Troubleshooting by Remote Controller
Si20-701_B
271
Troubleshooting
Can it be
considered that
the radiation fin
temperature was
high? (
∗
1)
YES
NO
YES
NO
Eliminate the
cause.
Turn ON the power
supply, and then press
the remote controller
check button once.
Caution
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
may be damaged.
Is the
connector of
the radiation fin
thermistor correctly
connected to the
outdoor unit
PCB? (
∗
1)
NO
Connect
correctly.
Is the error
"
P4
" displayed on
the remote
controller?
YES
Go to
troubleshooting
"
P4
".
A
B
RZQ(S)-C