ESIE19-06
|
Part 5. Appendix
5.2. Wiring diagram
Modular L Smart
Page 80
21/01/20
|
Version 1.1
5.2. Wiring diagram
5.2.1. HRV unit
5.2.1.1. Legend
Figure 5-13: Legend
5.2.1.2. Unit layout
Figure 5-14: Unit layout - Bottom view
5.2.1.3. Power supply and fan-S fan-R size 02 to 05
Figure 5-15: Power supply and fan-S fan-R size 02 to 05
4
3
1
2
ROOM AIR
SUPPLY AIR
FRESH AIR
EXHAUST AIR
Right connection
Left connection
3
4
2
1
FRESH AIR
EXHAUST AIR
ROOM AIR
SUPPLY AIR
EXTERNAL POWER SUPPLY
230V 1ph 50/60Hz
GND
0-10V
GND
0-10V
COM
NC
COM
NC
UNIT SIZE
Q1DI (EXTERNAL)
02 to 05
2P - 230...400Vac - 13A - type F - "C" - 10kA -
I
ǻQ
=300mA
06 & 07
-
2P - 230...400Vac - 16A - type F - "C" - 10kA -
I
ǻQ
=300mA
UNIT SIZE
N°. FANS & AMPS
02
MAX UNIT AMPS
2 x (1,35A)
2,9A
03 - 04
2 x (2,2A)
4,6A
05
2 x (2,3A)
4,8A
06
4 x (2,2A)
9,0A
07
4 x (2,3A)
9,4A