Table 13: MPS H03C – H05C, High Efficiency
Model
H03C
H04C
H05C
Cooling Performance
1
Gross Cooling Capacity Btu (kW)
36,200 (10.61)
48,000 (14.06)
59,00 (17.29)
EER/SEER
2
12.5/15
12.5/15
11.6/14
EER (1st Stage/2nd Stage)
N/A
N/A
19.9/11.6
Nominal CFM/AHRI Rated CFM (L/s)
7
1200/1250 (566/590)
1600/1600 (755/755)
1375/1800 (649/849)
AHRI Net Cooling Capacity Btu (kW)
7
35,400 (10.37)
46,500 (13.62)
49,000/57,000 (14.3/16.7)
Net Sensible Capacity Btu (kW)
7
26,200 (7.68)
35,700 (10.46)
34/,800/40,800 (10.2/12.0)
Net Latent Capacity Btu (kW)
7
9,200 (2.72)
10,800 (3.52)
17,500 (5.13)
Net System Power kW
7
2.72
3.69
2.1/4.8
Compressor
No./Type
1/Scroll
1/Scroll
1/Scroll
Gas Heating Performance
AFUE %
81
81
81
Steady stage efficiency %
82
82
82
No. stages
1
1
1
Gas connection size
1/2"
1/2"
1/2"
Heating input (BtuH) low/medium/high
80,000/120,000
80,000/100,000/135,000
100,000/135,000
Heating output (BtuH)
64,800/97,200
64,800/81,000/109,400
81,000/109,400
Temperature rise °F
25-70
25-70
30 - 70
Sound
4
Outdoor Rating (dB)
78
78
83
Outdoor Coil
Fin Type
Louvered
Louvered
Louvered
Tube Type
Microchannel
Microchannel
Microchannel
Microchannel Depth in. (mm)
0.7 (18)
0.7 (18)
0.7 (18)
Face Area sq. ft. (sq. m)
13.9 (1.29)
16.4 (1.52)
16.4 (1.52)
Rows / FPI (FPcm)
1 / 23 (9)
1 / 23 (9)
1 / 23 (9)
Indoor Coil - Fin Type
Fin Type
Louvered
Louvered
Louvered
Tube Type
Microchannel
Microchannel
Microchannel
Microchannel Depth in. (mm)
1 (25)
1.3 (32)
1.3 (32)
Face Area sq. ft. (sq. m)
4.8 (0.45)
4.8 (0.45)
4.8 (0.45)
Rows / FPI (FPcm)
1/20 (8)
1/20 (8)
1/20 (8)
Refrigerant Control
TX Valves
TX Valves
TX Valves
Drain Connection No./Size in. (mm)
1/0.75 (19.05)
1/0.75 (19.05)
1/0.75 (19.05)
Outdoor Fan
Type
Propeller
Propeller
Propeller
No. Used/Diameter in. (mm)
1/24 (609.6)
1/24 (609.6)
1/24 (609.6)
Drive Type/No. Speeds
Direct/1
Direct/1
Direct/1
CFM (L/s)
3680 (1737)
3680 (1737)
3930 (1855)
No. Motors/HP
1 at 1/3 HP
1 at 1/3 HP
1 at 1/3 HP
Motor RPM
1075
1075
1075
Indoor Fan
Type
FC Centrifugal
FC Centrifugal
FC Centrifugal
No. Used/Diameter in. (mm)
1/10×10 (254×254)
1/10×10 (254×254)
1/11×10 (279×254)
Drive Type/No. Speeds
Direct/1 or Belt/Adjustable
Direct/1 or Belt/Adjustable
Belt/Adjustable
No. Motors
1
1
1
Motor HP
1/2
1/2 or 3/4
1
Motor RPM Direct Drive/Belt Drive
1075/1725
1075/1725
1725
Motor Frame Size5
48 or 56
48 or 56
56
Filter
Type
Disposable
Disposable
Disposable
Furnished
Yes
Yes
Yes
[NO.] Size Recommended in. (mm × mm × mm)
[1] 1×16×25 (25×406×635)
[1] 1×16×25 (25×406×635)
[1] 1×16×25 (25×406×635)
[1] 1×16×25 (25×406×635)
[1] 1×16×25 (25×406×635)
[1] 1×16×25 (25×406×635)
Refrigerant Charge Oz . (g)
Charge Oz. (g)
54 (1531)
68 (1928)
63
NOTES:
[ ] Designates Metric Conversions
1. Cooling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. AHRI capacity is net and includes
the effect of fan motor heat. Units are suitable for operation to ±20% of nominal CFM. Units are certified in accordance with the Unitary Air Conditioner Equipment certification program, which is
based on AHRI Standard 210/240 or 360.
2. EER and/or SEER are rated at AHRI conditions and in accordance with DOE test procedures.
3. Integrated Energy Efficiency Ratio (IEER) is rated in accordance with AHRI Standard 340/360.
4. Outdoor Sound Rating shown is tested in accordance with AHRI Standard 270.
5. Greater value indicates larger HP indoor fan motor
6. Heating Performance limit settings and rating data were established and approved under laboratory test conditions using ANSI standards.
7. Values shown for H05C model are both AHRI rated. (1st stage/2nd stage)