Installation Manual
EDUS391437-F15
18
FXUQ-PVJU
3P161684-8T
3
3P161684-8T
English
Fig. 2
Indoor unit
Indoor unit
(NOTE 1)
Lighting
Exhaust
fan
Discharge
60 (1500)
or more
60 (1500) or more
80 (2000) or more
Distance between indoor units 160 (4000) or more
[unit: in. (mm)]
CAUTION
r
Install the indoor and outdoor units, power supply wiring,
remote controller wiring and transmission wiring at least
40 in. (1 m) away from televisions or radios to prevent im-
age interference or noise.
(Depending on the radio waves, a distance of 40 in. (1 m)
OC[PQVDGUWHƂEKGPVVQGNKOKPCVGVJGPQKUG
r
+PUVCNNVJGKPFQQTWPKVCUHCTCURQUUKDNGHTQOƃWQTGUEGPV
lamps. (NOTE 1)
NOTE
4GUVTKEVKQPCRRNKGUVQVJGGZRQUGFV[RGNKIJVKPIDWVFQGU
not apply to the recessed type.
When the air outlet is closed, the space shown with “
”
must have a distance of 1-3/16 in. (30 mm) or more.
3.
(QTUGVVKPIVJGCKTƃQYFKTGEVKQPQHJQTK\QPVCNDNCFGTGHGT
to the operation manual attached to the indoor unit and
remote controller.
Ceiling height
r
This indoor unit can be hung from the ceiling of which
height is up to 11-1/2 ft. (3.5 m) (models 30, 36: up to 13
ft. (4.0 m)).
r
*QYGXGTKHVJGEGKNKPIJGKIJVGZEGGFUHVO
(models 30, 36: 10-1/2 ft. (3.2 m)), it is necessary to set
on site from the remote controller. Refer to the section
“9. FIELD SETTING AND TEST OPERATION”
.
(3) Air discharge direction
Select the air discharge pattern according to the installa-
tion location.
In case of 2-way and 3-way, it is required to set on site
from the remote controller.
For details, see the section
“9. FIELD SETTING AND
TEST OPERATION”
.
(Caution) Since there are some restriction on the piping
connection side, make sure to select the air
discharge pattern from the
Fig. 3
.
The names of air outlet are shown in inscription by the
number of “
” marks on the underside of the air outlet.
4GHGTVQVJG(KI
Use hanging bolts for installation.
Investigate if the installation place can withstand the
mass of the indoor unit and, if necessary, hang the unit
with bolts after it is reinforced by beams etc.
(Refer to the installation pattern paper (11) for the mount-
ing pitch.)
Fig. 3
(Discharge pattern) (Views from the ceiling)
4-way discharge
3-way discharge
2-way discharge (optional blocking material kit 2-way
discharge is required)
1
3
2
4
1
2
2
4
1
3
2
1
2
4
For upward outlet piping, any outlet pattern can be selected.
: Backward outlet piping
(straight outlet)
: Rightward outlet piping
(piping needs to be bent)
The indication “ ” shows the refrigerant piping outlet
direction.
.
Name of air outlet
Indication on indoor unit
Indication on
indoor unit
No. of air outlet
Indoor unit
Air outlet 1
Air outlet 2
Air outlet 3
Air outlet 4
*
: This indication shows the air discharge direction.
Fig. 4
4
For cross-reference of air outlet No. to indication on indoor
unit
3. PREPARATION BEFORE INSTALLATION
Check the locations of indoor unit hanging bolts, pip-
ing outlet holes, drain piping outlet hole and electric
wirings inlet hole. (The drawing shows the view from
the ceiling.) (Refer to Fig. 5 and Fig. 6)
Summary of Contents for FXUQ PVJU Series
Page 1: ...EDUS391437 F15 FXUQ PVJU 4 Way Blow Ceiling Suspended Type ...
Page 2: ......
Page 14: ...Sound Levels Reference Data EDUS391437 F15 12 FXUQ PVJU FXUQ30PVJU FXUQ36PVJU 4D090215A ...
Page 36: ...Installation Manual EDUS391437 F15 34 FXUQ PVJU C 3P161684 8T ...
Page 40: ...Detail of Optional Accessories EDUS391437 F15 38 FXUQ PVJU 1P383776 1 ...
Page 41: ...EDUS391437 F15 Detail of Optional Accessories FXUQ PVJU 39 1P383776 1 ...
Page 42: ......
Page 43: ......