• Refer to Table 2 for the processing dimensions of the 

flare.

• Use the flare nut provided with the unit.

Apply ether oil or ester oil only to inner side of the 
flare

 and screw in the flare nut three to four turns first by 

hand at the time of connecting the flare nut. 

(Refer to Fig. 5)

• Refer to Table 2 for the corresponding tightening torque.

Table 2

CAUTION

Do not excessively tighten the flare nut.

Doing so will break the flare nut and refrigerant leakage may 
result.

Make sure that all parts around the flare are free of oil.

The drain pan and the resin part may be deteriorated if oil is 
attached.

• If no torque wrenches are available, refer to Table 3 as a 

standard.
When the flare nut is tightened with the spanner, the 
tightening torque should increase suddenly. Tighten the 
flare nut further for the corresponding angle shown in 
Table 3.

Table 3

(2) On completion of installation work, 

check that there is no 

gas leakage

.

(3) Refer to the illustration on the right-hand side and be sure to 

perform heat insulation work on the piping joints after gas 
leakage checks. 

(Refer to Fig. 6)

• Use the insulation for fitting (4) and (5) provided to the 

liquid piping and gas piping, respectively, and conduct 
heat insulation work.
(Tighten both edges of the insulation for fitting (4) and (5) 
for each joint with the clamp (8).)

• Make sure that the joint of the insulation for fitting (4) and 

(5) for the joint on the liquid piping and gas piping side 
faces upward.

• Wrap the middle sealing material (7) around the insula-

tion for fitting (4) and (5) for the joint (flare nut part).

CAUTION

Be sure to perform the heat insulation of the local piping 
up to the piping joint.

If the piping is exposed, dew condensation may result. Fur-
thermore, a burn may be caused if a human body comes in 
contact with the piping.

Pipe 

size

Tightening torque

Flare 

dimensions

A (mm)

Flare shape

 φ

 6.4

14.2 – 17.2N·m

8.7 – 9.1

 φ

 9.5

32.7 – 39.9N·m

12.8 – 13.2

 φ

 12.7

49.5 – 60.3N·m

16.2 – 16.6

 φ

 15.9

61.8 – 75.4N·m

19.3 – 19.7

Pipe size

Further tightening angle

Recommended arm length of 

tool

φ 

6.4

60 to 90 degrees

Approx. 150mm

φ 

9.5

60 to 90 degrees

Approx. 200mm

φ 

12.7

30 to 60 degrees

Approx. 250mm

φ 

15.9

30 to 60 degrees

Approx. 300mm

Fig. 5

Apply ester oil or ether oil 
only to inner side of flare.

A

45

0

±2

0

R0.4-0.8

90

0

± 2

0

 

Heat insulation procedure for gas piping

Insulation material 
for piping 
(on unit side)

Insulation material 
for piping (field supply)

Make sure that 
the seam faces 
upward.

Clamp (8) 
(accessory)

Gas pipe

Liquid pipe

Flare nut joint

Attached to 
the surface.

Insulation for fitting (5) (accessory)

Middle sealing pad (7) 
(accessory)

Wrap the insulation material 
around the portion from the 
surface of the main unit to the 
upper part of the flare nut joint.

Insulation material 
for piping (field supply)

Wrap the insulation material 
around the portion from the 
surface of the main unit to the 
upper part of the flare nut joint.

Fig. 6

Heat insulation procedure for liquid piping

Insulation material 
for piping 
(on unit side)

Make sure that 
the seam faces 
upward.

Clamp (8) 
(accessory)

Main unit

Flare nut joint

Attached to 
the surface.

Insulation for fitting (4) (accessory)

Middle sealing pad (7) 
(accessory)

01_EN_3PN06583-7N.fm  Page 6  Saturday, February 28, 2009  3:02 PM

Summary of Contents for FXMQ20PVE

Page 1: ...ES ANTES DE INSTALAR GUARDE ESTE MANUAL EN UN LUGAR A MANO PARA LEER EN CASO DE TENER ALGUNA DUDA PRIMA DELL INSTALLAZIONE LEGGERE ATTENTAMENTE QUESTE ISTRUZIONI TENERE QUESTO MANUALE A PORTATA DI MAN...

Page 2: ...artment 9th of January 2009 DAIKIN INDUSTRIES LTD EN60335 2 40 DAIKIN TCF 024D9 12 2008 T V Rheinland EPS B V 0510260101 A B C FXMQ20PVE FXMQ25PVE FXMQ32PVE FXMQ40PVE FXMQ50PVE FXMQ63PVE FXMQ80PVE FXM...

Page 3: ...cient strength may result in the equip ment falling and causing injury Carry out the specified installation work after taking into account strong winds typhoons or earthquakes Failure to do so during...

Page 4: ...l oil or filled with oil vapor or spray like in kitchens Plastic parts may deteriorate which could eventually cause the unit to fall out of place or could lead to leaks Where corrosive gas like sulfur...

Page 5: ...ay from televisions or radios in order to prevent image interference or noise Depending on the radio waves a distance of 1 meter may not be sufficient enough to eliminate the noise Name Washer 11 Wire...

Page 6: ...refer to the installation manual provided with the wireless remote controller Refer to 6 REFRIGERANT PIPING WORK 7 DRAIN PIPING WORK and 10 WIRING EXAMPLE AND HOW TO SET THE REMOTE CONTROLLER The cei...

Page 7: ...t refer to the installation manual provided to the outdoor unit Perform heat insulation work on both gas piping and liquid piping or otherwise water leakage may result Use the insulation material that...

Page 8: ...ing material 7 around the insula tion for fitting 4 and 5 for the joint flare nut part CAUTION Be sure to perform the heat insulation of the local piping up to the piping joint If the piping is expose...

Page 9: ...cket at 1 to 1 5 m intervals for the prevention of piping deflection Be sure to use the drain hose 2 and metal clamp 1 Insert the drain hose 2 deep into the base of the drain socket and securely faste...

Page 10: ...f the drain pump and others 3 Be sure to conduct heat insulation work on the follow ing portions or otherwise water leakage may occur as a result of dew condensation Drain piping indoors Drain socket...

Page 11: ...leaks Water pipes no grounding effect if hard vinyl piping is used Telephone ground wires or lightning rods might cause abnormally high electric potential in the ground during lighting storms 9 2 ELEC...

Page 12: ...wiring neatly and attach the control box lid securely An electric shock or fire may result if the control box lid catches any wiring or the wires push up the lid 4 Put the control box lid and wrap the...

Page 13: ...rque N m Terminal block for remote controller and transmission wires 0 80 0 96 Terminal block for power supply 1 18 1 44 Power supply wiring Earth wiring Transmission wiring Remote controller wiring F...

Page 14: ...use the remote controller to select operation 10 5 CENTRALIZED CONTROL For centralized control it is necessary to designate the group No For details refer to the manual of each optional control lers...

Page 15: ...OFF OPERATION button Then the operation lamp will be lit and the air conditioner will go into fan operation for airflow automatic adjustment Do not adjust the throttles of the air outlets or inlets d...

Page 16: ...ot to operate the air conditioner until the interior finish work is com pleted for the protection of the air conditioner Otherwise substances that will be generated from interior finish work materials...

Page 17: ...0904 HT 3PN06583 7N EM07A049D...

Reviews: