If the time to clean air filter is set to "Filter Contamination-a lot", set Mode No. to 10, First
Code No. to 0, and second Code No. to 02.
Do not use any settings not listed in the table.
Factory Setting
Factory Setting
Mode
No.
First
Code No.
Description of setting
Second Code No.
01
02
03
10
0
Filter Contamination-a little/a lot (Setting for
spacing time of display time to clean air filter)
(Setting for when filter contamination is a lot,
and spacing time of display time to clean air
filter is to be halved)
a little
(light)
approx.
2,500
hours
a lot
(heavy)
approx.
1,250
hours
—
3
Spacing time of display time to clean air filter
count (Use “Without indication” setting when
cleaning indication is not necessary such as
the case of periodical cleaning being carried
out.)
With indication
(Display)
Without Indication
(Do not display)
—
11
7
Air volume adjustment
OFF
Air volume
adjustment
completion
Air volume
adjustment
start
External static
pressure
Mode No.
First Code No.
Second Code No.
50 Pa
13 (23)
6
05
60 Pa
06
70 Pa
07
80 Pa
08
90 Pa
09
100 Pa
10
110 Pa
11
120 Pa
12
130 Pa
13
140 Pa
14
150 Pa
15