IM 970-2 • MAVERICK I ROOFTOP 34 www.DaikinApplied.com
P
erforManCe
d
aTa
Table 21: Gross System Performance—MPS H04C, 4 Tons Gas Heat
Entering Indoor Air @ 80°F (26 .7°C) dbE
1
wbE
71°F (21 .7°C)
67°F (19 .4°C)
63°F (17 .2°C)
CFM
(L/s)
1760
(831)
1600
(755)
1360
(642)
1760
(831)
1600
(755)
1360
(642)
1760
(831)
1600
(755)
1360
(642)
DR
1
0 .11
0 .09
0 .05
0 .11
0 .09
0 .05
0 .11
0 .09
0 .05
Outdoor Dry Bulb
Temperature °F (°C)
75
(23.9)
Total BTUH
(kW)
58.9
(17.3)
57.8
(16.9)
56.2
(16.5)
55.1
(16.1)
54.1
(15.9)
52.6
(15.4)
49.6
(14.5)
48.8
(14.3)
47.4
(13.9)
Sens BTUH
(kW)
31.1
(9.1)
29.7
(8.7)
27.6
(8.1)
40.2
(11.8)
38.4
(11.3)
35.7
(10.5)
43.7
(12.8)
41.8
(12.2)
38.9
(11.4)
Power (kW)
2.6
2.6
2.5
2.6
2.5
2.5
2.6
2.5
2.5
80
(26.7)
Total BTUH
(kW)
57.3
(16.8)
56.3
(16.5)
54.7
(16.0)
53.5
(15.7)
52.6
(15.4)
51.1
(15.0)
48.1
(14.1)
47.2
(13.8)
45.9
(13.5)
Sens BTUH
(kW)
31.1
(9.1)
29.7
(8.7)
27.6
(8.1)
40.2
(11.8)
38.4
(11.3)
35.7
(10.5)
43.7
(12.8)
41.8
(12.2)
38.9
(11.4)
Power (kW)
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
85
(29.4)
Total BTUH
(kW)
55.7
(16.3)
54.7
(16.0)
53.2
(15.6)
51.9
(15.2)
51.0
(15.0)
49.6
(14.5)
46.5
(13.6)
45.7
(13.4)
44.4
(13.0)
Sens BTUH
(kW)
30.9
(9.0)
29.5
(8.6)
27.4
(8.0)
40.0
(11.7)
38.2
(11.2)
35.5
(10.4)
43.5
(12.7)
41.6
(12.2)
38.7
(11.3)
Power (kW)
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.8
90
(32.2)
Total BTUH
(kW)
54.1
(15.9)
53.2
(15.6)
51.7
(15.2)
50.4
(14.8)
49.5
(14.5)
48.1
(14.1)
44.9
(13.2)
44.1
(12.9)
42.9
(12.6)
Sens BTUH
(kW)
30.4
(8.9)
29.1
(8.5)
27.0
(7.9)
39.5
(11.6)
37.7
(11.1)
35.1
(10.3)
43.1
(12.6)
41.1
(12.1)
38.3
(11.2)
Power (kW)
3.1
3.1
3.0
3.1
3.1
3.0
3.1
3.1
3.0
95
(35)
Total BTUH
(kW)
52.5
(15.4)
51.6
(15.1)
50.2
(14.7)
48.8
(14.3)
47 .9
(14 .0)
46.6
(13.7)
43.3
(12.7)
42.5
(12.5)
41.4
(12.1)
Sens BTUH
(kW)
29.7
(8.7)
28.4
(8.3)
26.4
(7.7)
38.8
(11.4)
37 .1
(10 .9)
34.5
(10.1)
42.4
(12.4)
40.5
(11.9)
37.7
(11.0)
Power (kW)
3.3
3.3
3.2
3.3
3 .3
3.2
3.3
3.3
3.2
100
(37.8)
Total BTUH
(kW)
50.9
(14.9)
50.0
(14.7)
48.7
(14.3)
47.2
(13.8)
46.3
(13.6)
45.1
(13.2)
41.7
(12.2)
41.0
(12.0)
39.9
(11.7)
Sens BTUH
(kW)
28.8
(8.4)
27.5
(8.1)
25.6
(7.5)
37.9
(11.1)
36.2
(10.6)
33.7
(9.9)
41.5
(12.2)
39.6
(11.6)
36.8
(10.8)
Power (kW)
3.5
3.5
3.5
3.5
3.5
3.4
3.5
3.5
3.4
105
(40.6)
Total BTUH
(kW)
49.3
(14.5)
48.5
(14.2)
47.1
(13.8)
45.6
(13.4)
44.8
(13.1)
43.5
(12.8)
40.1
(11.8)
39.4
(11.5)
38.3
(11.2)
Sens BTUH
(kW)
27.7
(8.1)
26.5
(7.8)
24.6
(7.2)
36.8
(10.8)
35.1
(10.3)
32.7
(9.6)
40.1
(11.8)
38.5
(11.3)
35.8
(10.5)
Power (kW)
3.8
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
110
(43.3)
Total BTUH
(kW)
47.7
(14.0)
46.9
(13.7)
45.6
(13.4)
44.0
(12.9)
43.2
(12.7)
42.0
(12.3)
38.5
(11.3)
37.8
(11.1)
36.8
(10.8)
Sens BTUH
(kW)
26.3
(7.7)
25.2
(7.4)
23.4
(6.9)
35.4
(10.4)
33.8
(9.9)
31.5
(9.2)
38.5
(11.3)
37.2
(10.9)
34.6
(10.1)
Power (kW)
4.0
4.0
3.9
4.0
3.9
3.9
4.0
3.9
3.9
115
(46.1)
Total BTUH
(kW)
46.1
(13.5)
45.3
(13.3)
44.1
(12.9)
42.3
(12.4)
41.6
(12.2)
40.4
(11.9)
36.9
(10.8)
36.2
(10.6)
35.2
(10.3)
Sens BTUH
(kW)
24.7
(7.2)
23.6
(6.9)
22.0
(6.4)
33.8
(9.9)
32.3
(9.5)
30.1
(8.8)
36.9
(10.8)
35.7
(10.5)
33.2
(9.7)
Power (kW)
4.2
4.2
4.1
4.2
4.2
4.1
4.2
4.2
4.1
120
(48.9)
Total BTUH
(kW)
44.5
(13.0)
43.7
(12.8)
42.5
(12.5)
40.7
(11.9)
40.0
(11.7)
38.9
(11.4)
35.3
(10.3)
34.6
(10.1)
33.7
(9.9)
Sens BTUH
(kW)
22.9
(6.7)
21.9
(6.4)
20.4
(6.0)
32.0
(9.4)
30.6
(9.0)
28.4
(8.3)
35.3
(10.3)
34.0
(10.0)
31.6
(9.3)
Power (kW)
4.5
4.5
4.4
4.5
4.4
4.4
4.5
4.4
4.4
125
(51.7)
Total BTUH
(kW)
42.9
(12.6)
42.1
(12.3)
40.9
(12.0)
39.1
(11.5)
38.4
(11.2)
37.3
(10.9)
33.6
(9.9)
33.0
(9.7)
32.1
(9.4)
Sens BTUH
(kW)
20.9
(6.1)
19.9
(5.8)
18.5
(5.4)
30.0
(8.8)
28.6
(8.4)
26.6
(7.8)
33.5
(9.8)
32.0
(9.4)
29.8
(8.7)
Power (kW)
4.8
4.7
4.7
4.8
4.7
4.7
4.7
4.7
4.6
Note:
DR — Depression Ratio; dbE — Entering Air Dry Bulb; wbE — Entering Air Wet Bulb; Total — Total Capacity × 1000 BTUH; Sens — Sensible Capacity × 1000 BTUH Power–KW input
1. When the entering air dry bulb is other than 80°F (27°C), adjust the sensible capacity from the table by adding (1.10 × CFM × (1 – DR) × (dbE – 80))