ESIE19-06
|
Part 5. Appendix
5.1. Field setting
Modular L Smart
Page 66
21/01/20
|
Version 1.1
How to select the optimal Ventilation Speed
The fine tuning of the Ventilation Speed can be done properly modifying the following parameters:
•
Initial fan speed: High or Ultra-High
•
Supply fan step setting: Step 1 to 15
•
Exhaust fan step setting: Step 1 to 15
These parameters can be accessed following the procedure The Configuration Service Settings
→
Field Settings page, as shown in the List of Settings paragraph.
Both Supply and Return Fans have an optimal speed value, described in term of RPM (Revolution per Minute), that can be retrieved directly from the DAE Unit Selection Software report,
as shown below:
Provided the Unit Size is known, you can proceed to set the correspondent Supply/Return Fan step on the BRC controller, according to the following Speed-selection Tables (Make sure
to consider “Heat recovery operation” rpm).
If you do not have the unit selection from Daikin tool software, please check individual unit size performances from
onwards.
Speed-selection tables
In order to select the correct step for the Supply and Return Fan it is necessary to:
•
Choose the table whose Unit Size number equals the Unit Size provided in the DAE Unit Selection software report.
•
Identify the Supply/Return Fan steps by choosing, from H(high) column, the steps whose RPM values are the closest to the Supply/Return Fan RPM provided by DAE Unit Selection
software report.
•
Set the selected step values on the controller by going to the path Service Settings
→
Field Settings and set the following
-
19(29)-2- Selected_Step_Supply_Fan, for the Supply Fan Step, from 01 to 15
-
19(29)-3- Selected_Step_Return_Fan, for the Return Fan Step, from 01 to 15
•
If both Supply and Return Fan RPM are not present in the column H, but they appear in UH (ultra high) one, then:
•
Set the Initial Fan Speed to UltraHigh by going to the path Service Settings
→
Field Settings and modifying the default value from 17(27)-4-01(High) to 17(27)-4-02(UltraHigh)
•
Set the selected steps as in point 3.
3)
Fan Supply
Model
K3G190RD4503
Type
EC Centrifugal Fan
Material
Composite
Quantity
1x(Single Fan)
External Static Pressure
100 Pa
Internal Static Pressure
183 Pa
Total Static Pressure
283 Pa
Dynamic Pressure
10 Pa
Flow Design
300 m³/h
Rotation Speed Work • Max
2957 RPM • 4120 RPM
Efficiency
45.3%
Shaft Power
0.07 kW
Electrical Power Input
0.07 kW
Power Class • PMREF (EN13053)
P1 • 0.14 kW
SFPv Class • SFPv (EN13053)
SFP1 • 631 W/(m³/s)
3)
Fan Return
Model
K3G190RD4503
Type
EC Centrifugal Fan
Material
Composite
Quantity
1x(Single Fan)
External Static Pressure
100 Pa
Internal Static Pressure
182 Pa
Total Static Pressure
282 Pa
Dynamic Pressure
10 Pa
Flow Design
300 m³/h
Rotation Speed Work • Max
2954 RPM • 4120 RPM
Efficiency
45.3%
Shaft Power
0.07 kW
Electrical Power Input
0.07 kW
Power Class • PMREF (EN13053)
P1 • 0.14 kW
SFPv Class • SFPv (EN13053)
SFP1 • 609 W/(m³/s)
Optimal RPM values for Supply and Return (Exhaust) Fans
Summary of Contents for Modular L Smart
Page 1: ...Service Manual Modular L Smart ESIE19 06 ...
Page 6: ...ESIE19 06 Page 6 21 01 20 Version 1 1 Modular L Smart ...
Page 16: ...ESIE19 06 Part 1 Introduction 1 4 How to use Page 16 21 01 20 Version 1 1 Modular L Smart ...
Page 59: ...ESIE19 06 Part 4 Maintenance 4 1 HRV unit 21 01 20 Version 1 1 Page 59 Modular L Smart ...
Page 60: ...ESIE19 06 Part 4 Maintenance 4 1 HRV unit Page 60 21 01 20 Version 1 1 Modular L Smart ...