EDUS391437-F15
Installation Manual
FXUQ-PVJU
31
3P161684-8T
16
3P161684-8T
English
CAUTION FOR MENDING THE COVER
r
In case the cover for penetrating piping is cut off and used
as wiring penetrating hole, after the wiring connection is
ƂPKUJGFOGPFVJGEQXGT
r
Cut the sealing material (Small) (9) into two pieces and
wrap each wiring with each piece.
r
Seal the clearance around the wiring with putty and insulat-
KPIOCVGTKCNƂGNFUWRRN[
(If insects and small animals get into the indoor unit, short
EKTEWKVKPIOC[QEEWTKPUKFGVJGEQPVTQNDQZ
r
If the low voltage wiring (remote controller wiring, transmis-
sion wiring) and the high voltage wiring (power supply wir-
ing, ground wiring) are brought into the indoor unit from the
same place, they may be affected by electric noise (outside
noise) and cause malfunction or failure.
r
-GGRVJGFKUVCPEGQHKP|OODGVYGGPVJG
low voltage wiring (remote controller wiring, transmission
wiring) and the high voltage wiring (power supply wiring,
ground wiring) at anywhere outside the indoor unit.
If both the wiring are laid down together, they may be af-
fected by electric noise (outside noise) and cause malfunc-
tion or failure.
Sealing material (Small) (9)
Remote controller/
transmission wiring
Power supply wiring/
ground wiring
Fig. 39
Seal with putty and insulating
material.
WARNING
r
9JGPYKTKPIHQTOVJGYKTKPIQTFGTN[UQVJCVVJGEQPVTQNDQZ
lid can be securely fastened.
+HVJGEQPVTQNDQZNKFKUPQVKPRNCEGVJGYKTKPIOC[ƃQCVWR
QTDGUCPFYKEJGFD[VJGDQZCPFVJGNKFCPFECWUGGNGEVTKE
UJQEMUQTCƂTG
WIRING EXAMPLES
0QU[UVGO9JGPTGOQVGEQPVTQNNGTKUWUGFHQT
indoor unit >
L
1
L
2
L
1
L
2
IN/D OUT/D
F1 F2 F1 F2
Control box
L
1
L
2
F
1
P
2
P
1
F
2
T
1
T
2
F
1
F
2
T
1
T
2
F
1
F
2
T
1
T
2
F
1
F
2
T
1
T
2
L
1
L
2
Outdoor unit
No. 1
System
Indoor
unit A
Indoor
unit B
Indoor
unit C
Most
downstream
indoor unit
Power supply
single phase
208/230 V
60 Hz
Power supply
single phase
208/230 V
60 Hz
Power supply
single phase
208/230 V
60 Hz
Power supply
single phase
208/230 V
60 Hz
L
2
L
1
L
2
L
1
L
2
L
1
L
2
L
1
P
2
P
1
P
2
P
1
P
2
P
1
P
2
P
1
P
2
P
1
P
2
P
1
P
2
P
1
(KI
0QU[UVGO9JGPECTT[KPIQWVITQWREQPVTQNQT
remote controllers control >
Note: It is not necessary to designate indoor
unit address when using group
control. The address is automatically
set when power is activated.
L
1
L
2
L
1
L
2
L
1
L
2
Control box
Outdoor unit
No. 2
System
Indoor
unit A
Indoor
unit B
Indoor
unit C
Most
downstream
indoor unit
For use with 2
remote controllers
IN/D OUT/D
F
1
F
2
F
1
F
2
F
1
F
2
P
1
P
2
T
1
T
2
F
1
F
2
T
1
T
2
F
1
F
2
T
1
T
2
F
1
F
2
T
1
T
2
L
2
L
1
L
2
L
1
L
2
L
1
L
2
L
1
Power supply
single phase
208/230 V
60 Hz
Power supply
single phase
208/230 V
60 Hz
Power supply
single phase
208/230 V
60 Hz
Power supply
single phase
208/230 V
60 Hz
L
1
L
2
P
2
P
1
P
2
P
1
P
2
P
1
P
1
P
2
P
1
P
2
P
1
P
2
(KI
< No.3 system: When Branch Selector unit is used >
IN/D OUT/D
F
1
F
2
F
1
F
2
IN/D
OUT/D
F
1
F
2
F
1
F
2
L
1
L
2
F
1
F
2
P
1
P
2
T
1
T
2
Branch
Selector unit
Branch
Selector unit
No. 3
System
Outdoor unit
Indoor unit A
Most
downstream
indoor unit
Control box
Control box
IN/D
OUT/D
F
1
F
2
F
1
F
2
Control box
L
1
L
2
F
1
F
2
T
1
T
2
L
2
L
1
L
2
L
1
Power supply
single phase
208/230 V
60 Hz
Power supply
single phase
208/230 V
60 Hz
P
1
P
2
P
1
P
2
P
1
P
2
(KI
NOTE
r
Remote controller wiring and transmission wiring do not
have polarity.
WARNING
Be sure to install a ground leakage circuit breaker.
(CKNWTGVQFQUQOC[ECWUGGNGEVTKEUJQEMUCPFCƂTG
Summary of Contents for FXUQ PVJU Series
Page 1: ...EDUS391437 F15 FXUQ PVJU 4 Way Blow Ceiling Suspended Type ...
Page 2: ......
Page 14: ...Sound Levels Reference Data EDUS391437 F15 12 FXUQ PVJU FXUQ30PVJU FXUQ36PVJU 4D090215A ...
Page 36: ...Installation Manual EDUS391437 F15 34 FXUQ PVJU C 3P161684 8T ...
Page 40: ...Detail of Optional Accessories EDUS391437 F15 38 FXUQ PVJU 1P383776 1 ...
Page 41: ...EDUS391437 F15 Detail of Optional Accessories FXUQ PVJU 39 1P383776 1 ...
Page 42: ......
Page 43: ......