ESIE19-06
|
Part 5. Appendix
5.1. Field setting
Modular L Smart
21/01/20
|
Version 1.1
Page 65
Setting
mode
Setting
switch
no.
Setting
description
Setting position no.
Setting position no.
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
17(27)
0
Filter cleaning
time setting
Approx. 2500
hours
±1250 hours
1
Nigh-time free
cooling timer
(after stop)
Off
On after 2
hours
On after 4
hours
On after 6
hours
On after 8
hours
2
Pre-cool/
pre-heat
Off
On
3
Pre-cool/
pre-heat duration
30 minutes
45 minutes
60 minutes
4
Initial fan speed
High
Ultra-high
5
Yes/No setting for
duct connection
with VRV system
Without duct
With duct
Without duct
With duct
Setting for cold
areas (fan
operation when
heater thermostat
is off)
Stop
Low
Stop
Low
6
Night-time free
cooling (fan
settings)
High
Ultra-high
7
Target
temperature for
independent
Nigh-time free
cooling
18°C
19°C
20°C
21°C
22°C
23°C
24°C
25°C 26°C 27°C 28°C 29°C 30°C
8
Centralised zone
interlock setting
No
Yes
9
Pre-heat time
extension setting
0 minutes
30 minutes
60 minutes
90 minutes
Setting
mode
Setting
switch
no.
Setting
description
Setting position no.
Setting position no.
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
18(28)
0
External signal
JC/J2
Last
command
Priority on
external input
Priority on
operation
Disable
night-time
free cooling /
Forced stop
24 hours
ventilation
On/off
1
Setting for direct
Power
Off
On
2
Autorestart setting
Off
On
3
Output signal to
external damper
(X24A)
Damper
output (fan
operation)
Damper
output (fan
operation)
4
Indication of
ventilation mode
On
Off
6
Automatic
ventilation air flow
mode
Linear
Fixed A
Fixed B
7
Fresh-up mode
No indication
supply
No indication
supply
Indication
exhaust
Indication
exhaust
8
External input
terminal function
selection (between
J1 and JC)
Fresh-up
Error output
Error output
stop
operation
Forced off Fan forced off Air-flow up
9
BRP4A50A output
switching selection
(between X3 and
X4)
Heater output Error output
Fan output
(Low/ High/
Ultra-high)
Fan output
(High/
Ultra-high)
Fan output
(Ultra-high)
Fan output
(Low/
High/
Ultra-high)
11
Filter contamination
check**
No action
Reset filter
check
Force filter
check
Summary of Contents for Modular L Smart
Page 1: ...Service Manual Modular L Smart ESIE19 06 ...
Page 6: ...ESIE19 06 Page 6 21 01 20 Version 1 1 Modular L Smart ...
Page 16: ...ESIE19 06 Part 1 Introduction 1 4 How to use Page 16 21 01 20 Version 1 1 Modular L Smart ...
Page 59: ...ESIE19 06 Part 4 Maintenance 4 1 HRV unit 21 01 20 Version 1 1 Page 59 Modular L Smart ...
Page 60: ...ESIE19 06 Part 4 Maintenance 4 1 HRV unit Page 60 21 01 20 Version 1 1 Modular L Smart ...