VRV SYSTEM Inverter Air Conditioners

Installation manual

CONTENTS

1. SAFETY PRECAUTIONS................................................ 1

2. BEFORE INSTALLATION ................................................ 2

3. SELECTING INSTALLATION SITE ................................. 3

4. PREPARATIONS BEFORE INSTALLATION.................... 4

5. INDOOR UNIT INSTALLATION ....................................... 5

6. REFRIGERANT PIPING WORK ..................................... 5

7. DRAIN PIPING WORK .................................................... 7

8. DUCT WORK .................................................................. 8

9. ELECTRIC WIRING WORK ............................................ 9

10. WIRING EXAMPLE AND HOW TO SET 

THE REMOTE CONTROLLER...................................... 10

11. FIELD SETTING............................................................ 12

12. TEST OPERATION........................................................ 14

1.

SAFETY PRECAUTIONS

Please read these “SAFETY PRECAUTIONS” carefully before 
installing air conditioning unit and be sure to install it correctly.
After completing installation, conduct a trial operation to check 
for faults and explain to the customer how to operate the air con-
ditioner and take care of it with the aid of the operation manual. 
Ask the customer to store the installation manual along with the 
operation manual for future reference.

This air conditioner comes under the term “appliances not 
accessible to the general public”.

Safety Precaution

This unit is a class A product. In a domestic environment this 
product may cause radio interference in which case the user 
may be required to take adequate measures.

Meaning of WARNING and CAUTION notices

WARNING

 ............. Failure to follow these instructions 

properly may result in personal injury 
or loss of life.

CAUTION

  ..............Failure to observe these instructions 

properly may result in property dam-
age or personal injury, which may be 
serious depending on the circum-
stances.

WARNING

• Ask your dealer or qualified personnel to carry out installation 

work.
Do not attempt to install the air conditioner yourself. Improper 
installation may result in water leakage, electric shocks or 
fire.

• Install the air conditioner in accordance with the instructions 

in this installation manual.
Improper installation may result in water leakage, electric 
shocks or fire.

• Consult your local dealer regarding what to do in case of 

refrigerant leakage. When the air conditioner is to be 
installed in a small room, it is necessary to take proper mea-
sures so that the amount of any leaked refrigerant does not 
exceed the concentration limit in the event of a leakage. 
Otherwise, this may lead to an accident due to oxygen deple-
tion.

• Be sure to use only the specified accessories and parts for 

installation work.
Failure to use the specified parts may result in the unit falling, 
water leakage, electric shocks or fire. 

• Install the air conditioner on a foundation strong enough to 

withstand the weight of the unit.
A foundation of insufficient strength may result in the equip-
ment falling and causing injury.

• Carry out the specified installation work after taking into 

account strong winds, typhoons or earthquakes.
Failure to do so during installation work may result in the unit 
falling and causing accidents.

• Make sure that a separate power supply circuit is provided for 

this unit and that all electrical work is carried out by qualified 
personnel according to local laws and regulations and this 
installation manual.
An insufficient power supply capacity or improper electrical 
construction may lead to electric shocks or fire.

• Make sure that all wiring is secured, the specified wires are 

used, and that there is no strain on the terminal connections 
or wires.
Improper connections or securing of wires may result in 
abnormal heat build-up or fire.

• When wiring the power supply and connecting the remote 

controller wiring and transmission wiring, position the wires 
so that the control box lid can be securely fastened.
Improper positioning of the control box lid may result in elec-
tric shocks, fire or the terminals overheating.

• If refrigerant gas leaks during installation, ventilate the area 

immediately.
Toxic gas may be produced if the refrigerant comes into con-
tact with fire.

• After completing installation, check for refrigerant gas leakage.

Toxic gas may be produced if the refrigerant gas leaks into the 
room and comes into contact with a source of fire, such as a 
fan heater, stove or cooker.

• Be sure to switch off the unit before touching any electrical 

parts.

• Be sure to earth the air conditioner.

Do not earth the unit to a utility pipe, lightning conductor or 
telephone earth lead. Imperfect earthing may result in elec-
tric shocks or fire.
A high surge current from lightning or other sources may 
cause damage to the air conditioner.

• Be sure to install an earth leakage breaker.

Failure to install an earth leakage breaker may result in elec-
tric shocks or fire.

CAUTION

• While following the instructions in this installation manual, 

install drain piping to ensure proper drainage and insulate 
piping to prevent condensation.
Improper drain piping may result in indoor water leakage and 
property damage.

• Install the indoor and outdoor units, power cord and connect-

ing wires at least 1 meter away from televisions or radios to 
prevent picture interference and noise.
(Depending on the incoming signal strength, a distance of 
1 meter may not be sufficient to eliminate noise.)

• Remote controller (wireless kit) transmitting distance can be 

shorter than expected in rooms with electronic fluorescent 
lamps (inverter or rapid start types).
Install the indoor unit as far away from fluorescent lamps as 
possible.

01_EN_3PN06583-7N.fm  Page 1  Saturday, February 28, 2009  3:02 PM

Summary of Contents for FXMQ20PVE

Page 1: ...ES ANTES DE INSTALAR GUARDE ESTE MANUAL EN UN LUGAR A MANO PARA LEER EN CASO DE TENER ALGUNA DUDA PRIMA DELL INSTALLAZIONE LEGGERE ATTENTAMENTE QUESTE ISTRUZIONI TENERE QUESTO MANUALE A PORTATA DI MAN...

Page 2: ...artment 9th of January 2009 DAIKIN INDUSTRIES LTD EN60335 2 40 DAIKIN TCF 024D9 12 2008 T V Rheinland EPS B V 0510260101 A B C FXMQ20PVE FXMQ25PVE FXMQ32PVE FXMQ40PVE FXMQ50PVE FXMQ63PVE FXMQ80PVE FXM...

Page 3: ...cient strength may result in the equip ment falling and causing injury Carry out the specified installation work after taking into account strong winds typhoons or earthquakes Failure to do so during...

Page 4: ...l oil or filled with oil vapor or spray like in kitchens Plastic parts may deteriorate which could eventually cause the unit to fall out of place or could lead to leaks Where corrosive gas like sulfur...

Page 5: ...ay from televisions or radios in order to prevent image interference or noise Depending on the radio waves a distance of 1 meter may not be sufficient enough to eliminate the noise Name Washer 11 Wire...

Page 6: ...refer to the installation manual provided with the wireless remote controller Refer to 6 REFRIGERANT PIPING WORK 7 DRAIN PIPING WORK and 10 WIRING EXAMPLE AND HOW TO SET THE REMOTE CONTROLLER The cei...

Page 7: ...t refer to the installation manual provided to the outdoor unit Perform heat insulation work on both gas piping and liquid piping or otherwise water leakage may result Use the insulation material that...

Page 8: ...ing material 7 around the insula tion for fitting 4 and 5 for the joint flare nut part CAUTION Be sure to perform the heat insulation of the local piping up to the piping joint If the piping is expose...

Page 9: ...cket at 1 to 1 5 m intervals for the prevention of piping deflection Be sure to use the drain hose 2 and metal clamp 1 Insert the drain hose 2 deep into the base of the drain socket and securely faste...

Page 10: ...f the drain pump and others 3 Be sure to conduct heat insulation work on the follow ing portions or otherwise water leakage may occur as a result of dew condensation Drain piping indoors Drain socket...

Page 11: ...leaks Water pipes no grounding effect if hard vinyl piping is used Telephone ground wires or lightning rods might cause abnormally high electric potential in the ground during lighting storms 9 2 ELEC...

Page 12: ...wiring neatly and attach the control box lid securely An electric shock or fire may result if the control box lid catches any wiring or the wires push up the lid 4 Put the control box lid and wrap the...

Page 13: ...rque N m Terminal block for remote controller and transmission wires 0 80 0 96 Terminal block for power supply 1 18 1 44 Power supply wiring Earth wiring Transmission wiring Remote controller wiring F...

Page 14: ...use the remote controller to select operation 10 5 CENTRALIZED CONTROL For centralized control it is necessary to designate the group No For details refer to the manual of each optional control lers...

Page 15: ...OFF OPERATION button Then the operation lamp will be lit and the air conditioner will go into fan operation for airflow automatic adjustment Do not adjust the throttles of the air outlets or inlets d...

Page 16: ...ot to operate the air conditioner until the interior finish work is com pleted for the protection of the air conditioner Otherwise substances that will be generated from interior finish work materials...

Page 17: ...0904 HT 3PN06583 7N EM07A049D...