Field Settings
Part 7 Trial Operation and Field Settings
196
Note
Overview of
Settings
: factory setting
: factory setting
Any function that is not available on the indoor unit is not displayed.
6
7
8
9
10
<Setting confirmation screen>
6
7
Return
Setting
Save the settings?
Field settings
Yes
No
Press Menu/Enter button.
Press Menu/Enter button. Setting
confirmation screen is displayed.
Select
Yes
and press Menu/
Enter button. Setting details are
saved and Field settings screen
returns.
In the case of multiple setting
changes, repeat
3
to
7
.
After all setting changes are
completed, press Cancel button
twice.
Backlight goes out, and
"Checking the connection.
Please stand by." is displayed
during initialization. After the
initialization, the Basic screen
returns.
Setting confirmation
Mode
No.
First
Code No.
Description of setting
Second Code No.
01
02
03
04
10 (20)
0
Filter
Contamination
- Heavy/Light
(Setting for
spacing time of
display time to
clean air filter)
Ultra longlife
filter
Li
g
ht
Approx.
10,000
hrs.
Heavy
Approx.
5,000
hrs.
—
—
Longlife filter
Approx.
2,500 hrs.
Approx.
1,250 hrs.
Standard filter
Approx.
200 hrs.
Approx.
100 hrs.
1
Long-life filter type (Setting of
filter sign indication time)
Longlife filter
Ultra longlife filter
—
—
2
Thermostat sensor in remote
controller
Enabled
Disabled
—
—
3
Spacing time of display time to
clean air filter count
Display
No display
—
—
11 (21)
7
Air volume adjustment
OFF
Air volume
adjustment
completion
Air volume
adjustment
start
—
13 (23)
6
External static pressure
Refer to below table
External static
pressure
Mode No.
First Code No.
Second Code No.
50 Pa
13 (23)
6
05
60 Pa
06
70 Pa
07
80 Pa
08
90 Pa
09
100 Pa
10
110 Pa
11
120 Pa
12
130 Pa
13
140 Pa
14
150 Pa
15