background image

Installation and operation manual

5

Refrigerant piping work

For refrigerant piping of outdoor unit, refer to the installation manual
supplied with the outdoor unit.

Before rigging tubes, check which type of refrigerant is used.

Use a pipe cutter and flare suitable for the used refrigerant.

To prevent dust, moisture or other foreign matter from infiltrating
the tube, either pinch the end, or cover it with tape.

Use copper alloy seamless pipes (ISO 1337).

The outdoor unit is charged with refrigerant.

To prevent water leakage, execute heat insulation work
completely on both sides of the gas and liquid piping. When
using a heat pump, the temperature of the gas piping can reach
up to approximately 120°C. Use insulation which is sufficiently
heat resistant.

Be sure to use both a spanner and torque wrench together when
connecting or disconnecting pipes to/from the unit.

Do not mix anything other than the specified refrigerant, such as
air, etc..., inside the refrigerant circuit.

Flares should not be re-used. New ones should be made in
order to prevent leaks.
Only use annealed flare nuts included with the unit. Using
different flare nuts may cause the refrigerant to leak.

Refer to the table below for the dimensions of flare nut spaces
and the appropriate tightening torque. (Overtightening may
damage the flare and cause leaks.)

When connecting the flare nut, coat the flare inner surface with
ether oil or ester oil and initially tighten 3 or 4 turns by hand
before tightening firmly.

Finally, insulate as shown in the figure below.

NOTE

When mounting the unit to a wall, operating sound may
become bigger.

All field piping must be provided by a licensed refrigeration
technician and must comply with the relevant local and
national codes.

Place

Installation period

Protection method

More than a month

Pinch the pipe

Less than a month

Pinch or tape the pipe

Regardless of the period

13

9

10

8

9

8

10

13

12

12

11

Pipe gauge 

(mm)

Tightening 

torque (N•m)

Flare dimension 

A (mm)

Flare shape

Ø6.4

15~17

8.7~9.1

Ø9.5

33~39

12.8~13.2

Ø12.7

50~60

16.2~16.6

Ø15.9

63~75

19.3~19.7

Be sure to insulate local piping all the way into the
pipe connections inside the unit.
Exposed piping may cause condensation or may
cause burns when touched.

After all piping has been connected, use nitrogen to
perform a gas leak check. A toxic gas may be
released by the refrigerant gas leaking indoor and
being exposed to flames from an area heater, cooking
stove, etc. If the refrigerant gas leaks during the work,
ventilate the area.

1

Insulation for gas pipe (accessory part)

2

Sealing pad (accessory part) (wrapped over union)

3

Clamp (4x accessory part)

4

Gas pipe

5

Insulation for liquid pipe (accessory part)

6

Liquid pipe

1

2

4

3

1

Torque wrench

2

Spanner

3

Piping union

4

Flare nut

R=0.4~0.8

45

° ±

2

90

°±

2

A

1
2
3
4

6

5

01_4PEN323720-1E.book  Page 5  Tuesday, October 3, 2017  4:34 PM

Summary of Contents for FXLQ20P5VEB

Page 1: ...INSTALLATION AND OPERATION MANUAL FXLQ20P5VEB FXLQ25P5VEB FXLQ32P5VEB FXLQ40P5VEB FXLQ50P5VEB FXLQ63P5VEB System air conditioners 01_4PEN323720 1E book Page 1 Tuesday October 3 2017 4 34 PM...

Page 2: ...x L N L N P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 3 1 4 2 L N L N L N L N 2 1 2 3 7 9 8 10 4 5 6 L N IN D OUT D F1 F2 F1 F2 Control box L N P1 P...

Page 3: ...ajo v skladu z na imi navodili on vastavuses j rgmis t e standardi te ga v i teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele atitinka emiau nurodytus standartus ir a...

Page 4: ...corrosive gas like sulphurous gas exists Copper tubing and brazed spots may corrode Where volatile flammable gas like thinner or gasoline is used Where machines generating electromagnetic waves exist...

Page 5: ...9 1 7 6 3 0 11 58 FXLQ63P5VEB 4 9 2 2 8 0 11 59 1x 1x 4x 1x 1x 1x 1 2 3 5 6 1x 8 8x 7 4 Tick 3 when checked Is the indoor unit fixed firmly The unit may drop vibrate or make noise Is the gas leak test...

Page 6: ...This is to prevent image interference and noise in those electrical appliances Noise may be generated depending on the conditions under which the electric wave is generated even if 1 meter is kept Whe...

Page 7: ...sten to the floor with a field supplied floor fastener Wallmounted installation 1 Positioning of holes for fastening to the wall Unit of measurement mm 2 The legs can be removed if the indoor unit is...

Page 8: ...leaks When connecting the flare nut coat the flare inner surface with ether oil or ester oil and initially tighten 3 or 4 turns by hand before tightening firmly Finally insulate as shown in the figure...

Page 9: ...um pump which can evacuate to 100 7 kPa 5 Torr 755 mm Hg Drain piping work Rig the drain pipe as shown below Improperly rigged piping could lead to leaks and eventually wet furniture and belongings 1...

Page 10: ...sive force to the terminal Use torques according to the table below When attaching the control box lid make sure not to pinch any wires and make sure that the wiring does not come in contact with the...

Page 11: ...Circuit Amps A MFA Maximum Fuse Amps A FLA Full Load Amps A NOTE For details refer to Electrical data in the technical data book Power supply wiring Model Field fuses Wire Size 20 63 16 A H05VV U3G L...

Page 12: ...put from outside to terminals T1 and T2 of the terminal board remote controller to transmission wiring 2 Actuation The following table explains forced off and on off operations in response to input A...

Page 13: ...terminals T1 T2 U4 or UH The power on the outdoor unit is off The outdoor unit has not been wired for power supply Incorrect transmission no display The power on the indoor unit is off The indoor uni...

Page 14: ...onsumption even if the system is not operating The remote controller display is turned off when the main power switch is turned off Disposal requirements Your product and the batteries supplied with t...

Page 15: ...C RECEIVER F U FU FOR CHARACTERISTICS REFER TOPCBINSIDE YOUR UNIT FUSE S C LIMIT SWITCH FG CONNECTOR FRAMEGROUND S L FLOAT SWITCH H HARNESS S NPH PRESSURESENSOR HIGH H P LED V L PILOT LAMP LIGHT EMITT...

Page 16: ...7 1 2019 12 Copyright 2019 Daikin DAIKIN ISITMA VE SO UTMA S STEMLER SAN T C A G lsuyu Mahallesi Fevzi akmak Caddesi Bur ak Sokak No 20 34848 Maltepe STANBUL T RK YE Tel 0216 453 27 00 Faks 0216 671 0...

Reviews: