background image

8

English

(2) Check the smooth draining of the piping on completion of 

the installation of the piping.

[Before electrical work]

CAUTION

A licensed electrical engineering technician must con-
duct electrical wiring work (including grounding work).

If no licensed electrical engineering technician is avail-
able, take steps 3 and 4 after the test operation of the air 
conditioner is finished.

1. Remove the control box lid, 

and connect the single-

phase electric wires to terminals L and N of the termi-
nal block and the ground wire to the ground terminal

.

Perform wiring according to 

10-1 CONNECTING POWER 

SUPPLY, GROUND, REMOTE CONTROLLER, AND 
TRANSMISSION WIRING

 in 

10. WIRING EXAMPLE 

AND HOW TO SET THE REMOTE CONTROLLER

.

CAUTION

• In order not to impose tension on the wire connections, per-

form clamping securely with the provided clamp (8) specified 
in 3 in 

10-1 CONNECTING POWER SUPPLY, GROUND, 

REMOTE CONTROLLER, AND TRANSMISSION WIRING

.

2. Check that the control box lid is closed before turning the 

air conditioner ON.

3. Provide 

approximately one liter of water

 gradually into 

the drain pan through the water inlet on the bottom of the 
drain socket or the outlet. Make sure that the water is not 
spilled onto the drain pump.

4. The drain pump will operate with the power turned ON. 

Check that the pump drains water smoothly. (The drain 
pump will stop automatically in 10 minutes.)
The drainage can be checked with the water level change 
in the drain pan through the water inlet.

CAUTION

Do not touch the drain pump.

Otherwise, an electric shock may be received.

Do not impose external force on the float switch.

Otherwise, a failure may result.

5. On completion of the drainage check, shut off the power 

supply and disconnect the power supply line.

6. Put the control box lid to the original position.

[After electrical work]

• After completion of

 8. DUCT WORK

 

provide 

approximately 

one liter of water

 gradually into the drain pan through the 

water inlet on the bottom of the drain socket, and check that 
the water is drained while the air conditioner is in cooling 
operation according to 

11. FIELD SETTING

 and 

12. TEST 

OPERATION 

. Make sure that the water is not spilled onto 

the electric parts of the drain pump and others.

(3) Be sure to conduct heat insulation work on the follow-

ing portions, or otherwise water leakage may occur as 
a result of dew condensation.

Drain piping indoors

Drain socket

• On completion of the drainage check, refer to the follow-

ing illustration, and use the provided large sealing pad 
(6) and heat insulate the metal clamp (1) and drain hose 
(2).

8.

DUCT WORK

Pay the utmost attention to the following items and conduct 
the ductwork.

• Check that the duct will not be in excess of the setting range 

of external static pressure for the unit. (Refer to the technical 
datasheet for the setting range. Each model has each setting 
range of external static pressure.)

• Attach a canvas duct each to the air outlet and air inlet so that 

the vibration of the equipment will not be transmitted to the 
duct or ceiling.
Use a sound-absorbing material (insulation material) for the 
lining of the duct and apply vibration insulation rubber to the 
hanging bolts.

• At the time of duct welding, perform the curing of the duct so 

that the sputter will not come in contact with the drain pan for 
the filter.

• If the metal duct pass through a metal lath, wire lath, or metal 

plate of a wooden structure, separate the duct and wall elec-
trically.

• Be sure to heat insulate the duct for the prevention of dew 

condensation. (Material: Glass wool or styrene foam; Thick-
ness: 25 mm)

• Be sure to attach the field supply air filter to the air inlet of the 

unit or field supply inlet in the air passage on the air suction 
side. (Be sure to select an air filter with a duct collection effi-
ciency of 50 weight percent.)

• Explain the operation and washing methods of the locally 

procured components (i.e., the air filter, air inlet grille, and air 
outlet grille) to the customer.

• Locate the air outlet grille on the indoor side for the preven-

tion of drafts in a position where indirect contact with people.

• The air conditioner incorporates a function to adjust the fan to 

rated speed automatically. 

(11. FIELD SETTING)

Therefore, do not use booster fans midway in the duct.

Water inlet

Drain soket

Drain pan

Control box lid

Terminal block for 
power supply

Screw

Water inlet lid

Control box

Refrigerant piping

Air outlet

Socket for maintenance 
(with rubber cap)

Drain pump position

Plastic water container

Make sure that the 
seam faces upward.

Metal clamp (1)

(accessory)

Large sealing pad (6)

(accessory)

4 mm max.

01_EN_3PN06583-7N.fm  Page 8  Saturday, February 28, 2009  3:02 PM

Summary of Contents for FXMQ20PVE

Page 1: ...ES ANTES DE INSTALAR GUARDE ESTE MANUAL EN UN LUGAR A MANO PARA LEER EN CASO DE TENER ALGUNA DUDA PRIMA DELL INSTALLAZIONE LEGGERE ATTENTAMENTE QUESTE ISTRUZIONI TENERE QUESTO MANUALE A PORTATA DI MAN...

Page 2: ...artment 9th of January 2009 DAIKIN INDUSTRIES LTD EN60335 2 40 DAIKIN TCF 024D9 12 2008 T V Rheinland EPS B V 0510260101 A B C FXMQ20PVE FXMQ25PVE FXMQ32PVE FXMQ40PVE FXMQ50PVE FXMQ63PVE FXMQ80PVE FXM...

Page 3: ...cient strength may result in the equip ment falling and causing injury Carry out the specified installation work after taking into account strong winds typhoons or earthquakes Failure to do so during...

Page 4: ...l oil or filled with oil vapor or spray like in kitchens Plastic parts may deteriorate which could eventually cause the unit to fall out of place or could lead to leaks Where corrosive gas like sulfur...

Page 5: ...ay from televisions or radios in order to prevent image interference or noise Depending on the radio waves a distance of 1 meter may not be sufficient enough to eliminate the noise Name Washer 11 Wire...

Page 6: ...refer to the installation manual provided with the wireless remote controller Refer to 6 REFRIGERANT PIPING WORK 7 DRAIN PIPING WORK and 10 WIRING EXAMPLE AND HOW TO SET THE REMOTE CONTROLLER The cei...

Page 7: ...t refer to the installation manual provided to the outdoor unit Perform heat insulation work on both gas piping and liquid piping or otherwise water leakage may result Use the insulation material that...

Page 8: ...ing material 7 around the insula tion for fitting 4 and 5 for the joint flare nut part CAUTION Be sure to perform the heat insulation of the local piping up to the piping joint If the piping is expose...

Page 9: ...cket at 1 to 1 5 m intervals for the prevention of piping deflection Be sure to use the drain hose 2 and metal clamp 1 Insert the drain hose 2 deep into the base of the drain socket and securely faste...

Page 10: ...f the drain pump and others 3 Be sure to conduct heat insulation work on the follow ing portions or otherwise water leakage may occur as a result of dew condensation Drain piping indoors Drain socket...

Page 11: ...leaks Water pipes no grounding effect if hard vinyl piping is used Telephone ground wires or lightning rods might cause abnormally high electric potential in the ground during lighting storms 9 2 ELEC...

Page 12: ...wiring neatly and attach the control box lid securely An electric shock or fire may result if the control box lid catches any wiring or the wires push up the lid 4 Put the control box lid and wrap the...

Page 13: ...rque N m Terminal block for remote controller and transmission wires 0 80 0 96 Terminal block for power supply 1 18 1 44 Power supply wiring Earth wiring Transmission wiring Remote controller wiring F...

Page 14: ...use the remote controller to select operation 10 5 CENTRALIZED CONTROL For centralized control it is necessary to designate the group No For details refer to the manual of each optional control lers...

Page 15: ...OFF OPERATION button Then the operation lamp will be lit and the air conditioner will go into fan operation for airflow automatic adjustment Do not adjust the throttles of the air outlets or inlets d...

Page 16: ...ot to operate the air conditioner until the interior finish work is com pleted for the protection of the air conditioner Otherwise substances that will be generated from interior finish work materials...

Page 17: ...0904 HT 3PN06583 7N EM07A049D...