OM 1280-2 • MICROTECH UNIT CONTROLLER 28 www.DaikinApplied.com
Description of Operation
Table 11:
Occupancy Mode Interactions
Occupancy
Override Input
(MSV7)
LUI OccManCmd
Tenant Override
Active/Inactive
Occupancy
Scheduler Input
(MSV8)
Internal Schedule
Occupancy
Sensor Input
(MSV9)
Hardwired Sensor
Input
Effective
Occupancy
Output (MSV6)
1 (Occ)
NA
NA
NA
NA
NA
NA
1 (Occ)
2 (Unoc)
NA
NA
NA
NA
NA
NA
2 (Unoc)
3 (Bypass)
NA
NA
1 (Occ)
NA
NA
NA
1 (Occ)
2 (Unoc)
NA
NA
NA
3 (Bypass)
3 (Standby)
NA
NA
NA
3 (Bypass)
4 (Null)
Occ
NA
NA
1 (Occ)
Unoc
1 (Occ)
NA
1 (Occ)
Unoc
2 (Unoc)
NA
3 (Bypass)
Unoc
3 (Null)
NoBI
1
3 (Bypass)
Unoc
3 (Null)
Occ
2
1 (Occ)
Unoc
3 (Null)
Unoc
3
3 (Bypass)
4 (Standby)
NA
NA
NA
NA
NA
NA
4 (Standby)
5 (Null)
Occ
NA
NA
NA
NA
NA
1 (Occ)
5 (Null)
Unoc
NA
NA
NA
NA
NA
2 (Unoc)
5 (Null)
Bypass
NA
1 (Occ)
NA
NA
NA
1 (Occ)
2 (Unoc)
NA
NA
NA
3 (Bypass)
3 (Standby)
NA
NA
NA
3 (Bypass)
4 (Null)
Occ
NA
NA
1 (Occ)
Unoc
1 (Occ)
NA
1 (Occ)
Unoc
2 (Unoc)
NA
3 (Bypass)
Unoc
3 (Null)
NoBI
1
3 (Bypass)
Unoc
3 (Null)
Occ
2
1 (Occ)
Unoc
3 (Null)
Unoc
3
3 (Bypass)
5 (Null)
Standby
NA
NA
NA
NA
NA
4 (Standby)
5 (Null)
Null
Inactive
1 (Occ)
NA
1 (Occ)
NA
1 (Occ)
NA
2 (Unoc)
NA
4 (Standby)
NA
3 (Null)
NoBI
1
1 (Occ)
NA
3 (Null)
Occ
2
1 (Occ)
NA
3 (Null)
Unoc
3
4 (Standby)
2 (Unoc)
NA
NA
NA
2 (Unoc)
3 (Standby)
NA
NA
NA
4 (Standby)
4 (Null)
Occ
1 (Occ)
NA
1 (Occ)
Occ
2 (Unoc)
NA
4 (Standby)
Occ
3 (Null)
NoBI
1
1 (Occ)
Occ
3 (Null)
Occ
2
1 (Occ)
Occ
3 (Null)
Unoc
3
4 (Standby)
Unoc
1 (Occ)
NA
1 (Occ)
Unoc
2 (Unoc)
NA
2 (Unoc)
Unoc
3 (Null)
NoBI
1
2 (Unoc)
Unoc
3 (Null)
Occ
2
1 (Occ)
Unoc
3 (Null)
Unoc
3
2 (Unoc)
5 (Null)
Null
Active
1 (Occ)
NA
1 (Occ)
NA
1 (Occ)
NA
2 (Unoc)
NA
3 (Bypass)
NA
3 (Null)
NoBI
1
1 (Occ)
NA
3 (Null)
Occ
2
1 (Occ)
NA
3 (Null)
Unoc
3
3 (Bypass)
2 (Unoc)
NA
NA
NA
3 (Bypass)
3 (Standby)
NA
NA
NA
3 (Bypass)
4 (Null)
Occ
1 (Occ)
NA
1 (Occ)
Occ
2 (Unoc)
NA
3 (Bypass)
Occ
3 (Null)
NoBI
1
1 (Occ)
Occ
3 (Null)
Occ
2
1 (Occ)
Occ
3 (Null)
Unoc
3
3 (Bypass)
Unoc
1 (Occ)
NA
1 (Occ)
Unoc
2 (Unoc)
NA
3 (Bypass)
Unoc
3 (Null)
NoBI
1
3 (Bypass)
Unoc
3 (Null)
Occ
2
3 (Bypass)
Unoc
3 (Null)
Unoc
3
3 (Bypass)
NOTE:
The tenant override is a set of dry contacts placed in parallel with the space temperature sensor (aiSetpointAdjust). When the contacts are closed momentarily, the bypass timer becomes
active and is set to ncpBypassTime, and the unit enters the Bypass mode. The tenant override function is active until the timer expires.
1
No binary inputs are configured for an Unoccupied input.
2
A binary input is configured for an Unoccupied input and that input indicates occupied.
3
A binary input is configured for an Unoccupied input and that input indicates unoccupied.