Run Test and Final Check

1.

Trial operation and testing.

1-1 Measure the supply voltage and make sure that it falls in the specified range.
1-2 Trial operation should be carried out in either cooling or heating mode.

In cooling mode, select the lowest programmable temperature; in heating mode, select the highest 
programmable temperature.
1) Trial operation may be disabled in either mode depending on the room temperature.

Use the remote controller for trial operation as described below.

2) After trial operation is complete, set the temperature to a normal level (78˚F to 82˚F (26˚C to 28˚C) in cooling 

mode, 68˚F to 75˚F (20˚C to 24˚C) in heating mode).

3) For protection, the unit disables restart operation for 3 minutes after it is turned off.

1-3 Carry out the test operation in accordance with the Operation Manual to ensure that all functions 

and parts, are working properly.

The air conditioner requires a small amount of power in its standby mode.  If the system is not to be used for 
some time after installation, shut off the circuit breaker to eliminate unnecessary power consumption.

If the circuit breaker trips to shut off the power to the air conditioner, the system will restore the original 
operation mode when the circuit breaker is opened again.

Test items

Incomplete cooling/heating function

No refrigerant gas leaks.

Drain line is properly installed.

Indoor and outdoor units are installed properly on 
solid bases.

Refrigerant gas and liquid pipes and indoor drain 
hose extension are thermally insulated.

Fall, vibration, noise

Water leakage

Water leakage

System is properly ground to earth.

Electrical leakage

Indoor unit properly receives remote controller 
commands.

Inoperative

Indoor or outdoor unit’s air intake or exhaust has 
clear path of air. 
Stop valves are opened.

Incomplete cooling/heating function

The specified wires are used for interconnecting 
wire connections.

Inoperative or burn damage

Symptom

Check

2.

Test items.

Trial operation from remote controller.

1) Press the MODE button and select the trial operation mode.
2) Press ON/OFF button to turn on the system.
3) Simultaneously press MODE button and both of TEMP button.
4) Press MODE button twice.

(“    ” will appear on the display to indicate that Trial Operation mode is selected.)

5) Trial run mode terminates in approx. 30 minutes and switches into normal mode. To quit a trial

operation, press ON/OFF button.

Summary of Contents for M08B055

Page 1: ...or death WARNING Installation should be left to the authorized dealer or another trained professional Improper installation may cause water leakage electrical shock fire or equipment damage Install th...

Page 2: ...and builds up around the unit it may catch fire Establish drain piping according to the instructions of this manual Inadequate piping may cause water damage Tighten the flare nut according to the spec...

Page 3: ...m ceiling Front panel 1 15 16 50mm or more from walls on both sides B 3 16 1 L M4 25mm The mounting plate should be installed on a wall which can support the weight of the indoor unit A Mounting plate...

Page 4: ...talled on a wall which can support the weight of the indoor unit 1 Temporarily secure the mounting plate to the wall make sure that the panel is completely level and mark the boring points on the wall...

Page 5: ...the bottom edge of indoor unit with both hands until it is firmly caught by the mounting plate hooks Secure indoor unit to the mounting plate with the screws 3 16 1 2 L M4 12mm 2 Boring a wall hole an...

Page 6: ...h terminal numbers on indoor and outdoor unit s terminal blocks and firmly screw wires to the corresponding terminals 3 Connect the earth wires to the corresponding terminals 4 Pull wires to make sure...

Page 7: ...aterials When using commercial copper pipes and fittings observe the following 1 Insulation material Polyethylene foam Heat transfer rate 0 041 to 0 052 W mK 0 024 to 0 030 Btu fth F 0 035 to 0 045 kc...

Page 8: ...f the circuit breaker trips to shut off the power to the air conditioner the system will restore the original operation mode when the circuit breaker is opened again Test items Incomplete cooling heat...

Reviews: