Table 5 continued: Group 01: Operating Data
0145 MOTOR TEMP
Par . 3501
= 1…3:
-10…200 °C
Par . 3501 =
4: 0…5000
ohm Par .
3501 =
5…6: 0…1
1
—
Motor temperature in degrees Celsius / PTC resistance in ohms .
• Applies only if motor temperature sensor is set up .
0150 CB TEMP
-20 .0…
150 .0 °C
1 .0 °C
—
Temperature of the drive control board in degrees Celsius .
Note: Some drives have a control board (OMIO) that does not support this feature . These drives always show the constant value of 25 .0 °C .
0153 MOT THERM STRESS
0 .0…100 .0%
0 .1%
—
Estimated rise of the motor temperature . Value equals to the estimated motor thermal stress as a percentage of the motor temperature trip level .
0158 PID COMM VALUE 1
-32768…
+32767
1
—
Data received from fieldbus for PID control (PID1 and PID2).
0159 PID COMM VALUE 2
-32768…
+32767
1
—
Data received from fieldbus for PID control (PID1 and PID2).
0174 SAVED KWH
0 .0…999 .9
kWh
0 .1 kWh
—
Energy saved in kWh compared to the energy used when the pump is connected directly to the supply . See the note on page 1-163 .
• The counter value is accumulated till it reaches 999 .9 after which the counter rolls over and starts again from 0 .0 .
• Can be reset with parameter 4509 ENERGY RESET (resets all energy calculators at the same time) .
0175 SAVED MWH
0…65535
MWh
1 MWh
—
—
Energy saved in MWh compared to the energy used when the pump is connected directly to the supply . See the note on page 1-163 .
• The counter value is accumulated till it reaches 65535 after which the counter rolls over and starts again from 0 .
• Can be reset with parameter 4509 ENERGY RESET (resets all energy calculators at the same time) .
0176 SAVED AMOUNT 1
0 .0…999 .9
0 .1
—
Energy saved in local currency (remainder when the total saved energy is divided by 1000) . See the note on page 1-163 .
• To find out the total saved energy in currency units, add the value of parameter 0177 multiplied by 1000 to the value of parameter 0176.
Example:
0176 SAVED AMOUNT 1 = 123 .4
0177 SAVED AMOUNT 2 = 5
Total saved energy = 5
×
1000 + 123 .4 = 5123 .4 currency units .
• The counter value is accumulated till it reaches 999 .9 (the counter does not roll over) .
• Can be reset with parameter 4509 ENERGY RESET (resets all energy calculators at the same time) .
• Local energy price is set with parameter 4502 ENERGY PRICE .
0177 SAVED AMOUNT 2
0…65535
1
—
Energy saved in local currency in thousand currency units . Eg value 5 means 5000 currency units . See the note on page 1-163 .
• The counter value is accumulated till it reaches 65535 (the counter does not roll over) .
• See parameter 0176 SAVED AMOUNT 1 .
0178 SAVED CO
2
0 .0…6553 .5
tn
0 .1 tn
—
Reduction of carbon dioxide emissions in tons . See the note on page 1-163 .
• The counter value is accumulated till it reaches 6553 .5 (the counter does not roll over) .
• Can be reset with parameter 4509 ENERGY RESET (resets all energy calculators at the same time) .
• CO
2
conversion factor is set with parameter 4507 CO
2
CONV FACTOR .
OM 1191 • MD5 VFD 16 www .DaikinApplied .com
P
araMeTers