ESIE19-06
|
Part 5. Appendix
5.1. Field setting
Modular L Smart
Page 74
21/01/20
|
Version 1.1
Settings for all configuration
Setting 17(27)-4: First choose the fan speed. Set it to high or ultrahigh.
About setting 19(29)-0-04 and 19(29)-0-05
If the user interface is switched off while you are activating setting 19(29)-0-04 or 19(29)-0-05, the configuration is aborted. When you switch the user interface back on, the function starts
from the beginning. Setting 19(29)-0-04 takes between 1 and 6 minutes to complete. You can check if the setting was completed successfully by checking if the field setting is changed to
0-01. Setting 19(29)-0-05 takes between 3 and 35 minutes to complete. You can check if the setting was completed successfully by checking if the field setting is changed to 0-02. You can
ONLY activate these settings with clean filters. Make sure that the ducting pressure drop of the top and bottom units is balanced. The function starts as soon as it is selected and the user
interface is on. Setting 19(29)-0-04 CANNOT be configured if the outside temperature is ≤-10°C, which is out of the operation range. Setting 19(29)-0-05 CANNOT be configured if the
outside temperature is ≤5°C. In this case error 65-03 is shown and the unit stops working. Change the setting to 19(29)-0-04. The setting CANNOT be configured if there are alerts or errors
present. If booster fans are used, you can ONLY configure setting 19(29)-0-03. You can configure settings 19(29)-0-04 and 19(29)-0-05 for multiple units with 1 user interface.
5.1.1.3. About the user interface
Please read the manual supplied with the user interface for more detailed instructions.
Item
Description
a
Operation Mode Selector button
b
Fan Speed/Airflow Direction button
c
Menu/Enter button
d
Up button
e
Down button
f
Right button
g
Left button
h
ON/OFF button
i
Operation lamp
j
Cancel button
k
LCD (with backlight)
Choose between 19(29)-0-04 or 19(29)-0-05
Setting 19(29)-2 and setting
19(29)-3: Balance return air and
outdoor air with fan steps 1-15,
based on the air flow curves
and the system pressure drop.
You can activate setting
19(29)-0-04.
Warning: If it is NOT activated,
the clean filter signal will NOT
be given at the correct time.
You can activate setting
19(29)-0-05: the nominal point
is automatically determined at
the nominal flow rate (see the
databook for specific values).
Summary of Contents for Modular L Smart
Page 1: ...Service Manual Modular L Smart ESIE19 06 ...
Page 6: ...ESIE19 06 Page 6 21 01 20 Version 1 1 Modular L Smart ...
Page 16: ...ESIE19 06 Part 1 Introduction 1 4 How to use Page 16 21 01 20 Version 1 1 Modular L Smart ...
Page 59: ...ESIE19 06 Part 4 Maintenance 4 1 HRV unit 21 01 20 Version 1 1 Page 59 Modular L Smart ...
Page 60: ...ESIE19 06 Part 4 Maintenance 4 1 HRV unit Page 60 21 01 20 Version 1 1 Modular L Smart ...