Installation and operation manual

7

Electric wiring work

General instructions

Be sure to use a dedicated power supply. Never use a power
supply shared by another appliance.

All field supplied parts and materials and electric works must be
conform to local and national regulations.

All wiring must be performed by an authorized electrician.

Use copper wire only.

Follow the "Wiring diagram" attached to the unit to wire the
outdoor unit, indoor units and the remote controller. For details
how to mount the remote controller, refer to the "Installation
manual of the remote controller".

Attach the earth leakage circuit breaker and fuse to the power
supply line.

A main switch or other means for disconnection, having a
contact separation in all poles, must be incorporated in the fixed
wiring in accordance with relevant local and national legislation.
Note that the operation will restart automatically if the main
power supply is turned off and then turned back on again.

This system consists of multiple indoor units. Mark each indoor
unit as unit A, unit B..., and be sure the terminal block wiring to
the outdoor unit and BS unit are properly matched. If wiring and
piping between the outdoor unit and an indoor unit are
mismatched, the system may cause a malfunction.

Be sure to ground the air conditioner.

Do not connect the ground wire to:
- gas pipes: might cause explosions or fire if gas leaks.
- telephone ground wires or lightning rods: might cause

abnormally high electric potential in the ground during 
lightning storms.

- plumbing pipes: no grounding effect if hard vinyl piping is 

used.

Make sure electrical wires are stripped
equally.

Use an all-pole disconnection type breaker
with at least 3mm between the contact point
gaps.

If the supply cord is damaged, it must be replaced by the
manufacturer, a service agent or similarly qualified persons in
order to avoid a hazard.

Precautions

1

Observe the notes mentioned below when wiring to the power
supply terminal board.
- Use a round crimp-style terminal for insulation sleeve for 

connection to the terminal block for wiring the units. When 
none are available, follow the instructions below.

- Do not connect wires of different gauge to the same power 

supply terminal. (Looseness in the connection may cause 
overheating.)

- When connecting wires of the same dimension, connect 

them according to the figure.

Use the specified electric wire. Connect the wire securely to the
terminal. Lock the wire down without applying excessive force to
the terminal. Use torques according to the table below.

- When attaching the control box lid, make sure not to pinch 

any wires and make sure that the wiring does not come in 
contact with the piping and sharp edges.

- After all wiring connections are done, fill in any gaps in the 

casing wiring holes with putty or insulation material (field 
supply) thus to prevent small animals or dirt from entering the 
unit from outside and causing short circuits in the control box.

2

Keep total current of crossover wiring between indoor units less
than 12 A. Branch the line outside the terminal board of the unit
in accordance with electrical equipment standards, when using
two power wiring greater than 2 mm

2

 (Ø1.6).

The branch must be sheathed in order to provide an equal or
greater degree of insulation as power supply wiring itself.

3

Do not connect wires of different dimensions to the same
grounding terminal. Looseness in the connection may
deteriorate the protection.

4

Remote controller cords and wires connecting the units should
be located at least 50 mm away from power supply wiring. Not
following this guideline may result in malfunction due to
electrical noise.

5

For the remote controller wiring, refer to the "Installation manual
of the remote controller" supplied with the remote controller.

6

Use only specified wires and tightly connect wires to the
terminals. Be careful that wires do not place external stress on
the terminals. Keep wiring in neat order so that they do not
obstruct other equipment such as popping open the control box
cover. Make sure the cover closes tight. Incomplete connections
could result in overheating, and in the worse case, electric shock
or fire.

7

Fasten wiring with clamps (accessory part).

DANGER: ELECTRICAL SHOCK

Switch off all power supply before removing the switch box
service panel or before making any connections or
touching electrical parts.

To avoid electric shock, be sure to disconnect the power
supply 1 minute or more before servicing the electrical
parts. Even after 1 minute, always measure the voltage at
the terminals of main circuit capacitors or electrical parts
and, before touching, be sure that those voltages are
50 V DC or less.

When service panels are removed, live parts can be easily
touched by accident.
Never leave the unit unattended during installation or
servicing when service panel is removed.

Terminal

Size

Tightening 

torque (N•m)

Terminal block for remote controller

M3.5

0.79~0.97

Power supply terminal block

M4

1.18~1.44

Ground terminal

M4

1.44~1.94

1

2

3

1

Round crimp-style terminal

2

Attach insulation sleeve

3

Wiring

01_4PEN323720-1E.book  Page 7  Tuesday, October 3, 2017  4:34 PM

Summary of Contents for FXLQ20P5VEB

Page 1: ...INSTALLATION AND OPERATION MANUAL FXLQ20P5VEB FXLQ25P5VEB FXLQ32P5VEB FXLQ40P5VEB FXLQ50P5VEB FXLQ63P5VEB System air conditioners 01_4PEN323720 1E book Page 1 Tuesday October 3 2017 4 34 PM...

Page 2: ...x L N L N P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 3 1 4 2 L N L N L N L N 2 1 2 3 7 9 8 10 4 5 6 L N IN D OUT D F1 F2 F1 F2 Control box L N P1 P...

Page 3: ...ajo v skladu z na imi navodili on vastavuses j rgmis t e standardi te ga v i teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele atitinka emiau nurodytus standartus ir a...

Page 4: ...corrosive gas like sulphurous gas exists Copper tubing and brazed spots may corrode Where volatile flammable gas like thinner or gasoline is used Where machines generating electromagnetic waves exist...

Page 5: ...9 1 7 6 3 0 11 58 FXLQ63P5VEB 4 9 2 2 8 0 11 59 1x 1x 4x 1x 1x 1x 1 2 3 5 6 1x 8 8x 7 4 Tick 3 when checked Is the indoor unit fixed firmly The unit may drop vibrate or make noise Is the gas leak test...

Page 6: ...This is to prevent image interference and noise in those electrical appliances Noise may be generated depending on the conditions under which the electric wave is generated even if 1 meter is kept Whe...

Page 7: ...sten to the floor with a field supplied floor fastener Wallmounted installation 1 Positioning of holes for fastening to the wall Unit of measurement mm 2 The legs can be removed if the indoor unit is...

Page 8: ...leaks When connecting the flare nut coat the flare inner surface with ether oil or ester oil and initially tighten 3 or 4 turns by hand before tightening firmly Finally insulate as shown in the figure...

Page 9: ...um pump which can evacuate to 100 7 kPa 5 Torr 755 mm Hg Drain piping work Rig the drain pipe as shown below Improperly rigged piping could lead to leaks and eventually wet furniture and belongings 1...

Page 10: ...sive force to the terminal Use torques according to the table below When attaching the control box lid make sure not to pinch any wires and make sure that the wiring does not come in contact with the...

Page 11: ...Circuit Amps A MFA Maximum Fuse Amps A FLA Full Load Amps A NOTE For details refer to Electrical data in the technical data book Power supply wiring Model Field fuses Wire Size 20 63 16 A H05VV U3G L...

Page 12: ...put from outside to terminals T1 and T2 of the terminal board remote controller to transmission wiring 2 Actuation The following table explains forced off and on off operations in response to input A...

Page 13: ...terminals T1 T2 U4 or UH The power on the outdoor unit is off The outdoor unit has not been wired for power supply Incorrect transmission no display The power on the indoor unit is off The indoor uni...

Page 14: ...onsumption even if the system is not operating The remote controller display is turned off when the main power switch is turned off Disposal requirements Your product and the batteries supplied with t...

Page 15: ...C RECEIVER F U FU FOR CHARACTERISTICS REFER TOPCBINSIDE YOUR UNIT FUSE S C LIMIT SWITCH FG CONNECTOR FRAMEGROUND S L FLOAT SWITCH H HARNESS S NPH PRESSURESENSOR HIGH H P LED V L PILOT LAMP LIGHT EMITT...

Page 16: ...7 1 2019 12 Copyright 2019 Daikin DAIKIN ISITMA VE SO UTMA S STEMLER SAN T C A G lsuyu Mahallesi Fevzi akmak Caddesi Bur ak Sokak No 20 34848 Maltepe STANBUL T RK YE Tel 0216 453 27 00 Faks 0216 671 0...

Reviews: