Table 5

CAUTION

Keep in mind that a shortage of airflow quantity or water leakage 
will result because the air conditioner will be operated outside 
the rated range of airflow quantity if the external static pressure 
is wrongly set.

3. Filter Sign Settings

• The remote controller is provided with an LCD that tells 

the time of air filter cleaning.

• If the air conditioner is used in places with excessive dust, 

change the “SECOND CODE NO.” as shown in Table 6. 
The “SECOND CODE NO.” is set to 01 (standard) at fac-
tory set.

Table 6

* Select “No display” under conditions in which the cleaning 
display is not required, such as the time of regular mainte-
nance.

12. TEST OPERATION 

Refer to the installation manual of the outdoor unit.

• The operation lamp of the remote controller will flash when 

an malfunction occurs. Check the malfunction code on the 
liquid crystal display to identify the point of trouble. An expla-
nation of malfunction codes and the corresponding trouble is 
provided in “CAUTION FOR SERVICING” of the outdoor unit.
If any of the items in Table 8 are displayed, there may be a 
problem with the wiring or power, so check the wiring again.

Table 7

Table 8

CAUTION

If interior finish work is continuing on completion of the test 
operation of the air conditioner, explain the customer not to 
operate the air conditioner until the interior finish work is com-
pleted for the protection of the air conditioner. 
Otherwise, substances that will be generated from interior finish 
work materials, such as paint and adhesive agents, may con-
taminate the air conditioner.

External Static 

Pressure

MODE NO.

FIRST 

CODE NO.

SECOND 

CODE NO.

30Pa (*1)(*4)

13 (23)

06

01

50Pa

02

60Pa

03

70Pa

04

80Pa

05

90Pa

06

100Pa

07

110Pa (*3)

08

120Pa (*3)

09

130Pa (*3)

10

140Pa (*3)

11

150Pa (*3)(*4)

12

160Pa (*3)(*4)

13

180Pa 
(*2)(*3)(*4)

14

200Pa 
(*2)(*3)(*4)

15

Dirt

Time for 

display

MODE 

NO.

FIRST 
CODE 

NO.

SECOND 

CODE 

NO.

Standard

Approxi-

mately 2500 

hours

10 (20)

0

01

Excessive 

dust

Approxi-

mately 1250 

hours

02

No display (*)

3

Remote controller display

Contents

“A8” lit

Error in power supply voltage to 
indoor unit.

“C1” lit

Fan driver PCB of indoor unit 

 

indoor control PCB transmission 
error.

“C6” lit

Improper combination of fan driver 
PCB of indoor unit or setting failure 
in control PCB type.

“U3” lit

Test operation of outdoor unit has 
not been finished.

Remote control display

Content

” is lit up

• There is a short circuit at the 

FORCED OFF terminals (T1, T2)

“U4” is lit up

“UH” is lit up

• The power on the outdoor unit is 

off.

• The outdoor unit has not been 

wired for power supply.

• Incorrect wiring for the transmis-

sion wiring and / or FORCED OFF 
wiring.

No display

• The power on the indoor unit is 

off.

• The indoor unit has not been 

wired for power supply.

• Incorrect wiring for the remote 

controller wiring, the transmission 
wiring and / or the FORCED OFF 
wiring.

01_EN_3PN06583-7N.fm  Page 14  Saturday, February 28, 2009  3:02 PM

Summary of Contents for FXMQ20PVE

Page 1: ...ES ANTES DE INSTALAR GUARDE ESTE MANUAL EN UN LUGAR A MANO PARA LEER EN CASO DE TENER ALGUNA DUDA PRIMA DELL INSTALLAZIONE LEGGERE ATTENTAMENTE QUESTE ISTRUZIONI TENERE QUESTO MANUALE A PORTATA DI MAN...

Page 2: ...artment 9th of January 2009 DAIKIN INDUSTRIES LTD EN60335 2 40 DAIKIN TCF 024D9 12 2008 T V Rheinland EPS B V 0510260101 A B C FXMQ20PVE FXMQ25PVE FXMQ32PVE FXMQ40PVE FXMQ50PVE FXMQ63PVE FXMQ80PVE FXM...

Page 3: ...cient strength may result in the equip ment falling and causing injury Carry out the specified installation work after taking into account strong winds typhoons or earthquakes Failure to do so during...

Page 4: ...l oil or filled with oil vapor or spray like in kitchens Plastic parts may deteriorate which could eventually cause the unit to fall out of place or could lead to leaks Where corrosive gas like sulfur...

Page 5: ...ay from televisions or radios in order to prevent image interference or noise Depending on the radio waves a distance of 1 meter may not be sufficient enough to eliminate the noise Name Washer 11 Wire...

Page 6: ...refer to the installation manual provided with the wireless remote controller Refer to 6 REFRIGERANT PIPING WORK 7 DRAIN PIPING WORK and 10 WIRING EXAMPLE AND HOW TO SET THE REMOTE CONTROLLER The cei...

Page 7: ...t refer to the installation manual provided to the outdoor unit Perform heat insulation work on both gas piping and liquid piping or otherwise water leakage may result Use the insulation material that...

Page 8: ...ing material 7 around the insula tion for fitting 4 and 5 for the joint flare nut part CAUTION Be sure to perform the heat insulation of the local piping up to the piping joint If the piping is expose...

Page 9: ...cket at 1 to 1 5 m intervals for the prevention of piping deflection Be sure to use the drain hose 2 and metal clamp 1 Insert the drain hose 2 deep into the base of the drain socket and securely faste...

Page 10: ...f the drain pump and others 3 Be sure to conduct heat insulation work on the follow ing portions or otherwise water leakage may occur as a result of dew condensation Drain piping indoors Drain socket...

Page 11: ...leaks Water pipes no grounding effect if hard vinyl piping is used Telephone ground wires or lightning rods might cause abnormally high electric potential in the ground during lighting storms 9 2 ELEC...

Page 12: ...wiring neatly and attach the control box lid securely An electric shock or fire may result if the control box lid catches any wiring or the wires push up the lid 4 Put the control box lid and wrap the...

Page 13: ...rque N m Terminal block for remote controller and transmission wires 0 80 0 96 Terminal block for power supply 1 18 1 44 Power supply wiring Earth wiring Transmission wiring Remote controller wiring F...

Page 14: ...use the remote controller to select operation 10 5 CENTRALIZED CONTROL For centralized control it is necessary to designate the group No For details refer to the manual of each optional control lers...

Page 15: ...OFF OPERATION button Then the operation lamp will be lit and the air conditioner will go into fan operation for airflow automatic adjustment Do not adjust the throttles of the air outlets or inlets d...

Page 16: ...ot to operate the air conditioner until the interior finish work is com pleted for the protection of the air conditioner Otherwise substances that will be generated from interior finish work materials...

Page 17: ...0904 HT 3PN06583 7N EM07A049D...

Reviews: