Installation and operation manual

9

Wiring examples

Fit the power supply wiring of each unit with a switch and fuse as
shown in figure 1.

Complete system example (3 systems)

When using 1 remote controller for 1 indoor unit. (Normal operation)
(See figure 2)

For group control or use with 2 remote controllers (See figure 4)

When including BS unit (See figure 3)

PRECAUTIONS

A single switch can be used to supply power to units on the
same system. However, branch switches and branch circuit
breakers must be selected carefully.

For a group control remote controller, choose the remote
controller that suits the indoor unit which has the most functions.

Do not ground the equipment on gas pipes, water pipes,
lightning rods or crossground with telephones. Improper
grounding could result in electric shock.

Field setting

Field setting must be made on the remote controller in function of the
installation condition.

Setting can be made by changing the "Mode number", "First
code No." and "Second code No.".

For setting and operation, refer to the "Field settings" in the
installation manual of the remote controller.

Control by 2 Remote Controllers (Controlling 1 indoor 
unit by 2 remote controllers)

When using 2 remote controllers, one must be set to "MAIN" and the
other to "SUB". Refer to the installatoin manual of the remote
controller.

Computerised control (forced off and on/off operation)

1

Wire specifications and how to perform wiring
- Connect input from outside to terminals T1 and T2 of the 

terminal board (remote controller to transmission wiring).

2

Actuation
- The following table explains "forced off" and "on/off 

operations" in response to input A.

3

How to select forced off and on/off operation
- Turn the power on and then use the remote controller to 

select operation.

- Set the remote controller to the field set mode. For details, 

refer to the chapter "How to set in the field", in the remote 
controller manual.

- When in the field set mode, select mode No. 12, then set the 

first code No. to "1". Then set second code (position) No. to 
"01" for forced off and to "02" for on/off operation. (forced off 
at factory set.)

Centralized control

For centralized control, it is necessary to designate the group No. For
details, refer to the manual of each optional controller for centralized
control.

1

Power supply

6

BS unit (only for heat 
recovery system)

2

Main switch

3

Outdoor unit

7

Power supply wiring

4

Indoor unit

8

Transmission wiring

5

Remote controller

9

Switch

10

Fuse

1

Outdoor unit

2

Indoor unit

3

Remote controller (optional accessories)

4

Most downstream indoor unit

5

For use with 2 remote controllers

6

BS unit

Wire specification

Sheathed vinyl cord or cable (2 wire)

Gauge

0.75-1.25 mm

2

Length

Maximum 100 m

External terminal

Contact that can ensure the minimum 
applicable load of 15 V DC, 10 mA

Forced off

on/off operation

Input "on" stops operation 

input off 

Ü

 on: turns on the unit 

(impossible by remote controllers)

Input "off" enables control 

input on 

Ü

 off: turns off the unit by 

remote controller

F2

T1

T2

FORCED
OFF

Input A

01_4PEN323720-1E.book  Page 9  Tuesday, October 3, 2017  4:34 PM

Summary of Contents for FXLQ20P5VEB

Page 1: ...INSTALLATION AND OPERATION MANUAL FXLQ20P5VEB FXLQ25P5VEB FXLQ32P5VEB FXLQ40P5VEB FXLQ50P5VEB FXLQ63P5VEB System air conditioners 01_4PEN323720 1E book Page 1 Tuesday October 3 2017 4 34 PM...

Page 2: ...x L N L N P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 3 1 4 2 L N L N L N L N 2 1 2 3 7 9 8 10 4 5 6 L N IN D OUT D F1 F2 F1 F2 Control box L N P1 P...

Page 3: ...ajo v skladu z na imi navodili on vastavuses j rgmis t e standardi te ga v i teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele atitinka emiau nurodytus standartus ir a...

Page 4: ...corrosive gas like sulphurous gas exists Copper tubing and brazed spots may corrode Where volatile flammable gas like thinner or gasoline is used Where machines generating electromagnetic waves exist...

Page 5: ...9 1 7 6 3 0 11 58 FXLQ63P5VEB 4 9 2 2 8 0 11 59 1x 1x 4x 1x 1x 1x 1 2 3 5 6 1x 8 8x 7 4 Tick 3 when checked Is the indoor unit fixed firmly The unit may drop vibrate or make noise Is the gas leak test...

Page 6: ...This is to prevent image interference and noise in those electrical appliances Noise may be generated depending on the conditions under which the electric wave is generated even if 1 meter is kept Whe...

Page 7: ...sten to the floor with a field supplied floor fastener Wallmounted installation 1 Positioning of holes for fastening to the wall Unit of measurement mm 2 The legs can be removed if the indoor unit is...

Page 8: ...leaks When connecting the flare nut coat the flare inner surface with ether oil or ester oil and initially tighten 3 or 4 turns by hand before tightening firmly Finally insulate as shown in the figure...

Page 9: ...um pump which can evacuate to 100 7 kPa 5 Torr 755 mm Hg Drain piping work Rig the drain pipe as shown below Improperly rigged piping could lead to leaks and eventually wet furniture and belongings 1...

Page 10: ...sive force to the terminal Use torques according to the table below When attaching the control box lid make sure not to pinch any wires and make sure that the wiring does not come in contact with the...

Page 11: ...Circuit Amps A MFA Maximum Fuse Amps A FLA Full Load Amps A NOTE For details refer to Electrical data in the technical data book Power supply wiring Model Field fuses Wire Size 20 63 16 A H05VV U3G L...

Page 12: ...put from outside to terminals T1 and T2 of the terminal board remote controller to transmission wiring 2 Actuation The following table explains forced off and on off operations in response to input A...

Page 13: ...terminals T1 T2 U4 or UH The power on the outdoor unit is off The outdoor unit has not been wired for power supply Incorrect transmission no display The power on the indoor unit is off The indoor uni...

Page 14: ...onsumption even if the system is not operating The remote controller display is turned off when the main power switch is turned off Disposal requirements Your product and the batteries supplied with t...

Page 15: ...C RECEIVER F U FU FOR CHARACTERISTICS REFER TOPCBINSIDE YOUR UNIT FUSE S C LIMIT SWITCH FG CONNECTOR FRAMEGROUND S L FLOAT SWITCH H HARNESS S NPH PRESSURESENSOR HIGH H P LED V L PILOT LAMP LIGHT EMITT...

Page 16: ...7 1 2019 12 Copyright 2019 Daikin DAIKIN ISITMA VE SO UTMA S STEMLER SAN T C A G lsuyu Mahallesi Fevzi akmak Caddesi Bur ak Sokak No 20 34848 Maltepe STANBUL T RK YE Tel 0216 453 27 00 Faks 0216 671 0...

Reviews: