OM 1280-2 • MICROTECH UNIT CONTROLLER 50 www.DaikinApplied.com
UVC Configuration Parameters
Parameter (LUI)
Operating Range (Default)
ABV
Min
Max
Default
Description
OutHumSens
NOT_INSTALLED, INSTALLED (INSTALLED)
0
1
1
Configures if the sensor is installed.
RATSens
NOT_INSTALLED, INSTALLED (INSTALLED)
0
1
1
Configures if RAT sensor is installed.
RemSptAdjType
DIFF, ABS (ABS)
0
1
1
“Wall Sensor Type.
DIFF: (
LonWorks: Log_Off): use 3°F Diff,
ABS: (
LonWorks
: Log_ON): use 55°F to 85°F
Adjust.”
SpcRHEn
DISABLE, ENABLE (DISABLE)
0
1
0
Space Humidity Sensor Enable
OutRHEn
DISABLE, ENABLE (DISABLE)
0
1
0
Outdoor Humidity Sensor Enable
EconSel
NONE, DIFF_TEMP, OUTDOOR_ENTH, ENTH_
COMPARE (DIFF_TEMP)
0
3
1
“Specifies strategy for determining when free-
cooling is available.
DIFF_TEMP: Compare OAT to space temp.
OUTDOOR_ENTH: using OAT and the outside
humidity
ENTH_COMPARE: Compare outdoor enthalpy
to indoor enthalpy using OAT and outdoor
humidity versus space temperature and indoor
humidity.”
KeyDehumEn
DISABLED, ENABLED (ENABLED)
0
1
1
Specifies if the LUI enables or disables
dehumidification.
DehumType
ACTIVE, PASSIVE (ACTIVE)
0
1
0
“Type of Dehumidification.
ACTIVE: Using water or compressor
(depending on availability),
PASSIVE: The air is not reheated.
Note: Dehumidification is enabled/disabled via
DehumidEnabled.”
DehumLTmpSpt
35°F to 65°F
35
65
55
Cannot perform dehumidification when the
control temp is lower than this setpoint.
DehumStgDn
20°F to 40°F
20
40
32
Stage down dehumidification when the
aiIndoorCoilTemp ≤ this setpoint. Stage up
when aiIndoorCoilTemp ≥ this se 4°F.
PassDhmFBPD
0% to 100%
1
100
50
Passive Dehum F&B Damper Max
TemperEn
DISABLE, ENABLE (DISABLE)
0
1
0
Enables Air Tempering Mode.
TemperDiff
2.0°F to 20.0°F (5.0°F)
2
20
5
DAT is compared to ncpOccHeatSetpt – this
parameter when entering Enters Air Tempering
Mode.
FanOnInUnocc
OFF, ON (OFF)
0
1
0
Indoor fan runs in unoccupied mode
SpcCO2En
DISABLE, ENABLE (DISABLE)
0
1
0
Space CO
2
Enable
CfgAnIn14:
NONE/CO2
0
2
1
Selects virtual function for configurable analog
inputs. Options are:
NONE
CO2
RSTVLT
CfgAnIn10:
NONE/EWT/OCT
0
3
1
Selects virtual function for configurable analog
inputs. Options are:
NONE
EWT
OCT
ICT_SRT
CfgAnIn12:
NONE/ICT_SRT
0
3
3
CfgBI1
(HIGH_PRESSURE)
0
10
1
Selects virtual function for binary input. 24 VAC
Input
CfgBI2
(FREEZE_STAT)
0
10
2
Selects virtual function for binary input. 24 VAC
Input
CfgBI3
(NONE)
0
10
0
Selects virtual function for binary input. 24VAC
Input
CfgBI4
(NONE)
0
10
0
Selects virtual function for binary input. 24VAC
Input
CfgBI5
(BOILERLESS_EH)
0
10
5
Selects virtual function for binary input. Discrete
Input
CfgBI6
(VENT_LOCKOUT)
0
10
6
Selects virtual function for binary input. Discrete
Input
CfgBI7
(UNOCCUPIED)/(NONE)
0
10
7
Selects virtual function for binary input. Discrete
Input
CfgBI8
(SHUTDOWN)
0
10
8
Selects virtual function for binary input. Discrete
Input