IM 970-2 • MAVERICK I ROOFTOP
Table 8: Recommended Wire Sizes For Given Conduit and Hole Size
Wire Size,
AWG
14
12
10
8
6
4
3
2
1
0
00
000
Conduit
Size
1/2"
1/2"
1/2"
3/4"
1"
1"
1-1/4"
1-1/4"
1-1/2"
1-1/2"
2"
2"
Hole Size
7/8"
7/8"
7/8"
1-31/32"
1-23/64"
1-23/64"
1-23/32"
1-23/32"
1-31/32"
1-31/32"
2-15/32"
2-15/32"
Hook-Up
To wire unit, refer to the following hook-up diagram. Refer to
Figure 27 on page 29
and
Figure 14
for location of wiring
entrances.
Wiring to be done in the field between the unit and devices not
attached to the unit, or between separate devices which are
field installed and located, shall conform with the temperature
limitation for Type T wire [63°F rise (35°C)] when installed in
accordance with the manufacturer’s instructions.
Internal Wiring
NOTICE
Some single phase units are equipped with a single pole contactor. Caution
must be exercised when servicing as only one leg of the power supply is
broken with the contactor.
Some models are equipped with electronically commutated
blower motors which are constantly energized, unless the main
unit disconnect is in the OFF position.
A diagram of the internal wiring of this unit is located under the
electrical box cover and this manual. If any of the original wire
as supplied with the unit must be replaced, the wire gauge and
insulation must be same as original wiring.
Transformer is factory wired for 230 volts on 208/230 volt
models and must be changed for 208 volt applications. See
unit wiring diagram for 208 volt wiring.