PCB?
Install a capacitor setting
adaptor that matches the
capacity of the indoor unit.
YES
YES
Turn OFF the power
supply and turn the power
ON.
NO
The error was
caused by a
missing capacity
resistor.
Replace the
indoor unit PCB.
Caution
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
may be damaged.