• Perform nitrogen substituent or apply nitrogen into the 

refrigerant piping (see NOTE 1) in the case of refrigerant 
piping blazing (see NOTE 2). Then perform the flare con-
nection of the indoor unit. 

(Refer to Fig. 7)

CAUTION

Do not use any antioxidant at the time of piping blazing.

The piping may be clogged with a residual antioxidant and 
parts may malfunction.

NOTE

1.

At the time of blazing, set the pressure of nitrogen to 
approximately 0.02 MPa (close to the pressure of a 
breeze coming in contact with the cheek) with a decom-
pression valve.

2.

Do not use flux at the time of blazing and connecting the 
refrigerant piping. Use a copper phosphorus brazing alloy 
(BCuP-2: JIS Z 3264/BCu 93P-710/795: ISO3677), which 
does not require flux, for blazing.
(Flux has a bad influence on the refrigerant piping. Chlo-
rine-based flux will cause piping corrosion. Furthermore, if 
it contains fluorine, the flux will deteriorate refrigerant oil.)

• As for the branching of the refrigerant piping or refrigerant, 

refer to the installation manual provided with the outdoor unit.

7.

DRAIN PIPING WORK

(1) Conduct drain piping work.

Check that the piping 
ensures proper draining.

• Make sure that the diam-

eter of the piping exclud-
ing the rising part is the 
same as or larger than 
the diameter of the con-
necting pipe (vinyl chloride pipe with an outer diameter 
of 32 mm and a nominal inner diameter of 25 mm).

• Make sure that the piping is short enough 

with a down-

ward slope of at least 1/100

 and that there is no air 

bank formed. No drain trap is required.

CAUTION

• The drain piping will be clogged with water and water leak-

age may result if the water is accumulated in the drain piping.

• Conduct drain-up piping work if the gradient is insuffi-

cient.

• Attach a support bracket at 1 to 1.5 m intervals for the 

prevention of piping deflection.

• Be sure to use the drain hose (2) and metal clamp (1).

Insert the drain hose (2) deep into the base of the 
drain socket, and securely fasten the metal clamp (1) 
within the taped part on the insertion front end of the 
hose.

Be sure to fasten the screw of the metal clamp (1) until 
the margin of the screw thread decreases to 4 mm or 
less.

NOTE

Be sure to follow the instructions as below.

• Do not connect the drain piping directly to a sewer that 

smells of ammonia.
The ammonia in the sewer may reach through the drain 
piping and corrode the heat exchanger of the indoor unit.

• Do not bend or twist the provided drain hose (2) in order 

not to impose excessive force on the hose. (Doing so 
may result in water leakage.)

• Take the procedure shown in the following illustration to 

perform concentrated drain piping.

• Select the diameter of the concentrated drain piping to 

suit the capacity of equipment connecting to the concen-
trated drain piping (see the equipment design sheet).

Nitrogen

Refrigerant 
piping

Part to be 
brazed 

Taping

Pressurereducing valve

hands 
valve

Nitrogen

Fig. 7

Refrigerant 
piping

Drain socket 

Socket for 
maintenance 
(with rubber cap)

1 - 1.5 m

Support bracket

Downward slope of at least 1/100

(accessory)

(accessory)

Metal clamp (1)

Tape

Drain hose (2)

Concentrated drain piping

The drain piping will be clogged with water 
and water leakage may result if the water is 
accumulated in the drain piping.

Maintain 

a downward slope of at least 

1/100

 so that no air bank will be formed.

0 - 467 mm

Ceiling slab

1 - 1.5 m

300 mm max.

700 mm max.

Support bracket

Drain-up piping 
(field supply)

Adjustable 
(467 mm max.)

Metal clamp (1) (accessory)

Drain hose (2) (accessory)

Drain hose (2) (accessory)

Horizontal or 
upward slope

If there is an air bank, noise may be generated 
as a result of a water backflow when the drain 
pump comes to a stop.

Locate the drain hose horizontally 
or with a little upward gradient.

01_EN_3PN06583-7N.fm  Page 7  Saturday, February 28, 2009  3:02 PM

Summary of Contents for FXMQ20PVE

Page 1: ...ES ANTES DE INSTALAR GUARDE ESTE MANUAL EN UN LUGAR A MANO PARA LEER EN CASO DE TENER ALGUNA DUDA PRIMA DELL INSTALLAZIONE LEGGERE ATTENTAMENTE QUESTE ISTRUZIONI TENERE QUESTO MANUALE A PORTATA DI MAN...

Page 2: ...artment 9th of January 2009 DAIKIN INDUSTRIES LTD EN60335 2 40 DAIKIN TCF 024D9 12 2008 T V Rheinland EPS B V 0510260101 A B C FXMQ20PVE FXMQ25PVE FXMQ32PVE FXMQ40PVE FXMQ50PVE FXMQ63PVE FXMQ80PVE FXM...

Page 3: ...cient strength may result in the equip ment falling and causing injury Carry out the specified installation work after taking into account strong winds typhoons or earthquakes Failure to do so during...

Page 4: ...l oil or filled with oil vapor or spray like in kitchens Plastic parts may deteriorate which could eventually cause the unit to fall out of place or could lead to leaks Where corrosive gas like sulfur...

Page 5: ...ay from televisions or radios in order to prevent image interference or noise Depending on the radio waves a distance of 1 meter may not be sufficient enough to eliminate the noise Name Washer 11 Wire...

Page 6: ...refer to the installation manual provided with the wireless remote controller Refer to 6 REFRIGERANT PIPING WORK 7 DRAIN PIPING WORK and 10 WIRING EXAMPLE AND HOW TO SET THE REMOTE CONTROLLER The cei...

Page 7: ...t refer to the installation manual provided to the outdoor unit Perform heat insulation work on both gas piping and liquid piping or otherwise water leakage may result Use the insulation material that...

Page 8: ...ing material 7 around the insula tion for fitting 4 and 5 for the joint flare nut part CAUTION Be sure to perform the heat insulation of the local piping up to the piping joint If the piping is expose...

Page 9: ...cket at 1 to 1 5 m intervals for the prevention of piping deflection Be sure to use the drain hose 2 and metal clamp 1 Insert the drain hose 2 deep into the base of the drain socket and securely faste...

Page 10: ...f the drain pump and others 3 Be sure to conduct heat insulation work on the follow ing portions or otherwise water leakage may occur as a result of dew condensation Drain piping indoors Drain socket...

Page 11: ...leaks Water pipes no grounding effect if hard vinyl piping is used Telephone ground wires or lightning rods might cause abnormally high electric potential in the ground during lighting storms 9 2 ELEC...

Page 12: ...wiring neatly and attach the control box lid securely An electric shock or fire may result if the control box lid catches any wiring or the wires push up the lid 4 Put the control box lid and wrap the...

Page 13: ...rque N m Terminal block for remote controller and transmission wires 0 80 0 96 Terminal block for power supply 1 18 1 44 Power supply wiring Earth wiring Transmission wiring Remote controller wiring F...

Page 14: ...use the remote controller to select operation 10 5 CENTRALIZED CONTROL For centralized control it is necessary to designate the group No For details refer to the manual of each optional control lers...

Page 15: ...OFF OPERATION button Then the operation lamp will be lit and the air conditioner will go into fan operation for airflow automatic adjustment Do not adjust the throttles of the air outlets or inlets d...

Page 16: ...ot to operate the air conditioner until the interior finish work is com pleted for the protection of the air conditioner Otherwise substances that will be generated from interior finish work materials...

Page 17: ...0904 HT 3PN06583 7N EM07A049D...

Reviews: