background image

Refrigerant Piping Work

1.

Flaring the pipe end.

1) Cut the pipe end with a pipe cutter.
2) Remove burrs with the cut surface facing 

downward so that the chips do not enter the pipe.

3) Put the flare nut on the pipe.
4) Flare the pipe.
5) Check that the flaring is properly made.

1) Do not use mineral oil on flared part.
2) Prevent mineral oil from getting into the system as this would reduce the unit life. 
3) Never use piping which has been used for previous installations. Only use parts which are provided with the unit.
4) Do never install a refrigerant drier to this unit.
5) The drying material may dissolve and damage the system.
6) Incomplete or improper flaring may cause refrigerant gas leakage.

WARNING

2.

Refrigerant piping.

1) Use the flare nut fixed to the main unit. (To prevent cracking of the flare nut by aged deterioration.)
2) To prevent gas leakage, apply refrigeration oil only to the inner surface of the flare. (Use refrigeration oil for R410A.)
3) Use torque wrenches when tightening the flare nuts to prevent damage to the flare nuts and gas leakage.

CAUTION

Align the centers of both flares and tighten the flare nuts 3 or 4 turns by hand.  Then tighten them fully with the torque wrenches.

Flare nut tightening torque

Gas side

Liquid side

3/8 inch

1/4 inch

24.1 - 29.4ft • Ibf

(32.7 - 39.9N • m)

10.4 - 12.7ft • Ibf

(14.2 - 17.2N • m)

2-1. Caution on piping handling

1) Protect the open end of the pipe against dust and moisture.
2) All pipe bends should be as gentle as possible. 

Use a pipe bender for bending. 

2-2. Selection of copper and heat insulation materials

When using commercial copper pipes and fittings, observe the following:

1) Insulation material:  Polyethylene foam

Heat transfer rate:  0.041 to 0.052 W/mK (0.024 to 0.030 Btu/fth˚F (0.035 to 0.045 kcal/mh˚C))
Refrigerant gas pipe’s surface temperature reaches 230˚F (110˚C) max.
Choose heat insulation materials that will withstand this temperature.

2) Be sure to insulate both the gas and liquid piping and to provide 

insulation dimensions as below.

3) Use separate thermal insulation pipes for gas and liquid refrigerant pipes.

Gas side

Liquid side

Gas pipe thermal insulation

Liquid pipe thermal insulation

O.D. 3/8 inch (9.5mm)

O.D. 1/4 inch (6.4mm)

I.D. 0.427 - 0.590 inch (12 - 15mm)

I.D. 0.315 - 0.393 inch (8 - 10mm)

Thickness 0.393 inch (8mm) Min.

Thickness 0.031 inch (0.8mm) (C1220T-O)

1-3/16 inch (30mm) or more

Minimum bend radius

(Cut exactly at 

right angles.)

 Remove burrs

Check

Flare’s inner 
surface must 
be flaw-free.

The pipe end must 
be evenly flared in 
a perfect circle.

Make sure that the 
flare nut is fitted.

Set exactly at the position shown below.

A

Flaring

Die

A

0 - 0.020 inch (0 - 0.5mm)

Clutch-type

Flare tool for R410A

0.039 - 0.059 inch (1.0 - 1.5mm)

Clutch-type (Rigid-type)

0.059 - 0.079 inch (1.5 - 2.0mm)

Wing-nut type (Imperial-type)

Conventional flare tool

Do not apply refrigeration 

oil to the outer surface.

Flare nut

Apply refrigeration 

oil to the inner 

surface of the flare.

Do not apply refrigeration 

oil to the flare nut avoid 

tightening with over torque.

[Apply oil]

Torque wrench

Piping union

Flare nut

Spanner

[Tighten]

Wall

If no flare cap is 
available, cover the 
flare mouth with 
tape to keep dirt or 
water out.

Be sure to 
place a cap.

Rain

Gas pipe

Liquid pipe

Gas pipe 
insulation

Liquid pipe 
insulation

Finishing tape

Drain hose

Inter-unit wiring

Summary of Contents for M08B055

Page 1: ...or death WARNING Installation should be left to the authorized dealer or another trained professional Improper installation may cause water leakage electrical shock fire or equipment damage Install th...

Page 2: ...and builds up around the unit it may catch fire Establish drain piping according to the instructions of this manual Inadequate piping may cause water damage Tighten the flare nut according to the spec...

Page 3: ...m ceiling Front panel 1 15 16 50mm or more from walls on both sides B 3 16 1 L M4 25mm The mounting plate should be installed on a wall which can support the weight of the indoor unit A Mounting plate...

Page 4: ...talled on a wall which can support the weight of the indoor unit 1 Temporarily secure the mounting plate to the wall make sure that the panel is completely level and mark the boring points on the wall...

Page 5: ...the bottom edge of indoor unit with both hands until it is firmly caught by the mounting plate hooks Secure indoor unit to the mounting plate with the screws 3 16 1 2 L M4 12mm 2 Boring a wall hole an...

Page 6: ...h terminal numbers on indoor and outdoor unit s terminal blocks and firmly screw wires to the corresponding terminals 3 Connect the earth wires to the corresponding terminals 4 Pull wires to make sure...

Page 7: ...aterials When using commercial copper pipes and fittings observe the following 1 Insulation material Polyethylene foam Heat transfer rate 0 041 to 0 052 W mK 0 024 to 0 030 Btu fth F 0 035 to 0 045 kc...

Page 8: ...f the circuit breaker trips to shut off the power to the air conditioner the system will restore the original operation mode when the circuit breaker is opened again Test items Incomplete cooling heat...

Reviews: