Table 6 continued: Group 03: Actual Signals
0305 FAULT WORD 1
—
1
—
Read-only copy of the Fault Word 1 .
• When a fault is active, the corresponding bit for the active fault is set in the Fault Words .
• Each fault has a dedicated bit allocated within Fault Words .
• See section Fault listing on page 1-282 for a description of the faults .
• The control panel displays the word in hex . For example, all zeros and a 1 in Bit 0 displays as 0001 . All zeros and a 1 in Bit 15 displays as 8000 .
Bit # 0305, FAULT WORD 1 0306, FAULT WORD 2
0307, FAULT WORD 3
0
OVERCURRENT
Obsolete
EFB 1
1
DC OVERVOLT
THERM FAIL
EFB 2
2
DEV OVERTEMP
OPEX LINK
EFB 3
3
SHORT CIRC
OPEX PWR
INCOMPATIBLE SW
4
Reserved
CURR MEAS
USER LOAD CURVE
5
DC UNDERVOLT
SUPPLY PHASE
Reserved
6
AI1 LOSS
ENCODER ERR
Reserved
7
AI2 LOSS
OVERSPEED
Reserved
8
MOT OVERTEMP
Reserved
Reserved
9
PANEL LOSS
DRIVE ID
Reserved
10
ID RUN FAIL
CONFIG FILE
System error
11
MOTOR STALL
SERIAL 1 ERR
System error
12
CB OVERTEMP
EFB CON FILE
System error
13
EXT FAULT 1
FORCE TRIP
System error
14
EXT FAULT 2
MOTOR PHASE
System error
15
EARTH FAULT
OUTP WIRING
Param . setting fault
0306 FAULT WORD 2
—
1
—
Read-only copy of the Fault Word 2 .
• See parameter 0305 .
0307 FAULT WORD 3
—
1
—
Read-only copy of the Fault Word 3 .
• See parameter 0305 .
0308 ALARM WORD 1
—
1
—
• When an alarm is active, the corresponding bit for the active alarm is set in the Alarm Words .
• Each alarm has a dedicated bit allocated within Alarm Words .
• Bits remain set until the whole alarm word is reset . (Reset by writing zero to the word .)
• The control panel displays the word in hex . For example, all zeros and a 1 in Bit 0 displays as 0001 . All zeros and a 1 in Bit 15 displays as 8000 .
Bit # 0308, ALARM WORD 1 0309, ALARM WORD 2
0
OVERCURRENT
Reserved
1
OVERVOLTAGE
PID SLEEP
2
UNDERVOLTAGE
ID RUN
3
DIR LOCK
Reserved
4
IO COMM
START ENABLE 1 MISSING
5
AI1 LOSS
START ENABLE 2 MISSING
6
AI2 LOSS
EMERGENCY STOP
7
PANEL LOSS
ENCODER ERROR
8
DEVICE OVERTEMP
FIRST START
9
MOTOR TEMP
Reserved
10
Reserved
USER LOAD CURVE
11
MOTOR STALL
START DELAY
12
AUTORESET
Reserved
13
AUTOCHANGE
Reserved
14
PFA I LOCK
Reserved
15
Reserved
Reserved
0309 ALARM WORD 2
—
1
—
• See parameter 0308 .Group 03: Actual Signals