Installation Manual
EDUS391437-F15
20
FXUQ-PVJU
3P161684-8T
5
3P161684-8T
English
Fig. 9
Hanger
Hanger
Hanger
r
When carrying the indoor unit, hold it by the hanging metal
ƂVVKPIU
(Refer to Fig. 9)
*QYVQDNQEMVJGCKTQWVNGVHQTYC[QTYC[CKT
discharge
r
For 2-way air discharge, in addition to the attached block-
ing material, the optional blocking material kit for 2-way
discharge is required.
The attached blocking material and the optional blocking
material for 2-way discharge can be used in common for
any air outlet.
r
For 2-way air discharge, take precautions with the inclina-
tion of the indoor unit when installing. For details, follow
the instruction mentioned in the section “
+056#..#
-
TION OF THE INDOOR UNIT
”.
Remove the horizontal blade of the air outlet to be
DNQEMGF4GHGTVQ(KICPF(KI
Without applying force to the bearings, lift the horizontal
blade with both hands and remove it from the bearing at
the side of the motor not mounted.
After turning the horizontal blade backward, remove
the claw of the bearing on the motor side. Then, lift the
horizontal blade and remove it.
Fig. 10
2.
1.
Motor
Horizontal blade
Bend the horizontal
blade and remove it.
Fig. 11
1.
2.
*
Bearing
Claw parts
Bearing
Horizontal blade
Claw (Lift upward.)
Bend the horizontal
blade and pull it out.
Turn the horizontal
blade backward.
Lift the claw on
the bearing
side.
* When the horizontal blade is difficult to remove, slowly
push down the horizontal blade in the direction of this
arrow. The horizontal blade will become easier to remove.
Remove the
horizontal
blade.
Fix the blocking material to the air outlet.
4GHGTVQ(KICPF(KI
Insert the projected part (2 places) of the blocking mate-
rial into the clearance between the upper decoration
panel and the insulation.
Insert the bent part (2 places) at both ends of the block-
ing material into the clearance between the lower deco-
ration panel and the drain pan until you hear a clicking
sound.
When doing this work, lift the end of the lower decora-
tion panel slightly and insert the blocking material.
+HKVKUFKHƂEWNVVQKPUGTVKVƂTUVNQQUGPVJGUETGYUQPVJG
both sides of the lower decoration panel and then insert
it.
3.
Insert the bent part (2 places) inside the blocking mate-
rial into the clearance between the lower decoration
panel and the drain pan until you hear a clicking sound,
CPFVJGPƂZVJGDNQEMKPIOCVGTKCN
Summary of Contents for FXUQ PVJU Series
Page 1: ...EDUS391437 F15 FXUQ PVJU 4 Way Blow Ceiling Suspended Type ...
Page 2: ......
Page 14: ...Sound Levels Reference Data EDUS391437 F15 12 FXUQ PVJU FXUQ30PVJU FXUQ36PVJU 4D090215A ...
Page 36: ...Installation Manual EDUS391437 F15 34 FXUQ PVJU C 3P161684 8T ...
Page 40: ...Detail of Optional Accessories EDUS391437 F15 38 FXUQ PVJU 1P383776 1 ...
Page 41: ...EDUS391437 F15 Detail of Optional Accessories FXUQ PVJU 39 1P383776 1 ...
Page 42: ......
Page 43: ......