ESIE19-06
|
Part 2. Troubleshooting
2.2. Error based troubleshooting
Page 20
21/01/20
|
Version 1.1
Modular L Smart
2.2. Error based troubleshooting
Overview of error codes:
HRV unit .............................................................................................................................................................................................. 23
“6A” – Damper motor malfunction ........................................................................................................................................... 23
“60” – External protection device activated ............................................................................................................................. 23
“64” – Air return thermistor faulty............................................................................................................................................. 24
“65” – Air intake thermistor faulty............................................................................................................................................. 24
“A1-01” – PCB abnormality...................................................................................................................................................... 25
“A6-00” – Fan motor abnormality............................................................................................................................................. 25
“A8-00” – Power supply malfunction........................................................................................................................................ 25
“AJ-00” – Capacity setting abnormality.................................................................................................................................... 26
“CH-00” – CO2 sensor warning ............................................................................................................................................... 26
“CJ-00” – Remote controller thermistor abnormality................................................................................................................ 27
Smart Gateway........................................................................................................................................................................ 27
System................................................................................................................................................................................................. 28
“U5-00” – Transmission user interface PCB abnormality ........................................................................................................ 28
“U8-00” – Main-Sub control error............................................................................................................................................. 28
“UA-00” – Wrong user interface used...................................................................................................................................... 29
“UC-00” – Duplication group number address......................................................................................................................... 29
“UE-00” – Transmission fault indoor-central control device..................................................................................................... 30
Error code
Unit
No.
Error level
Operation state
Cause of error
Main
Sub
A1
-
flashing
flashing
flashing
error
①
(reset remote control)
stop operation
EEPROM error
A6
01
flashing
flashing
flashing
error
①
(reset remote control)
stop fan operation
(cause of fault)
Supply air FAN
①
(address 1)
lock error
A6
02
flashing
flashing
flashing
error
①
(reset remote control)
stop fan operation
(cause of fault)
Exhaust air FAN
①
(address 3)
lock error
A6
05
flashing
flashing
flashing
error
①
(reset remote control)
stop fan operation
(cause of fault)
Supply air FAN
②
(address 2)
lock error
A6
06
flashing
flashing
flashing
error
①
(reset remote control)
stop fan operation
(cause of fault)
Exhaust air FAN
②
(address 4)
lock error
A6
10
flashing
flashing
flashing
error
①
(reset remote control)
stop fan operation
(cause of fault)
Supply air FAN
①
(address 1)
over-current error or IPM error
A6
11
flashing
flashing
flashing
error
①
(reset remote control)
stop fan operation
(cause of fault)
Supply air FAN
①
(address 1)
hall-sensor location detection
error
A6
12
flashing
flashing
flashing
error
①
(reset remote control)
stop fan operation
(cause of fault)
Exhaust air FAN
①
(address 3)
over-current error or IPM error
A6
13
flashing
flashing
flashing
error
①
(reset remote control)
stop fan operation
(cause of fault)
Exhaust air FAN
①
(address 2)
hall-sensor location detection
error
A6
14
flashing
flashing
flashing
error
①
(reset remote control)
stop fan operation
(cause of fault)
Supply air FAN
②
(address 2)
lock error or IPM error
A6
15
flashing
flashing
flashing
error
①
(reset remote control)
stop fan operation
(cause of fault)
Supply air FAN
②
(address 3)
hall-sensor location detection
error
A6
16
flashing
flashing
flashing
error
①
(reset remote control)
stop fan operation
(cause of fault)
Exhaust air FAN
②
(address 4)
over-current error or IPM error
Summary of Contents for Modular L Smart
Page 1: ...Service Manual Modular L Smart ESIE19 06 ...
Page 6: ...ESIE19 06 Page 6 21 01 20 Version 1 1 Modular L Smart ...
Page 16: ...ESIE19 06 Part 1 Introduction 1 4 How to use Page 16 21 01 20 Version 1 1 Modular L Smart ...
Page 59: ...ESIE19 06 Part 4 Maintenance 4 1 HRV unit 21 01 20 Version 1 1 Page 59 Modular L Smart ...
Page 60: ...ESIE19 06 Part 4 Maintenance 4 1 HRV unit Page 60 21 01 20 Version 1 1 Modular L Smart ...