background image

IM 1068-2 / Page 14 of 28

Installation

 

Figure 21: Remove the Escutcheon Plate and Control 

Knob

8.  While holding the control box in position, set the 

escutcheon plate in place on the flanges beneath the 

control door.

9.  Using the two screws removed in Step 7, secure the 

control box and escutcheon plate to the room cabinet.

10. Replace the thermostat control knob.
11. Connect the power cord from the heat section to the 

bottom of the control box. Plug in the cord from the 

control box to the receptacle in the cooling chassis.

12. Move the thermostat bulb to the cooling chassis and 

secure it to the snap clips provided. Inspect the filter to be 

sure it is securely in place.

13. Loosen the wing nuts on the nose piece that is attached 

to the heat section. Slide the nose piece toward the room 

cabinet until it makes contact. Tighten wing nuts to secure 

the nose piece in place. This nose piece prevents air from 

leaking back into the cabinet and giving the thermostat a 

false reading.

14. Before replacing the front panel, replace the tie bar (if it 

has been removed) and lock the latches. Then retrieve the 

front panel and replace it by sliding it in and downward 

into the room cabinet. See Figure 22.

Note:  Tie bar latches must be in and locked before installing 

the front panel.

15. Wipe cabinet with a soft cloth to remove smudges. If 

required, use a mild, nonabrasive cleanser.

Figure 22: Unit Cabinet Assembly Details

Equipment Start-up

Initial start-up of the McQuay equipment by an experienced 

person is usually the responsibility of the installing contractor.
This consists of inspecting and operating the equipment for 

all functions at the time of initial installation, and making 

adjustments as necessary. It also includes demonstrating its 

proper operation to the owners or their agents. 

Note:  That unless otherwise specifically agreed to in writing, 

there is no field labor or start-up service included in the 

price of the equipment.

The Type K unit is furnished with a concealed fan cycle 

rocker switch on the control box. Before start-up, open the 

front panel and place this switch in the “cycle” position.
Continue start-up procedures as follows:
1.  Check the main power supply to be sure there is power to  

the unit.

2.  Open the control access door and press the button labeled 

F-Fan. The indoor fans should be energized.

3.  Move the fan speed rocker switch from “Low Fan” to 

“High Fan” and back again. The fan speed should change.

4.  Depress the button marked H-Heat. Turn the thermostat 

knob completely counterclockwise. The electric heat 

elements or the hydronic valve should become energized 

and noticeable heat should be felt at the discharge grille.

5.  Depress the C-Cool button and move the thermostat 

completely clockwise. The compressor and condenser fan 

should come on and the air from the discharge should feel 

cold.

6.  Depress the S-Stop button and all functions of the unit 

should stop.

 

CAUTION

  The stop button does not disconnect power to the unit. Before 

servicing the equipment, disconnect the unit from the power 

source.

Summary of Contents for IM 1068-2

Page 1: ...ackaged Terminal Air Conditioner Incremental Room Conditioner with R 410A Refrigerant Group PTAC Part No 910146464 Date October 2013 Installation Maintenance Data IM 1068 2 2013 Daikin Applied www DaikinAP com 800 432 1342 ...

Page 2: ...ts With Hydronic Heat 11 Room Cabinet and Control Installation 13 Equipment Start up 14 Remote Mounted Thermostat Installation 15 Typical Wiring Diagrams 16 Standard Chassis With Electric Heat MCO Controls 16 Standard Chassis With Hot Water Heat MCO Controls 17 Standard Chassis With Steam Heat MCO Controls 18 Standard Chassis With Electric Heat 24V Wall Stat 19 Standard Chassis With Hot Water Heat...

Page 3: ...al 50 7 7 kW nominal 62 Hydronic Normally Open Valve Hot Water 63 Hydronic Normally Closed Valve Steam Hand Orientation A Same Hand Left B Same Hand Right N LH Supply RH Return P RH Supply LH Return Z Not Applicable Product Style 1 1st Style Change SKU A Stock B Standard Delivery C Extended Lead time Color I Antique Ivory Power Connection A Junction Box Return Air Outdoor Air 14 Bottom Discharge A...

Page 4: ... cartons have been received All units should be carefully in spected for damage when received If any damage is noticed the carrier should make the proper notation on the delivery receipt acknowledging the damage The carrier should also fill out a Carrier Inspection Report The Daikin Traffic Department should then be contacted The unit nameplate should be checked to make sure the volt age agrees wi...

Page 5: ...above the floor The standard adjustable kickplate can be telescoped to hide the space below the wall box Complete wall box installation instructions can found on page 6 CAUTION Sheet metal parts self tapping screws clips and such items in herently have sharp edges and it is necessary that the installer exercise caution This equipment is to be installed only by an experienced installation company w...

Page 6: ...he thickness of the wall the louver the amount the louver is recessed into the wall if any and the amount the wall box extends into the room The minimum B dimension is 21 2 64mm The wall box can be factory furnished in increments between 21 2 64mm and 10 254mm Wall box extensions in 1 25mm increments can also be provided to at tach to the rear of the wall box NOTICE 5 Place 2 51mm fiberglass batt ...

Page 7: ... the Type K cooling chassis but packaged and shipped separately Check the heat section carton label and the unit s nameplate to ensure it is correct for the cooling chassis and the space The following steps should be followed when installing the heat section 1 Remove the heater from the shipping carton and examine for concealed damage Report any damage found to the carrier The control is packaged ...

Page 8: ... this may cause erratic operation of the thermostat 10 Protect the heat section from damage during construction Do not operate the heat section without a filter or the warranty will be void Suggested Piping Arrangements Hot Water Supply Figure 6 Detail A Hot Water Supply R H Retun L H W S T V C L Return Stub 2 51mm 25 8 67mm Figure 7 Detail C Hot water supply R H return R H U T V W C L 1 25mm 2 51...

Page 9: ...al between chassis and wall box to ensure that it has not been unseated from slot during chassis installation Cooling Chassis Installation 1 Remove the cooling chassis from the shipping carton and examine it for damage Do not rest it on end Check the plate rating against the power supply to make sure that they are the same Figure 14 Also check the size capacity to make sure that it coincides with ...

Page 10: ...as follows Units With Electric Heat A 4 4 electrical junction box is located on the left side of the heat section Field wiring should be brought to this point for power to the unit See Figure 15 Figure 15 Electric Heat Section B Front View Side View A M E K J H Long Control Box D Room Cabinet Mounting Holes 4 Room Cabinet Heat Section Power Cord 8 203mm G 1 2 12mm 1 4 6mm Wall Box Cooling Chassis ...

Page 11: ...with emergency standby ESB power supply Side View Room Cabinet Removed Front View A M J K L D Junction Box 8 203mm Short Control Box Room Cabinet Room Cabinet Mounting Holes 4 1 2 12mm 1 4 6mm G F B P N E Wall Box Hydronic Coil H A D E F G H J K L M N P in 453 4 37 251 2 241 2 1311 16 227 8 10 16 41 2 11 2 143 4 13 4 mm 1162 940 648 622 348 581 254 406 114 38 375 44 Notes See Figure 6 through Figu...

Page 12: ...rol GRC Night Setback NSB and remote thermostats Left hand piping must be used with the long control box design Side View Room Cabinet Removed Front View 8 203mm Long Control Box Room Cabinet Room Cabinet Mounting Holes 4 1 2 12mm 1 4 6mm B F G Cool Chassis Power Cord Heat Chassis Power Cord Flexible Conduit Power Supply Cord Junction Box By Others H A M J K L D Wall Box Hydronic Coil E A D E F G ...

Page 13: ...n and cool chassis and push the cabinet firmly against the wall The discharge grille seals should rest on the discharge opening of the heat section 3 Fasten the cabinet to the wall using appropriate fasteners The back flanges of the room cabinet have factory furnished holes for securing the cabinet to the wall Figure 19 Unit Cabinet Assembly Details Installation 4 Fasten the two 2 end plates to th...

Page 14: ...quipment Start up Initial start up of the McQuay equipment by an experienced person is usually the responsibility of the installing contractor This consists of inspecting and operating the equipment for all functions at the time of initial installation and making adjustments as necessary It also includes demonstrating its proper operation to the owners or their agents Note That unless otherwise sp...

Page 15: ...of the slave unit as shown in Figure 23 The master unit is furnished with a 50 VA transformer that is capable of handling up to 7 slave units If additional slave units are to be added a larger field supplied transformer must be mounted external to the unit The master and slave units draw 5 6 VA each Furnish a transformer to handle the number of slaves installed plus the master unit 2 When using a ...

Page 16: ...l R3 Relay Night Setback NSB R4 Relay Guest Room Control GRC R5 Relay Hot Water Valve R6 Relay Control R7 Relay Night Setback NSB S1 Control Switch S2 Fan Speed Switch S3 Fan Cycle Switch S4 Damper Switch T1 Transformer TB1 Terminal Block Control Box TB2 Terminal Board 24V Control Box TB3 Terminal Board Heat Section TB4 Terminal Board Cool Section TB6 Terminal Box TC1 Room Thermostat TC2 Night Set...

Page 17: ...l R3 Relay Night Setback NSB R4 Relay Guest Room Control GRC R5 Relay Hot Water Valve R6 Relay Control R7 Relay Night Setback NSB S1 Control Switch S2 Fan Speed Switch S3 Fan Cycle Switch S4 Damper Switch T1 Transformer TB1 Terminal Block Control Box TB2 Terminal Board 24V Control Box TB3 Terminal Board Heat Section TB4 Terminal Board Cool Section TB6 Terminal Box TC1 Room Thermostat TC2 Night Set...

Page 18: ...R3 Relay Night Setback NSB R4 Relay Guest Room Control GRC R5 Relay Hot Water Valve R6 Relay Control R7 Relay Night Setback NSB S1 Control Switch S2 Fan Speed Switch S3 Fan Cycle Switch S4 Damper Switch T1 Transformer TB1 Terminal Block Control Box TB2 Terminal Board 24V Control Box TB3 Terminal Board Heat Section TB4 Terminal Board Cool Section TB6 Terminal Box TC1 Room Thermostat TC2 Night Setba...

Page 19: ...o Cool Section R1 Relay Heat R2 Relay Cool R3 Relay Night Setback NSB R4 Relay Guest Room Control GRC R5 Relay Hot Water Valve R6 Relay Control R7 Relay Night Setback NSB S2 Fan Speed Switch S3 Fan Cycle Switch S4 Damper Switch T1 Transformer TB1 Terminal Block Control Box TB2 Terminal Board 24V Control Box TB3 Terminal Board Heat Section TB4 Terminal Board Cool Section TB6 Terminal Box TC1 Room T...

Page 20: ...ection R1 Relay Heat R2 Relay Cool R3 Relay Night Setback NSB R4 Relay Guest Room Control GRC R5 Relay Hot Water Valve R6 Relay Control R7 Relay Night Setback NSB S1 Control Switch S2 Fan Speed Switch S3 Fan Cycle Switch S4 Damper Switch T1 Transformer TB1 Terminal Block Control Box TB2 Terminal Board 24V Control Box TB3 Terminal Board Heat Section TB4 Terminal Board Cool Section TB6 Terminal Box ...

Page 21: ...tion R1 Relay Heat R2 Relay Cool R3 Relay Night Setback NSB R4 Relay Guest Room Control GRC R5 Relay Hot Water Valve R6 Relay Control R7 Relay Night Setback NSB S1 Control Switch S2 Fan Speed Switch S3 Fan Cycle Switch S4 Damper Switch T1 Transformer TB1 Terminal Block Control Box TB2 Terminal Board 24V Control Box TB3 Terminal Board Heat Section TB4 Terminal Board Cool Section TB6 Terminal Box TC...

Page 22: ... walls turn the unit off to avoid drawing potentially damaging vapors into the package terminal unit 1 Disconnect power to the unit 2 Remove the front panel and the kickplate 3 Unplug the chassis from the control box and remove the chassis from the wall sleeve Replace with spare chassis or weatherplate 4 Move chassis to maintenance area and check all seals wires and insulation and repair as requir...

Page 23: ...a short interval 4 Blowers run on Cool and compressor starts and runs but compressor occasionally stops on overload device 5 Compressor starts and runs on Cool but blowers do not run 6 Compressor starts and runs on Cool but fan motor starts then stops 7 Equipment gives electrical shock 8 Insufficient cooling capacity If equipment is in warranty a No power b Faulty push button switch c Loose connec...

Page 24: ... short circuit or a grounded condition in the circuit c Replace d Replace wire or tighten e Adjust rotate knob to Warm f Replace g Replace h 1 Temporarily lock valve open replace 2 Replace 8 Insufficient cooling capacity continued 9 Too much cooling 10 Sweating 11 Blowers won t operate on Heat 12 Equipment is noisy 13 Insufficient or no heat d Heat load in room exceeds capacity of equipment e Wind...

Page 25: ...3 lbs Hydronic Heat Section With Control Size 007 65 lbs Size 009 65 lbs Size 012 65 lbs Size 014 65 lbs Electric Heat Section With Control Size 007 60 lbs Size 009 60 lbs Size 012 60 lbs Size 014 60 lbs Wall Box With Rear Extension of Sizes 007 014 2 45 lbs 3 46 lbs Room Cabinet Sizes 007 014 7 44 lbs 8 48 lbs Louver 007 014 6 lbs ...

Page 26: ...IM 1068 2 Page 26 of 28 ...

Page 27: ...IM 1068 2 Page 27 of 28 ...

Page 28: ...ld pursuant to its standard terms and conditions of sale including Limited Product Warranty Consult your local Daikin Representative for warranty details Refer to Form 933 430285Y To find your local Daikin Representative go to www DaikinAP com Aftermarket Services To find your local parts office visit www DaikinAP com or call 800 37PARTS 800 377 2787 To find your local service office visit www Dai...

Reviews: