Figure 3: Start-Up By Changing the Parameters Individually
To change the parameters, follow these steps:
1
Select MENU to enter the main menu .
2
Select the Parameters mode with the UP/DOWN buttons
and select ENTER to select the Parameters mode .
3
Select the appropriate parameter group with the UP/
DOWN buttons and select SEL
4
Select the appropriate parameter in a group with the UP/
DOWN buttons . Select EDIT to change the parameter
value .
5
Press the UP/DOWN buttons to change the parameter
value .
6
Select SAVE to store the modified value or select
CANCEL to leave the set mode. Any modifications not
saved are cancelled .
7
Select EXIT to return to the listing of parameter groups,
and again to return to the main menu .
To complete the control connections by manually entering the
parameters, see
Parameters on page 12
For detailed hardware description, see the
Technical Data on
page 82
.
NOTE:
The current parameter value appears below the
highlighted parameter .
To view the default parameter value, press the UP/
DOWN buttons simultaneously .
The most typical and necessary parameters to
change are parameter groups 99 Start-up data, 10
Start/Stop/Dir, 11 Reference Select, 20 Limits, 21
Start/Stop, 22 Accel/Decel, 26 Motor Control and 30
Fault Functions .
To restore the default factory settings, select the
application macro HVAC Default .
OM 1191 • MD5 VFD