System Control
Using the fieldbus for miscellaneous drive control requires:
•
Drive parameter values set as defined below.
• Fieldbus controller command(s) in the appropriate
location. (The location is defined by the Protocol
Reference, which is protocol dependent .)
Table 47: Fieldbus Controller Commands
Drive Parameter
Value
Description
Protocol Reference
1601
RUN ENABLE
7 (COMM)
Run enable by fieldbus.
1604
FAULT RESET SEL
8 (COMM)
Fault reset by fieldbus.
1607
PARAM SAVE
1 (SAVE
Saves altered parameters to memory (then value returns to 0) .
Relay Output Control
Using the fieldbus for relay output control requires:
•
Drive parameter values set as defined below.
• Fieldbus controller supplied, binary coded, relay
command(s) in the appropriate location . (The location
is defined by the Protocol Reference, which is protocol
dependent .)
Table 48: Relay Output Control
Drive Parameter
Value
Description
Protocol Reference
1401
RELAY OUTPUT 1
35 (COMM)
36 (COMM(-1))
Relay Output 1 controlled by fieldbus.
1402
RELAY OUTPUT 2
Relay Output 2 controlled by fieldbus.
1403
RELAY OUTPUT 3
Relay Output 3 controlled by fieldbus.
1410
1
RELAY OUTPUT 4
Relay Output 4 controlled by fieldbus.
1411
1
RELAY OUTPUT 5
Relay Output 5 controlled by fieldbus.
1412
1
RELAY OUTPUT 6
Relay Output 6 controlled by fieldbus.
0122
RO 1-3 STATUS
Relay 1…3 status .
0123
RO 4-6 STATUS
Relay 4…6 status .
1 . More than 3 relays requires the addition of a relay extension module .
NOTE:
Note: Relay status feedback occurs without
configuration as defined below.
Analog Output Control
Using the fieldbus for analog output control (e.g. PID setpoint)
requires:
•
Drive parameter values set as defined below.
• Fieldbus controller supplied analog value(s) in the
appropriate location. (The location is defined by the
Protocol Reference, which is protocol dependent .)
Table 49: Analog Output Control
Drive Parameter
Value
Description
Protocol Reference
1501
AO1 CONTENT SEL
135 (COMM VALUE 1)
Analog Output 1 controlled by writing to parameter 0135 .
—
0135
COMM VALUE 1
—
1502…1505
AO1 CONTENT MIN…
MAXIMUM AO1
Set appropriate values .
Used for scaling
—
1506
FILTER AO1
Filter time constant for AO1 .
—
1507
AO2 CONTENT SEL
136 (COMM VALUE 2)
Analog Output 2 controlled by writing to parameter 0136 .
—
0136
COMM VALUE 2
—
1508…1511
AO2 CONTENT MIN…
MAXIMUM AO2
Set appropriate values .
Used for scaling
—
1512
FILTER AO2
Filter time constant for AO2 .
—
OM 1191 • MD5 VFD
70
www .DaikinApplied .com
f
ieldbUs
a
daPTer