![background image](http://html1.mh-extra.com/html/daikin/maverick-i-mps-a03c/maverick-i-mps-a03c_installation-and-maintenance-manual_2460257028.webp)
IM 970-2 • MAVERICK I ROOFTOP 28 www.DaikinApplied.com
P
hysICal
d
aTa
Table 16: Miscellaneous Data
Electrical Data
A03
A04
A05
Unit Information
Unit Operating Voltage
Range
187-253
187-253
414-506
414-506
187-253
187-253
414-506
414-506
187-253
187-253
414-506
414-506
Volts
208/230
208/230
460
460
208/230
208/230
460
460
208/230
208/230
460
460
Minimum Circuit Ampacity
16/16
16/16
10
10
21/21
22/22
11
11
26/26
27/27
13
13
Minimum Overcurrent
Protection Device Size
20/20
20/20
15
15
25/25
25/25
15
15
30/30
35/35
15
15
Maximum Overcurrent
Protection Device Size
20/20
20/20
15
15
30/30
30/30
15
15
40/40
40/40
20
20
Compressor Motor
No.
1
1
1
1
1
1
1
1
1
1
1
1
Volts
208/230
208/230
460
460
208/230
208/230
460
460
208/230
208/230
460
460
Phase
3
3
3
3
3
3
3
3
3
3
3
3
RPM
3450
3450
3450
3450
3450
3450
3450
3450
3450
3450
3450
3450
HP, Compressor 1
3
3
3
3
4
4
4
4
5
5
5
5
Amps (RLA), Comp. 1
9/9
9/9
5.6
5.6
13.1/13.1 13.1/13.1
6.1
6.1
16/16
16/16
7.8
7.8
Amps (LRA), Comp. 1
71/71
71/71
38
38
83.1/83.1 83.1/83.1
41
41
110/110
110/110
52
52
Condenser Motor
No.
1
1
1
1
1
1
1
1
1
1
1
1
Volts
208/230
208/230
460
460
208/230
208/230
460
460
208/230
208/230
460
460
Phase
1
1
1
1
1
1
1
1
1
1
1
1
HP
1/3
1/3
1/3
1/3
1/3
1/3
1/3
1/3
1/3
1/3
1/3
1/3
Amps (FLA, each)
1.5/1.5
1.5/1.5
1
1
1.5/1.5
1.5/1.5
1
1
2.2/2.2
2.2/2.2
1
1
Amps (LRA, each)
3/3
3/3
1.9
1.9
3/3
3/3
1.9
1.9
4.9/4.9
4.9/4.9
1.9
1.9
Evaporator Fan
No.
1
1
1
1
1
1
1
1
1
1
1
1
Volts
208/230
208/230
460
460
208/230
208/230
460
460
208/230
208/230
460
460
Phase
3
3
3
3
3
3
3
3
3
3
3
3
HP
1/2
1/2
1/2
1/2
1/2
3/4
1/2
3/4
3/4
1
3/4
1
Amps (FLA, each)
2.8/2.8
2.8/2.8
1.4
1.4
2.8/2.8
3.4/3.4
1.4
1.6
3.4/3.4
4.1/4.1
1.6
2
Amps (LRA, each)
11.3/11.3 11.3/11.3
6.2
6.2
11.3/11.3 16.8/16.8
6.2
8.4
16.8/16.8
24/24
8.4
12