Binary Value Object Instance Summary
The following table summarizes the Binary Value Objects supported:
Table 39: Binary Value Objects
Instance ID
Object Name
Description
Active/Inactive Text
Present Value
Access Type
BV0
RUN/STOP ACT
This object indicates the drive Run Status, regardless of the control source .
RUN/STOP
R
BV1
FWD/REV ACT
This object indicates the motor’s rotation direction, regardless of the control source .
REV/FWD
R
BV2
FAULT ACT
this object indicates the drive’s fault status .
FAULT/OK
R
BV3
EXT 1/2 ACT
This object indicates which control source is active: External 1 or External 2 .
EXT2/EXT1
R
BV4
HAND/AUTO ACT
This object indicates whether the drive is under Hand or Auto control .
HAND/AUTO
R
BV5
ALARM ACT
This object indicates the drive’s alarm status .
ALARM/OK
R
BV6
MAINT REQ
This object indicates the drive’s maintenance status . Refer to Group 29 in the
drive’s parameter descriptions .
MAINT/OK
R
BV7
DRIVE READY
This object indicates whether the drive is ready to accept a run command .
READY/NOT READY
R
BV8
AT SETPOINT
This object indicates whether the drive is at the commanded setpoint .
YES/NO
R
BV9
RUN ENA ACT
This object indicates the Run Enable command status, regardless of the control
source .
ENABLE/DISABLE
R
BV10
RUN/STOP CMD
This object commands a drive start . Control requires either:
• Parameter 1001 value = COMM for control by EXT1 or
• Parameter 1002 value = COMM for control by EXT2 .
RUN/STOP
C
BV11
FWD/REV CMD
This object commands a motor rotation direction change . Control requires 1003 =
REQUEST and either:
• Parameter 1001 value = COMM for control by EXT1 or
• Parameter 1002 value = COMM for control by EXT2 .
REV/FWD
C
BV12
RUN ENA CMD
This object commands Run Enable . Control requires parameter 1601 value =
COMM .
ENABLE/DISABLE
C
BV13
EXT 1/2 CMD
This object selects ext1 or ext2 as the active control source . Control requires
parameter 1102 value = COMM .
EXT2/EXT1
C
BV14
FAULT RESET
This object resets a faulted drive . The command is rising edge triggered . Control
requires parameter 1604 value = COMM .
RESET/NO
C
BV15
MBOX READ
This object reads a parameter (defined by AV25 MBOX PARAM) and returns it in
AV26 MBOX DATA .
READ/RESET
W
BV16
MBOX WRITE
This object writes the data value specified by AV26, MBOX DATA, to a parameter
(defined by AV25, MBOX PARAM).
WRITE/RESET
W
BV17
LOCK PANEL
This object locks the panel and prevents parameter changes . The corresponding
drive parameter is 1602 .
LOCK/UNLOCK
W
BV18
CTL OVERRIDE
CMD
This object commands the drive into BACnet Control Override . In this mode,
BACnet takes drive control from the normal source . However, the control panel’s
HAND mode has priority over BACnet Control Override .
ON/OFF
C
BV19
CTL OVERRIDE
ACT
This object indicates whether the drive is in BACnet Control Override . (See BV18 .)
ON/OFF
R
BV20
START ENABLE 1
This object commands start enable1 . Control requires param 1608 value = COMM .
ENABLE/DISABLE
C
BV21
START ENABLE 2
This object commands start enable1 . Control requires param 1609 value = COMM .
ENABLE/DISABLE
C
NOTE:
For Present Value Access Types, R = Read-only,
W = Writeable, C = Commandable . Commandable
values support priority arrays & relinquish defaults .
Analog Input Object Instance Summary
The following table summarizes the Analog Input Objects supported:
Table 40: Analog Input Objects
Instance ID
Object Name
Description
Units
Present Value
Access Type
AI0
ANALOG INPUT 1
This object indicates the value of Analog Input 1 . The corresponding drive parameter is 0120 .
Percent
R
AI1
ANALOG INPUT 2
This object indicates the value of Analog Input 2 . The corresponding drive parameter is 0121 .
Percen
R
NOTE:
For Present Value Access Types, R = Read-only,
W = Writeable, C = Commandable . Commandable
values support priority arrays & relinquish defaults .
OM 1191 • MD5 VFD 60 www .DaikinApplied .com