Installation and operation manual

3

FXFQ20~125AVEB

VRV System air conditioners

3P320142-1A – 2012.10

4

Use suspension bolts for installation. Check whether the
ceiling is strong enough to support the weight of the indoor
unit. If there is a risk, reinforce the ceiling before installing
the unit.

(The installation pitch is marked on the paper pattern for
installation. Refer to it to check for points requiring reinforcing.)
Space required for installation see 

figure 2

 (

 = air flow

direction)

P

REPARATIONS

 

BEFORE

 

INSTALLATION

1.

Relation of ceiling opening to unit and suspension bolt
position. 

(See figure 3)

Use the installation guide (delivered with the unit) for exact
vertical positioning of the unit.

Installation is possible when opening dimensions are as follows.
When installing the unit within the frame for fixing ceiling
materials. 

(See figure 4)

2.

Make the ceiling opening needed for installation where
applicable. (For existing ceilings.)

Refer to the paper pattern for installation for the ceiling opening
dimensions.

Create the ceiling opening required for installation. From the side
of the opening to the casing outlet, implement the refrigerant and
drain piping and wiring for remote controller (unnecessary for
wireless type) and indoor-outdoor unit casing outlet. Refer to
each piping or wiring section.

After making an opening in the ceiling, it may be necessary to
reinforce ceiling beams to keep the ceiling level and to prevent it
from vibrating. Consult the builder for details.

3.

Install the suspension bolts. (use either a W3/8 or M10 size
bolt.)

Use anchors for existing ceilings, and a sunken insert, sunken
anchors or other field supplied parts for new ceilings to reinforce the
ceiling in order to bear the weight of the unit. Adjust clearance from
the ceiling before proceeding further.

Installation example see 

figure 5

.

NOTE

Air flow directions as shown in 

figure 1

 merely

serve as examples of possible air flow directions.

1

Air discharge

2

Air inlet

NOTE

Leave 200 mm or more space where marked with *; on
sides where the air outlet is closed.

Model

H

FXFQ20~63

214

100

256

FXFQ125

298

1

Refrigerant piping

2

Suspension bolt (x4)

3

Hanger bracket

4

False ceiling

5

Suspension bolt pitch

6

Indoor unit

7

Ceiling opening

8

Decoration panel

Apply the short side of the 
installation guide in case of 

normal installation

Apply the long side of the 
installation guide in case of 

installation with fresh air 
intake kit

1

2

1

2

Apply the long side of the 
installation guide after removal 
of the tear-off tab in case of 

installation with self 
cleaning decoration panel

1

Lower ceiling surface

2

Underside of the unit

1

Dimensions inside frame

2

Opening dimension inside the frame for ceiling

3

Frame

4

Ceiling material

5

Ceiling opening dimension

6

Ceiling-panel overlapping dimension

NOTE

Installation is possible with a ceiling dimension of
910 mm (marked with *). However, to achieve a ceiling-
panel overlapping dimension of 20 mm, the spacing
between the ceiling and the unit should be 35 mm or
less. If the spacing between ceiling and the unit is over
35 mm, attach ceiling material to the part or recover
the ceiling.

1

Ceiling slab

2

Anchor

3

Long nut or turn-buckle

4

Suspension bolt

5

False ceiling

NOTE

All the above parts are field supplied.

For other installation than standard installation, contact
your dealer for details.

1

2

Summary of Contents for FXFQ20AVEB

Page 1: ...VRV System air conditioners INSTALLATION AND OPERATION MANUAL FXFQ20AVEB FXFQ25AVEB FXFQ32AVEB FXFQ40AVEB FXFQ50AVEB FXFQ63AVEB FXFQ80AVEB FXFQ100AVEB FXFQ125AVEB System air conditioners...

Page 2: ...4 2 1 950 950 860 910 840 780 860 910 4 125 130 0 3 3 1 1 840 910 840 910 1 1 5 35 35 3 5 0 75 675 850 175 300 mm 1 1 5 m 2 3 1 5 6 100 mm 1 0 675 mm 1 3 3 1 2 4 100 4 3 5 1 2 2 2 1 4 70 90 mm 0 15 m...

Page 3: ...es valorado positivamente por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A e com o pare...

Page 4: ...ms or for commercial use by lay persons Do not install or operate the unit in rooms mentioned below Places with mineral oil or filled with oil vapour or spray like in kitchens Plastic parts may deteri...

Page 5: ...ke adequate measures Keep indoor unit outdoor unit inter unit wiring and remote controller at least 1 meter away from televisions and radios This is to prevent image interference and noise in those el...

Page 6: ...ing ceilings and a sunken insert sunken anchors or other field supplied parts for new ceilings to reinforce the ceiling in order to bear the weight of the unit Adjust clearance from the ceiling before...

Page 7: ...piping Otherwise this can sometimes result in water leakage Before rigging tubes check which type of refrigerant is used Use a pipe cutter and flare suitable for the used refrigerant To prevent dust m...

Page 8: ...ket between drain hose and unit body Wrap the supplied large sealing pad over the metal clamp and drain hose to insulate and fix it with clamps Insulate the complete drain piping inside the building f...

Page 9: ...er supply line A main switch or other means for disconnection having a contact separation in all poles must be incorporated in the fixed wiring in accordance with relevant local and national legislati...

Page 10: ...material field supply thus to prevent small animals or dirt from entering the unit from outside and causing short circuits in the control box 2 Keep total current of crossover wiring between indoor u...

Page 11: ...aning display indications Long life filter Light 2 500 hrs Heavy 1 250 hrs 2 Thermostat sensor selection Use both the unit sensor or remotesensorif installed AND the remote controller sensor See note...

Page 12: ...e obtaining access to terminal devices all power supply circuits must be interrupted To clean the air conditioner be sure to stop operation and turn the power switch off Otherwise an electric shock an...

Page 13: ...ration panel Hold the suction grille open at 45 degrees and lift it upward to unhook it from the decoration panel 3 Remove the air filter actions 2 to 4 in the illustration Refer to procedure step 2 i...

Page 14: ...adaptor for wiring X35A Connector group control adaptor X36A Connector self cleaning decoration panel X38A Connector multi tenant Notes 1 Terminal block Connector Field wiring 2 In case of using a cen...

Page 15: ...IN D OUT D F1 F2 F1 F2 Control box LN P1 P2 P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 P1 P2 P1 P2 1 4 2 3 5 IN D OUT D F1 F2 F1 F2 Control box LN P1 P2 P1 P2 F1...

Page 16: ...3P320142 1A 2012 10 Copyright 2012 Daikin...

Reviews: