Diagnostics and Service
www.DaikinApplied.com 61
OM 1280-2 • MICROTECH UNIT CONTROLLER
Hydronic Water Coil Freeze Fault
Name
: WaterCoilFreezeFaultAlarm
Description
: Hydronic water coil freeze fault to protect coil
from freezing. Note: see WaterCoilFreezeProblemAlarm
for problem alarm that occurs when the unit has a face and
bypass damper.
Type
: Fault
Activate: Unit is configured to have a Hydronic Water Coil
Freeze Stat installed, the associated binary input is open. and
the face and bypass damper is disabled.
Upon active
:
• Alarm type is Fault which causes unit shutdown.
•
State: Off Alarm
• Alarm is indicated on the LUI
• Fault relay is energized
• LED output fault indication is activated
• Space fan is immediately de-energized
• Compressor is immediately de-energized
• Outdoor fan is immediately de-energized
• Outside air damper is forced closed
• All electric heat stages are de-energized
• The hot/cold water valves are forced to position of 50%.
Deactivate
: Freeze stat input closes
Reset
: Auto
Application Configuration Alarm
Name
: ConfigurationAlarm
Description
: There is an issue with one or more configuration
parameters. This means that multiple, or duplicate, inputs have
been configured for the same functionality.
Type
: Warning
Upon active
:
• Alarm is indicated on the LUI
Deactivate
: Activate is not Active.
Reset
: Auto
Control Board Alarm
Name
: ControlBoardAlarm
Description
: The application has detected a functional issue
with the control board.
Type
: Fault
Activate
: Internal application point ControlBoardStatus bit field
is not 0.
Upon active
:
• Alarm is indicated on the LUI
• Unit is shut down
Deactivate
: Internal application point ControlBoardStatus bit
field is 0.
Reset
: Auto (this is not likely to reset as the cause is usually a
hardware problem with the board).