background image

IM 1068-2 / Page 22 of 28

Scheduled Maintenance

Incremental conditioners are built to last. With proper care, 

the unit should provide uninterrupted service for many years. 

Scheduled maintenance of this equipment, as described 

below, is the key to the equipment’s longevity. Air filters must 

be cleaned at regular intervals. Twice annually may be ad-

equate in some areas while twice monthly may be required in 

others. Areas with high dirt and lint content or heavy usage of 

units require more frequent filter maintenance that those areas 

of relatively clean operating or low usage conditions. Unit 

malfunction may occur if air filters are not kept clean.
The standard filter supplied with the Type K unit is a per-

manent wire mesh type. This type of filter should be rinsed 

with hot water and a mild detergent. Let dry and oil lightly to 

enhance dust collecting ability.
The Type K is also available with a carbon filter, a zeolite 

filter or electrostatic filter. The electrostatic filter is renewable 

by rinsing with hot water and replacing in the unit once dry. 

The carbon or zeolite filters must be discarded and replaced. 

The frequency of this replacement depends on the air quality 

of the room being filtered. Rooms with heavy smoke or am-

monia content will require more frequent filter changes than 

rooms with minimal degrees of smoke or ammonia.

Note:  When replacing the standard filter with an optional 

carbon, electrostatic, or zeolite filter, compress the 

filter brackets slightly. The optional filters are slightly 

thinner than the standard filter and will stay in place 

better if the brackets are squeezed slightly.

It is recommended that the chassis be removed every year for 

a thorough check-up. The heat section need not be removed 

but should be inspected or cleaned if necessary. 
Should the heat section blowers or motor need service, the e 

tire fan board can be easily removed from the unit for service. 

To access the unit for cleaning or service, proceed as follows:

 

WARNING

  Residential and institutional cleaning compounds can cause 

permanent damage to the packaged terminal unit. To avoid 

damage to unit controls and heat transfer surfaces, do not spray 

cleaning compounds onto the return air opening or unit controls.

  Normal cleaning can be accomplished by wiping the unit surface 

with a damp cloth. When using cleaning compounds on carpets, 

floors  or  walls,  turn  the  unit  off  to  avoid  drawing  potentially   

damaging vapors into the package terminal unit.

1.  Disconnect power to the unit.
2.  Remove the front panel and the kickplate.
3.  Unplug the chassis from the control box and remove the 

chassis from the wall sleeve. Replace with spare chassis or 

weatherplate.

4.  Move chassis to maintenance area and check all seals, 

wires, and insulation and repair as required.

5.  Cover motor and protect all electrical components before 

washing dirt from chassis.

6.  Clean condensate drain and clear weep holes.
7.  Dry equipment thoroughly, especially electric parts and 

insulation.

8.  Clean any rust spots with steel wool and paint with rustm 

inhibiting paint.

9.  Check all fasteners and tighten if necessary.
10. Check the motor nameplate for routine oiling instructions.
11. Test run chassis before reinstalling or returning to spare 

parts stock.

Recommended Spare Parts

An advantage of the Incremental system is that failure of 

anyone part affects only one Incremental conditioner and 

does not interrupt the operation of the rest of the system. 

A further advantage is that a failed part can be quickly and 

easily replaced, thus minimizing the inoperative time of the 

equipment. This is so, however, only if a replacement part is 

quickly available. In order to replace a failed part quickly and 

keep all Incremental conditioners in good operating condition, 

Daikin recommends that at the time Incremental conditioners 

are purchased, owners arrange for a small stock of replace-

ment parts.
Where an owner carries such a stock, immediate replacement 

of a defective part is possible. The defective part can then be 

returned to Daikin or one of its authorized service stations. So 

long as it is still in warranty, it is repaired or replaced and re-

turned to the owner without cost for shop labor and material. 

Thus, the stock of replacement parts is constantly replenished. 

To the right is listed the kind of parts which Daikin recom-

mends be carried in stock, together with the quantity of parts 

recommended per 100 Incremental conditioners installed.

 

Qty. Per 

Part Name 

100 Units

Cooling Chassis ...................................................................... 1
Compressor Overload Device ................................................. 1
Compressor Running Capacity ............................................... 1
Indoor Fan Motor .................................................................... 1
Outdoor Fan Motor ................................................................. 1
Outdoor Fan Motor Capacitor ................................................. 1
Push button Switch ................................................................. 2
Damper Switch ........................................................................ 2
Thermostat .............................................................................. 2
Knob for Thermostat ............................................................... 6
Control Relay .......................................................................... 2
Damper Motor ......................................................................... 2
Hydronic Valve ....................................................................... 4
Spare Filter ............................................................................ 10
Touch-up Paint (1 Pt. Spray Can) ........................................... 1

For the current spare parts list, and applicable prices, see our 

Daikin representative or write:  

DaikinMcQuayService, P.O Box 1551, Minneapolis, MN 

55440.

Summary of Contents for IM 1068-2

Page 1: ...ackaged Terminal Air Conditioner Incremental Room Conditioner with R 410A Refrigerant Group PTAC Part No 910146464 Date October 2013 Installation Maintenance Data IM 1068 2 2013 Daikin Applied www DaikinAP com 800 432 1342 ...

Page 2: ...ts With Hydronic Heat 11 Room Cabinet and Control Installation 13 Equipment Start up 14 Remote Mounted Thermostat Installation 15 Typical Wiring Diagrams 16 Standard Chassis With Electric Heat MCO Controls 16 Standard Chassis With Hot Water Heat MCO Controls 17 Standard Chassis With Steam Heat MCO Controls 18 Standard Chassis With Electric Heat 24V Wall Stat 19 Standard Chassis With Hot Water Heat...

Page 3: ...al 50 7 7 kW nominal 62 Hydronic Normally Open Valve Hot Water 63 Hydronic Normally Closed Valve Steam Hand Orientation A Same Hand Left B Same Hand Right N LH Supply RH Return P RH Supply LH Return Z Not Applicable Product Style 1 1st Style Change SKU A Stock B Standard Delivery C Extended Lead time Color I Antique Ivory Power Connection A Junction Box Return Air Outdoor Air 14 Bottom Discharge A...

Page 4: ... cartons have been received All units should be carefully in spected for damage when received If any damage is noticed the carrier should make the proper notation on the delivery receipt acknowledging the damage The carrier should also fill out a Carrier Inspection Report The Daikin Traffic Department should then be contacted The unit nameplate should be checked to make sure the volt age agrees wi...

Page 5: ...above the floor The standard adjustable kickplate can be telescoped to hide the space below the wall box Complete wall box installation instructions can found on page 6 CAUTION Sheet metal parts self tapping screws clips and such items in herently have sharp edges and it is necessary that the installer exercise caution This equipment is to be installed only by an experienced installation company w...

Page 6: ...he thickness of the wall the louver the amount the louver is recessed into the wall if any and the amount the wall box extends into the room The minimum B dimension is 21 2 64mm The wall box can be factory furnished in increments between 21 2 64mm and 10 254mm Wall box extensions in 1 25mm increments can also be provided to at tach to the rear of the wall box NOTICE 5 Place 2 51mm fiberglass batt ...

Page 7: ... the Type K cooling chassis but packaged and shipped separately Check the heat section carton label and the unit s nameplate to ensure it is correct for the cooling chassis and the space The following steps should be followed when installing the heat section 1 Remove the heater from the shipping carton and examine for concealed damage Report any damage found to the carrier The control is packaged ...

Page 8: ... this may cause erratic operation of the thermostat 10 Protect the heat section from damage during construction Do not operate the heat section without a filter or the warranty will be void Suggested Piping Arrangements Hot Water Supply Figure 6 Detail A Hot Water Supply R H Retun L H W S T V C L Return Stub 2 51mm 25 8 67mm Figure 7 Detail C Hot water supply R H return R H U T V W C L 1 25mm 2 51...

Page 9: ...al between chassis and wall box to ensure that it has not been unseated from slot during chassis installation Cooling Chassis Installation 1 Remove the cooling chassis from the shipping carton and examine it for damage Do not rest it on end Check the plate rating against the power supply to make sure that they are the same Figure 14 Also check the size capacity to make sure that it coincides with ...

Page 10: ...as follows Units With Electric Heat A 4 4 electrical junction box is located on the left side of the heat section Field wiring should be brought to this point for power to the unit See Figure 15 Figure 15 Electric Heat Section B Front View Side View A M E K J H Long Control Box D Room Cabinet Mounting Holes 4 Room Cabinet Heat Section Power Cord 8 203mm G 1 2 12mm 1 4 6mm Wall Box Cooling Chassis ...

Page 11: ...with emergency standby ESB power supply Side View Room Cabinet Removed Front View A M J K L D Junction Box 8 203mm Short Control Box Room Cabinet Room Cabinet Mounting Holes 4 1 2 12mm 1 4 6mm G F B P N E Wall Box Hydronic Coil H A D E F G H J K L M N P in 453 4 37 251 2 241 2 1311 16 227 8 10 16 41 2 11 2 143 4 13 4 mm 1162 940 648 622 348 581 254 406 114 38 375 44 Notes See Figure 6 through Figu...

Page 12: ...rol GRC Night Setback NSB and remote thermostats Left hand piping must be used with the long control box design Side View Room Cabinet Removed Front View 8 203mm Long Control Box Room Cabinet Room Cabinet Mounting Holes 4 1 2 12mm 1 4 6mm B F G Cool Chassis Power Cord Heat Chassis Power Cord Flexible Conduit Power Supply Cord Junction Box By Others H A M J K L D Wall Box Hydronic Coil E A D E F G ...

Page 13: ...n and cool chassis and push the cabinet firmly against the wall The discharge grille seals should rest on the discharge opening of the heat section 3 Fasten the cabinet to the wall using appropriate fasteners The back flanges of the room cabinet have factory furnished holes for securing the cabinet to the wall Figure 19 Unit Cabinet Assembly Details Installation 4 Fasten the two 2 end plates to th...

Page 14: ...quipment Start up Initial start up of the McQuay equipment by an experienced person is usually the responsibility of the installing contractor This consists of inspecting and operating the equipment for all functions at the time of initial installation and making adjustments as necessary It also includes demonstrating its proper operation to the owners or their agents Note That unless otherwise sp...

Page 15: ...of the slave unit as shown in Figure 23 The master unit is furnished with a 50 VA transformer that is capable of handling up to 7 slave units If additional slave units are to be added a larger field supplied transformer must be mounted external to the unit The master and slave units draw 5 6 VA each Furnish a transformer to handle the number of slaves installed plus the master unit 2 When using a ...

Page 16: ...l R3 Relay Night Setback NSB R4 Relay Guest Room Control GRC R5 Relay Hot Water Valve R6 Relay Control R7 Relay Night Setback NSB S1 Control Switch S2 Fan Speed Switch S3 Fan Cycle Switch S4 Damper Switch T1 Transformer TB1 Terminal Block Control Box TB2 Terminal Board 24V Control Box TB3 Terminal Board Heat Section TB4 Terminal Board Cool Section TB6 Terminal Box TC1 Room Thermostat TC2 Night Set...

Page 17: ...l R3 Relay Night Setback NSB R4 Relay Guest Room Control GRC R5 Relay Hot Water Valve R6 Relay Control R7 Relay Night Setback NSB S1 Control Switch S2 Fan Speed Switch S3 Fan Cycle Switch S4 Damper Switch T1 Transformer TB1 Terminal Block Control Box TB2 Terminal Board 24V Control Box TB3 Terminal Board Heat Section TB4 Terminal Board Cool Section TB6 Terminal Box TC1 Room Thermostat TC2 Night Set...

Page 18: ...R3 Relay Night Setback NSB R4 Relay Guest Room Control GRC R5 Relay Hot Water Valve R6 Relay Control R7 Relay Night Setback NSB S1 Control Switch S2 Fan Speed Switch S3 Fan Cycle Switch S4 Damper Switch T1 Transformer TB1 Terminal Block Control Box TB2 Terminal Board 24V Control Box TB3 Terminal Board Heat Section TB4 Terminal Board Cool Section TB6 Terminal Box TC1 Room Thermostat TC2 Night Setba...

Page 19: ...o Cool Section R1 Relay Heat R2 Relay Cool R3 Relay Night Setback NSB R4 Relay Guest Room Control GRC R5 Relay Hot Water Valve R6 Relay Control R7 Relay Night Setback NSB S2 Fan Speed Switch S3 Fan Cycle Switch S4 Damper Switch T1 Transformer TB1 Terminal Block Control Box TB2 Terminal Board 24V Control Box TB3 Terminal Board Heat Section TB4 Terminal Board Cool Section TB6 Terminal Box TC1 Room T...

Page 20: ...ection R1 Relay Heat R2 Relay Cool R3 Relay Night Setback NSB R4 Relay Guest Room Control GRC R5 Relay Hot Water Valve R6 Relay Control R7 Relay Night Setback NSB S1 Control Switch S2 Fan Speed Switch S3 Fan Cycle Switch S4 Damper Switch T1 Transformer TB1 Terminal Block Control Box TB2 Terminal Board 24V Control Box TB3 Terminal Board Heat Section TB4 Terminal Board Cool Section TB6 Terminal Box ...

Page 21: ...tion R1 Relay Heat R2 Relay Cool R3 Relay Night Setback NSB R4 Relay Guest Room Control GRC R5 Relay Hot Water Valve R6 Relay Control R7 Relay Night Setback NSB S1 Control Switch S2 Fan Speed Switch S3 Fan Cycle Switch S4 Damper Switch T1 Transformer TB1 Terminal Block Control Box TB2 Terminal Board 24V Control Box TB3 Terminal Board Heat Section TB4 Terminal Board Cool Section TB6 Terminal Box TC...

Page 22: ... walls turn the unit off to avoid drawing potentially damaging vapors into the package terminal unit 1 Disconnect power to the unit 2 Remove the front panel and the kickplate 3 Unplug the chassis from the control box and remove the chassis from the wall sleeve Replace with spare chassis or weatherplate 4 Move chassis to maintenance area and check all seals wires and insulation and repair as requir...

Page 23: ...a short interval 4 Blowers run on Cool and compressor starts and runs but compressor occasionally stops on overload device 5 Compressor starts and runs on Cool but blowers do not run 6 Compressor starts and runs on Cool but fan motor starts then stops 7 Equipment gives electrical shock 8 Insufficient cooling capacity If equipment is in warranty a No power b Faulty push button switch c Loose connec...

Page 24: ... short circuit or a grounded condition in the circuit c Replace d Replace wire or tighten e Adjust rotate knob to Warm f Replace g Replace h 1 Temporarily lock valve open replace 2 Replace 8 Insufficient cooling capacity continued 9 Too much cooling 10 Sweating 11 Blowers won t operate on Heat 12 Equipment is noisy 13 Insufficient or no heat d Heat load in room exceeds capacity of equipment e Wind...

Page 25: ...3 lbs Hydronic Heat Section With Control Size 007 65 lbs Size 009 65 lbs Size 012 65 lbs Size 014 65 lbs Electric Heat Section With Control Size 007 60 lbs Size 009 60 lbs Size 012 60 lbs Size 014 60 lbs Wall Box With Rear Extension of Sizes 007 014 2 45 lbs 3 46 lbs Room Cabinet Sizes 007 014 7 44 lbs 8 48 lbs Louver 007 014 6 lbs ...

Page 26: ...IM 1068 2 Page 26 of 28 ...

Page 27: ...IM 1068 2 Page 27 of 28 ...

Page 28: ...ld pursuant to its standard terms and conditions of sale including Limited Product Warranty Consult your local Daikin Representative for warranty details Refer to Form 933 430285Y To find your local Daikin Representative go to www DaikinAP com Aftermarket Services To find your local parts office visit www DaikinAP com or call 800 37PARTS 800 377 2787 To find your local service office visit www Dai...

Reviews: