OM 1280-2 • MICROTECH UNIT CONTROLLER 44 www.DaikinApplied.com
Trending
Trending
Trending Parameters
If the UVC has an optional SD card installed, data trending
can be enabled to capture historical operational data. The
rate at which the data is recorded can be configured to time
intervals of 1 minute, 10 minutes, hourly, or daily, or based on a
change in occupancy mode. This configuration can be changed
through the LUI keypad or ServiceTools software.
The data is captured in a .csv file format and saved to the SD
card. This data can accessed by removing the SD card from
the UVC and inserting it into an appropriate SD card reader. A
separate trend file is created for each day. Refer to Table 23 for
the comprehensive list of all parameters supported by trending.
Table 23:
Trending-Supported Parameters
Parameter
Description
AirTmprgMode
Air Tempering Mode. Enables air tempering if the DAT (discharge air
temperature) is less than the occupied heating setpoint and the unit is
not in an unoccupied state
Alarm1_Date
Alarm Date. Day, month, and year of active alarm occurrence
Alarm1_Descr
Alarm Description. Describes the type of alarm (ex, High DX
Pressure) or No Alarm
Alarm1_Time
Alarm Date. Hour, minute, and second of alarm occurrence
Alarm1_Type
Alarm Type. Category of alarm (Problem, Fault, Warning)
AlarmStatus
Alarm Status. Active alarm(s) status
AllowCool
Allow Cooling. Status of cooling-enable function
AllowDehumid
Allow Dehumidification. Status of dehumidification-enable function
AllowHeat
Allow Heating. Status of heating-enable function
NetAppMode
Network Application Mode. BAS-commanded input that determines
the unit heat/cool mode
ClgSpt
Cooling Setpoint. Current cooling setpoint the unit is controlling to
CO2
CO
2
analog input setpoint
CldWtr
Cold water valve position
ColdWtrPI
Cold water PI loop output
CmpAirTmprg
Compressor Air Tempering. Indicates if compressor air tempering
mode is heating to control to the DAT under certain conditions
ClOATLckStat
Cooling Outdoor Air Temperature Lockout Status. Current state of
OAT compressor cooling lock-out on ASHPs
CmpClAvl
Compressor Cooling Available. Indicates if compressor cooling can
be enabled
CmpHtAvl
Compressor Heating Available. Indicates if compressor heating can
be enabled
NetCompEn
Network Compressor Enable. BAS-commanded compressor enable
parameter
CmpHtEWTLckSt
Compressor Heating Entering Water Temperature Lockout Status.
Current state of EWT compressor heating lock-out function
CmpHtOATLckSt
Compressor Outdoor Air Temperature Lockout Status. Current state
of OAT compressor heating lock-out function
CmpStgCmd
Compressor Stage Command. Indicates if cooling stages are
controlled by the compressor
CondOverflw
Condensate overflow. Indicates wet or dry if sensor is installed
CntrlTmp
Control Temperature. Selected temperature from either a space or
return air sensor
CntrlTmpStat
Control Temperature Status (heat, cool, between or invalid)
ClVlv
Cooling valve position
ClStgChg
Cooling Stage Change. Cooling is commanded to stage up
DAT
Discharge Air Temperature
aiDAT
DAT from sensor input
DATClgSpt
DAT Cooling Setpoint
NetDATClgSpt
Network Discharge Cooling Setpoint. BAS-commanded discharge air
cooling setpoint
DATRstClin
DAT Cooling Reset control value
DATRstHtin
DAT Heating Reset control value
DATRstHtln
DAT Heating Reset input used to determine control value
niDATRstHtln
Network DAT Heating Reset. BAS-commanded parameter
DATDehumSpt
DAT Dehumidification Setpoint
Parameter
Description
DATHtgSetpt
DAT Heating Setpoint
NetDATHtgSpt
Network DAT Heating Setpoint. BAS-commanded parameter
DATHotWtr
DAT Hot Water lower limit PI loop output
DATReHtSpt
DAT Heating Reheat Setpoint
DATSpt
DAT Setpoint
DfrstSt
Defrost State
DehumAvl
Dehumidification Available. Indicates if dehumidification can be
enabled
DehumidEnabled
Dehumidification Enabled. LUI keypad or network command
DAHiLimMode
Discharge Air High Limit Mode. Active if DAT is greater than this
setpoint and unit is in heating mode
NetEconEn
Network Economizer Enable. BAS-commanded parameter
EconMode
Economizer Mode. Current mode of the outside air damper
EffHeatCool
Effective Heat Cool. Actual heat/cool mode of the unit
EffHtClNone
Effective Heat Cool None. Indicates unit mode is heat, cool, or none
EffHum
Effective Humidity. Current humidity status of the space as either
humid or not humid
EffectOcc
Effective Occupancy. Current occupancy mode of the unit
EffSpt
Effective Setpoint. Temperature setpoint the unit is currently
controlling to
EffEWT
Effective Entering Water Temperature
EffOutRH
Effective Outdoor Air Relative Humidity
EffOAT
Effective Outdoor Air Temperature
EffSpcCO2
Effective Space CO
2
value of indoor space
EffSpaceRH
Effective Space Relative Humidity level of indoor space
ElDatLLPIOut
Electric Heat DAT Lower Limit PI loop output
ElectDehumPIOut
Electric Heat Dehumidification lower limit PI loop output
ElHtStgOut
Electric Heat Stage Output. Number of currently active electric heat
stages
ElectHtAvl
Electric Heat Available. Indicates if electric heating can be enabled
NetEmergOv
Network Emergency Override. BAS-commanded emergency override
input
EnergHold
Energy Hold-off. Status of energy hold-off state. Prevents unit from
heating/cooling except in the event of extreme temperatures
NetEnergHold
Network Energy Hold-off. BAS-commanded energy hold-off
parameter
EWT
Entering Water Temperature setpoint
niEWT
Entering Water Temperature. BAS-commanded input
FanCntMth
Fan Control Method. Determines how the indoor fan is being
controlled
CurFanSpd
Current Indoor Fan Speed
NetFanSpdCmd
Network Fan Speed Command. Indoor fan speed setpoint input from
the BAS
FB_PIOut
Face and Bypass Damper PI loop output
FBDamper
Face and Bypass Damper position
FBP
Face and Bypass Damper position analog output
FreeClAvl
Free Cooling Available. Indicates if free cooling is currently available
FreeClEn
Free Cooling Enabled. Indicates if free cooling is allowed to be
enabled
FreeClCmd
Free Cooling Command
SpcTmp
Space Temperature. Sensor-controlled space temperature (without
tenant override)
HtgVlv
Heating Valve. Valve position analog output
HtgStgChg
Heating Stage Change. Indicates if heating is commanded to stage
down
HH:MM:SS
Time of trend point generation
HotWtr
Hot Water. Hot water valve position
HtWtrPI
Hot Water PI. Hot water valve PI loop output
HtgSpt
Heating Setpoint. Current heating setpoint the unit is controlling to
HumIn
Humidity Input. Indoor air relative humidity analog input
HumOut
Outdoor Humidity. Outdoor air relative humidity analog input
HydroClAvl
Hydronic Cooling Available. Indicates if hydronic cooling is available
to be enabled
HydroClCmd
Hydronic Cooling Command
HydroHtAvl
Hydronic Heating Available. Indicates if hydronic heating is available
to be enabled