Installation and operation manual

6

Cautions for brazing

Be sure to carry out a nitrogen blow when brazing.
Brazing without carrying out nitrogen replacement or releasing
nitrogen into the piping will create large quantities of oxidized
film on the inside of the pipes, adversely affecting valves and
compressors in the refrigerating system and preventing normal
operation.

When brazing while inserting nitrogen into the piping, nitrogen
must be set to 0.02 MPa with a pressure-reducing valve (=just
enough so that it can be felt on the skin).

Do not use anti-oxidants when brazing the pipe joints. Residue
can clog pipes and break equipment.

Do not use flux when brazing copper-to-copper refrigerant
piping. Use phosphor copper brazing filler alloy (BCuP) which
does not require flux.

Flux has an extremely harmful influence on refrigerant piping
systems. For instance, if chlorine based flux is used, it will cause
pipe corrosion or, in particular, if the flux contains fluorine, it will
deteriorate the refrigerant oil.

Use R410A only when adding refrigerant
Installation tools:
Make sure to use installation tools (gauge manifold charge hose,
etc.) that are exclusively used for R410A installations to
withstand the pressure and to prevent foreign materials (e.g.
mineral oils and moisture) from mixing into the system.
Vacuum pump:
Use a 2-stage vacuum pump with a non-return valve
Make sure the pump oil does not flow oppositely into the system
while the pump is not working.
Use a vacuum pump which can evacuate to –100.7 kPa
(5 Torr, –755 mm Hg).

Drain piping work

Rig the drain pipe as shown below. Improperly rigged piping could
lead to leaks and eventually wet furniture and belongings.

1

Carry out the drain piping
Connect the drain hose (accessory part) using the attached
hose and parts, as shown in the figure below.

2

If converging multiple drain pipes, install according to the
procedure shown below. Use a slope downwards at a gradient of
at least 1/100.

Select converging drain pipes with a size that is suitable for the
operating capacity of the unit.

3

After piping work is finished, check if drainage flows smoothly.
Pour approximately 1 liter of water slowly in the air outlet and
check drainage flow.

4

Be sure to insulate all indoor pipes.

Protect or enclose refrigerant tubing to avoid mechanical
damage.

Installation shall be done by an installer, the choice of materials
and installation shall comply with the applicable legislation. In
Europe the EN378 is the applicable standard that shall be used.

1

Refrigerant piping

2

Part to be brazed

3

Taping

4

Hands valve

5

Pressure-reducing valve

6

Nitrogen

1

2

3

4

5

6

6

1

Drip pan

2

Drain hose (accessory part)

3

Metal clamp (accessory part)

4

3/4" drain pipe

5

Cut to a suitable length 

6

Slope

Drain piping connections

Do not connect the drain piping directly to sewage
pipes that smell of ammonia. The ammonia in the
sewage might enter the indoor unit through the drain
pipes and corrode the heat exchanger.

Keep in mind that the drain pipe will become blocked
if water remains in the drain pipe.

2

3

5

4

6

1

/1

00

Piping process inside unit

1/100

01_4PEN323720-1E.book  Page 6  Tuesday, October 3, 2017  4:34 PM

Summary of Contents for FXLQ20P5VEB

Page 1: ...INSTALLATION AND OPERATION MANUAL FXLQ20P5VEB FXLQ25P5VEB FXLQ32P5VEB FXLQ40P5VEB FXLQ50P5VEB FXLQ63P5VEB System air conditioners 01_4PEN323720 1E book Page 1 Tuesday October 3 2017 4 34 PM...

Page 2: ...x L N L N P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 3 1 4 2 L N L N L N L N 2 1 2 3 7 9 8 10 4 5 6 L N IN D OUT D F1 F2 F1 F2 Control box L N P1 P...

Page 3: ...ajo v skladu z na imi navodili on vastavuses j rgmis t e standardi te ga v i teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele atitinka emiau nurodytus standartus ir a...

Page 4: ...corrosive gas like sulphurous gas exists Copper tubing and brazed spots may corrode Where volatile flammable gas like thinner or gasoline is used Where machines generating electromagnetic waves exist...

Page 5: ...9 1 7 6 3 0 11 58 FXLQ63P5VEB 4 9 2 2 8 0 11 59 1x 1x 4x 1x 1x 1x 1 2 3 5 6 1x 8 8x 7 4 Tick 3 when checked Is the indoor unit fixed firmly The unit may drop vibrate or make noise Is the gas leak test...

Page 6: ...This is to prevent image interference and noise in those electrical appliances Noise may be generated depending on the conditions under which the electric wave is generated even if 1 meter is kept Whe...

Page 7: ...sten to the floor with a field supplied floor fastener Wallmounted installation 1 Positioning of holes for fastening to the wall Unit of measurement mm 2 The legs can be removed if the indoor unit is...

Page 8: ...leaks When connecting the flare nut coat the flare inner surface with ether oil or ester oil and initially tighten 3 or 4 turns by hand before tightening firmly Finally insulate as shown in the figure...

Page 9: ...um pump which can evacuate to 100 7 kPa 5 Torr 755 mm Hg Drain piping work Rig the drain pipe as shown below Improperly rigged piping could lead to leaks and eventually wet furniture and belongings 1...

Page 10: ...sive force to the terminal Use torques according to the table below When attaching the control box lid make sure not to pinch any wires and make sure that the wiring does not come in contact with the...

Page 11: ...Circuit Amps A MFA Maximum Fuse Amps A FLA Full Load Amps A NOTE For details refer to Electrical data in the technical data book Power supply wiring Model Field fuses Wire Size 20 63 16 A H05VV U3G L...

Page 12: ...put from outside to terminals T1 and T2 of the terminal board remote controller to transmission wiring 2 Actuation The following table explains forced off and on off operations in response to input A...

Page 13: ...terminals T1 T2 U4 or UH The power on the outdoor unit is off The outdoor unit has not been wired for power supply Incorrect transmission no display The power on the indoor unit is off The indoor uni...

Page 14: ...onsumption even if the system is not operating The remote controller display is turned off when the main power switch is turned off Disposal requirements Your product and the batteries supplied with t...

Page 15: ...C RECEIVER F U FU FOR CHARACTERISTICS REFER TOPCBINSIDE YOUR UNIT FUSE S C LIMIT SWITCH FG CONNECTOR FRAMEGROUND S L FLOAT SWITCH H HARNESS S NPH PRESSURESENSOR HIGH H P LED V L PILOT LAMP LIGHT EMITT...

Page 16: ...7 1 2019 12 Copyright 2019 Daikin DAIKIN ISITMA VE SO UTMA S STEMLER SAN T C A G lsuyu Mahallesi Fevzi akmak Caddesi Bur ak Sokak No 20 34848 Maltepe STANBUL T RK YE Tel 0216 453 27 00 Faks 0216 671 0...

Reviews: