For control with 2 remote controllers, set one remote con-
troller as main and the other remote controller as sub.
< Changeover method from main to sub and vice versa >
Refer to the installation manual attached to the remote
controller.
< Wiring method >
4GOQXGVJGEQPVTQNDQZNKFCEEQTFKPIVQVJGp
9+4
-
ING CONNECTION METHOD
”.
Carry out additional wiring from the remote controller
2 (Sub) to the terminals (P1·P2) for remote controller
YKTKPIQPVJGVGTOKPCNDNQEM:/KPVJGEQPVTQNDQZ
Fig. 43
No polarity
Remote controller 2
(Sub)
Remote controller 1
(Main)
Terminal block (X1M) for
remote controller wiring (P1, P2)
< Caution >
When using the group control and the 2 remote controllers
control at the same time, connect the remote controller 2
(Sub) to the indoor unit at the end of the crossover wiring
(the largest No.).
4GHGTVQ(KI
Fig. 44
Indoor unit 1
Indoor unit 2
Indoor unit Largest No.
Crossover wiring
(Remote controller)
Remote
controller 1
(Main)
Remote
controller 2
(Sub)
FOR CENTRALIZED CONTROL
r
When centralized equipment (such as centralized control-
ler) is used for control, it is required to set the group No. on
the remote controller.
For details, refer to the manual attached to the centralized
equipment.
r
Connect the centralized equipment to the indoor unit con-
nected to the remote controller.
FOR REMOTE CONTROL (FORCED OFF OR
ON/OFF OPERATION)
9KTKPIOGVJQFCPFURGEKƂECVKQP
r
4GOQVGEQPVTQNKUCXCKNCDNGD[EQPPGEVKPIVJGGZVGTPCN
input to the terminals T1 and T2 on the terminal block
for remote controller and transmission wiring.
FORCED
OFF
Input A
F2 T1 T2
9KTKPIURGEKƂECVKQP
Sheathed vinyl cord or 2 core cable
Gauge
AWG18-16 (0.75-1.25 mm
2
)
Wiring length
/CZHVO
'ZVGTPCNEQPVCEV
URGEKƂECVKQP
Contact that can make and break the
min. load DC15 V, 1 mA
Actuation
r
Input A of FORCED OFF and ON/OFF OPERATION
will be as the table shown below.
In case of
FORCED
OFF
FORCED OFF by input
A of “ON” (Remote
controller prohibited)
Remote controller
permitted by input A
of “OFF”
In case of
ON/OFF
OPERATION
Operation by input A of
“OFF”
o
“ON”
Stop by input A of
“ON”
o
“OFF”
(3) How to choose FORCED OFF or ON/OFF OPERA-
TION
r
For choosing FORCED OFF or ON/OFF OPERATION,
setting by remote controller is required.
(Refer to “
9. FIELD SETTING AND TEST OPERATION
”)
Summary of Contents for FXUQ PVJU Series
Page 1: ...EDUS391437 F15 FXUQ PVJU 4 Way Blow Ceiling Suspended Type ...
Page 2: ......
Page 14: ...Sound Levels Reference Data EDUS391437 F15 12 FXUQ PVJU FXUQ30PVJU FXUQ36PVJU 4D090215A ...
Page 36: ...Installation Manual EDUS391437 F15 34 FXUQ PVJU C 3P161684 8T ...
Page 40: ...Detail of Optional Accessories EDUS391437 F15 38 FXUQ PVJU 1P383776 1 ...
Page 41: ...EDUS391437 F15 Detail of Optional Accessories FXUQ PVJU 39 1P383776 1 ...
Page 42: ......
Page 43: ......