Connection method of ducts on air inlet and outlet sides.

• Connect the field supply duct in alignment with the inner side 

of the flange.

• Connect the flange and unit with the flange connection screw 

(3).

• Wrap aluminum tape around the flange and duct joint in order 

to prevent air leakage.

CAUTION

Connect the flange and unit with the flange connection screw (3) 
regardless of whether the duct is connected to the air inlet side.

9.

ELECTRIC WIRING WORK

9-1

GENERAL INSTRUCTIONS 

• All field supplied parts and materials and electric works must 

conform to local codes.

• Use copper wire only.
• For electric wiring work, refer to also “Wiring diagram” 

attached to the control box lid.

• For remote controller wiring details, refer to the installation 

manual attached to the remote controller.

• All wiring must be performed by an authorized electrician.
• This system consists of multiple indoor units. Mark each 

indoor unit as unit A, unit B..., and be sure the terminal board 
wiring to the outdoor unit and BS unit are properly matched. 
If wiring and piping between the outdoor unit and an indoor 
unit are mismatched, the system may cause a malfunction.

• A circuit breaker capable of shutting down power supply to 

the entire system must be installed.

• Refer to the installation manual attached to the outdoor unit 

for the size of power supply wiring connected to the outdoor 
unit, the capacity of the circuit breaker and switch, and wiring 
instructions.

• Be sure to ground the air conditioner.
• Do not connect the ground wire to gas and water pipes, light-

ning rods, or telephone ground wires.

• Gas pipes : might cause explosions or fire if gas leaks.
• Water pipes : no grounding effect if hard vinyl piping is 

used.

• Telephone ground wires or lightning rods : might cause 

abnormally high electric potential in the ground during 
lighting storms.

9-2

ELECTRICAL CHARACTERISTICS

MCA: Min. Circuit Amps (A); MFA: Max. Fuse Amps (A) 
kW: Fan Motor Rated Output (kW); FLA: Full Load Amps (A)

9-3

SPECIFICATIONS FOR FIELD SUPPLIED 
FUSES AND WIRE 

Allowable length of transmission wirings and remote controller 
wiring are as follows.

(1) Outdoor unit – Indoor unit: 

Max. 1000 m (Total wiring length: 2000 m) 

(2) Indoor unit – Remote controller: 

Max. 500 m

Unit

Flange on air outlet side 
(provided with the unit)

Insulation material 
(field supply)

Canvas duct 
(field supply)

Flange on air inlet side 
(provided with the unit)

Insulation material 
(field supply)

Air inlet

Air outlet

Screws for duct 
flanges (3)

(accessory)

Screws 
for duct 
flanges (3)

(accessory)

Units

Power supply

Fan motor

Model

Hz

Volts

Voltage 

range

MCA

MFA

kW

FLA

FXMQ20PVE

50

220-

240

Max. 264
Min.  198

0.6

16

0.09

0.5

FXMQ25PVE

0.6

16

0.09

0.5

FXMQ32PVE

0.6

16

0.09

0.5

FXMQ40PVE

1.4

16

0.140

1.1

FXMQ50PVE

1.6

16

0.350

1.3

FXMQ63PVE

1.8

16

0.350

1.4

FXMQ80PVE

2.3

16

0.350

1.8

FXMQ100PVE

2.9

16

0.350

2.3

FXMQ125PVE

3.4

16

0.350

2.7

FXMQ140PVE

3.4

16

0.350

2.7

FXMQ20PVE

60

220

Max. 242
Min.  198

0.6

16

0.09

0.5

FXMQ25PVE

0.6

16

0.09

0.5

FXMQ32PVE

0.6

16

0.09

0.5

FXMQ40PVE

1.4

16

0.140

1.1

FXMQ50PVE

1.6

16

0.350

1.3

FXMQ63PVE

1.8

16

0.350

1.4

FXMQ80PVE

2.3

16

0.350

1.8

FXMQ100PVE

2.9

16

0.350

2.3

FXMQ125PVE

3.4

16

0.350

2.7

FXMQ140PVE

3.4

16

0.350

2.7

Model

Power supply wiring

Remote controller wiring

Transmission wiring

Field fuses 

Wire

Size

Wire

Size

FXMQ20PVE

16A

H05VV-

U3G

Size must  
comply 
with local 
codes.

Sheathed 
wire 
(2 wire)

0.75 - 

1.25 mm

2

FXMQ25PVE

FXMQ32PVE

FXMQ40PVE

FXMQ50PVE

FXMQ63PVE

FXMQ80PVE

FXMQ100PVE

FXMQ125PVE

FXMQ140PVE

01_EN_3PN06583-7N.fm  Page 9  Saturday, February 28, 2009  3:02 PM

Summary of Contents for FXMQ20PVE

Page 1: ...ES ANTES DE INSTALAR GUARDE ESTE MANUAL EN UN LUGAR A MANO PARA LEER EN CASO DE TENER ALGUNA DUDA PRIMA DELL INSTALLAZIONE LEGGERE ATTENTAMENTE QUESTE ISTRUZIONI TENERE QUESTO MANUALE A PORTATA DI MAN...

Page 2: ...artment 9th of January 2009 DAIKIN INDUSTRIES LTD EN60335 2 40 DAIKIN TCF 024D9 12 2008 T V Rheinland EPS B V 0510260101 A B C FXMQ20PVE FXMQ25PVE FXMQ32PVE FXMQ40PVE FXMQ50PVE FXMQ63PVE FXMQ80PVE FXM...

Page 3: ...cient strength may result in the equip ment falling and causing injury Carry out the specified installation work after taking into account strong winds typhoons or earthquakes Failure to do so during...

Page 4: ...l oil or filled with oil vapor or spray like in kitchens Plastic parts may deteriorate which could eventually cause the unit to fall out of place or could lead to leaks Where corrosive gas like sulfur...

Page 5: ...ay from televisions or radios in order to prevent image interference or noise Depending on the radio waves a distance of 1 meter may not be sufficient enough to eliminate the noise Name Washer 11 Wire...

Page 6: ...refer to the installation manual provided with the wireless remote controller Refer to 6 REFRIGERANT PIPING WORK 7 DRAIN PIPING WORK and 10 WIRING EXAMPLE AND HOW TO SET THE REMOTE CONTROLLER The cei...

Page 7: ...t refer to the installation manual provided to the outdoor unit Perform heat insulation work on both gas piping and liquid piping or otherwise water leakage may result Use the insulation material that...

Page 8: ...ing material 7 around the insula tion for fitting 4 and 5 for the joint flare nut part CAUTION Be sure to perform the heat insulation of the local piping up to the piping joint If the piping is expose...

Page 9: ...cket at 1 to 1 5 m intervals for the prevention of piping deflection Be sure to use the drain hose 2 and metal clamp 1 Insert the drain hose 2 deep into the base of the drain socket and securely faste...

Page 10: ...f the drain pump and others 3 Be sure to conduct heat insulation work on the follow ing portions or otherwise water leakage may occur as a result of dew condensation Drain piping indoors Drain socket...

Page 11: ...leaks Water pipes no grounding effect if hard vinyl piping is used Telephone ground wires or lightning rods might cause abnormally high electric potential in the ground during lighting storms 9 2 ELEC...

Page 12: ...wiring neatly and attach the control box lid securely An electric shock or fire may result if the control box lid catches any wiring or the wires push up the lid 4 Put the control box lid and wrap the...

Page 13: ...rque N m Terminal block for remote controller and transmission wires 0 80 0 96 Terminal block for power supply 1 18 1 44 Power supply wiring Earth wiring Transmission wiring Remote controller wiring F...

Page 14: ...use the remote controller to select operation 10 5 CENTRALIZED CONTROL For centralized control it is necessary to designate the group No For details refer to the manual of each optional control lers...

Page 15: ...OFF OPERATION button Then the operation lamp will be lit and the air conditioner will go into fan operation for airflow automatic adjustment Do not adjust the throttles of the air outlets or inlets d...

Page 16: ...ot to operate the air conditioner until the interior finish work is com pleted for the protection of the air conditioner Otherwise substances that will be generated from interior finish work materials...

Page 17: ...0904 HT 3PN06583 7N EM07A049D...

Reviews: