Daikin Applications
Parameter Settings:
The MD5 VFD has been made to Daikin specifications. All
factory installed MD5 VFDs with MicroTech III controls are also
factory configured and started.
Table 63
lists the parameters
that have been specifically configured for Daikin or may need
owner adjustment as described in this manual .
• “HVAC Default” settings mentioned in the
Table 63
note is
the vendor default if Parameter 9902 is set as shown .
• “Daikin Settings” are the recommended settings for Daikin
units .
• No other parameters should be needed or adjusted .
WARNING
Unintended Equipment Operation
• Modifying or changing parameters whose function is not
described in this manual will affect drive controller operation .
Some register changes will take effect as soon as they are
entered .
• Do not modify or change parameters whose function is not
described in this instruction bulletin .
Failure to follow this instruction can result in death, serious
injury, or equipment damage .
OM 1191 • MD5 VFD 88 www .DaikinApplied .com