www.DaikinApplied.com 45
OM 1280-2 • MICROTECH UNIT CONTROLLER
Parameter
Description
HydroHeatingCmd
Hydronic Heating command
InCoilTmp
Indoor Coil Temperature
InEnth
Indoor Enthalpy. Determined by space temperature and indoor air
humidity
IntSched
Internal Schedule. Result of the user-defined daily occupancy
schedule
LowOAFrzStat
Low Outdoor Air Freeze Status. Indicates OAT freeze protection
status as active or not active
KeyEmergOv
LUI Display Emergency Override. Command set from the local user
interface
LuiEnergyHoldOff
LUI Energy Hold-off. Command set from the local user interface
KeyOccManCmd
LUI Occupancy Manual Command. Occupancy override set from the
local user interface
LuiSetptOffset
LUI Setpoint Offset. Setpoint offset adjustment set from the local user
interface
KeySysStat
LUI System Status. Current heat/cool status set from the local user
interface
LWT
Leaving Water Temperature
aiLWT
Leaving Water Temperature sensor input
MM/DD/YYYY
Date of trend point generation
MSM
Main State Machine. Function of the controller used to monitor unit
state
NetOccManCmd
Network Occupancy Command. BAS-commanded occupancy
override parameter
MultAlarmComp
Multiple Alarm Compressor. Activates when one or more compressor
alarms is generated
OADpos
Outdoor Air Damper Position
OADmpr
Outdoor Air Damper position analog output
NetOADIn
Network Outdoor Air Damper Input. OAD position configured for
client/server control strategy
OADAutoPos
Outdoor Air Damper Automatic Position. Maximum value of the OAD
setpoint and free cooling calculation
OADLowTmpStat
Outdoor Air Damper Low Temperature Status
niOADMinPos
Network Input Outdoor Air Damper Minimum Position. BAS-
commanded outdoor air damper position; overrides local control if
configured
OADMinPos
Outdoor Air Damper Minimum Position. Minimum OAD position for
span fan operating at high speed, or at any speed if CO
2
/DCV is
enabled.
OADPosCO2
Outdoor Air Damper Position for CO
2
OADPosFreeCl
Outdoor Air Damper Position for Free Cooling
OADPosReset
Outdoor Air Damper Position for hard-wired reset
OAMinPosLowSpd
Outdoor Air Damper Position Low Speed. Minimum OAD position for
space fan operating at low speed
OAMinPosMedSpd Outdoor Air Damper Position Medium Speed. Minimum outdoor air
damper position for space fan operating at medium speed
OAT
Outdoor Air Temperature
niOAT
Network Input Outdoor Air Temperature. BAS-commanded input
OccClSpt
Occupied Cooling Setpoint
Parameter
Description
LonOccClSptSh
Occupied Cooling Setpoint Shift from
LonWorks
(future use)
LonStdClSptSh
Standby Cooling Setpoint Shift from
LonWorks
(future use)
OccHtSpt
Occupied Heating Setpoint
LonOccHtSptSh
Occupied Heating Setpoint Shift from
LonWorks
(future use)
LonStdHtSptSh
Standby Heating Setpoint Shift from
LonWorks
(future use)
NtOccSched
Network Occupancy Schedule. BAS-commanded occupancy
schedule
NetOccSens
Network Occupancy Sensor. Occupancy control from BAS-
commanded room sensor
OutCoilTmp
Outdoor Air Coil Temperature
OutEnth
Outdoor Enthalpy. Output based on current outdoor air temperature
and outdoor air humidity
niOutRH
Outdoor Air Relative Humidity input
pwmECMSupplyFan ECM Supply Fan output
RAT
Return Air Temperature from unit-mounted room/return air sensor
RevValveCmd
Reversing Valve Command. Current valve command to either heating
or cooling
RSFanSpd
Remote Sensor Fan Speed (auto, low, medium, high, off) determined
by sensor input
RSSysMode
Remote Sensor System Mode. Status (auto, heat, cool) determined
by sensor input
Setpoint
Setpoint value
netSetpoint
Network Setpoint. BAS-commanded setpoint value
SptAdj
Setpoint Adjust. Temperature setpoint adjust analog input
LocSptShft
Local Setpoint Shift. Setpoint adjustment from the room sensor
SptOffAdj
Setpoint Offset Adjustment
NetSptOffst
Network Setpoint Offset. BAS-commanded setpoint offset
niSpcCO2
Space CO
2
Input. BAS-supplied space CO
2
input used to determine
effective space CO
2
SpcCO2Lim
Space CO
2
Setpoint
niSpcRH
Space Relative Humidity Network Input
SpaceTmp
Effective Space Temperature
SpcTmp
Space Temperature from hard-wired input
niSpcTmp
Space Temperature from BAS-commanded space temperature input
SpcTmpTO
Space Temperature with Tenant Override input
SysStatCmd
System Status Command. Unit heat/cool command
SZVavFanPI
Single-Zone VAV Fan speed PI loop output
NetInAlarm
Highest priority active alarm
ValveFrzProtect
Valve Freeze Protection strategy